CHIMNEYS AND VENTS


           504.2.14 Table interpolation. Interpolation shall be per-  504.3.3 Connectors with  longer  lengths. Connectors
           mitted in calculating capacities for vent dimensions that  with longer horizontal lengths than those listed in Section
           fall between the table entries.                       504.3.2 are permitted under the following conditions:
           504.2.15  Extrapolation  prohibited. Extrapolation      1. The maximum capacity (FAN Max or NAT Max) of
           beyond the table entries shall not be permitted.          the vent connector shall be reduced 10 percent for
                                                                     each additional multiple  of the length  allowed by
           504.2.16 Engineering calculations. For vent heights less  Section 504.3.2. For example, the maximum length
           than 6 feet (1829 mm) and greater than shown in the       listed in Table 504.3.2 for a 4-inch (102 mm) con-
           tables, engineering methods shall be used to calculate vent  nector is 6 feet (1829 mm). With a connector length
           capacities.                                               greater than 6 feet (1829 mm) but not exceeding 12
                                                                     feet (3658 mm), the maximum capacity must be
           504.2.17 Height entries. Where the actual height of a
           vent falls  between  entries in the height column  of  the  reduced by 10 percent (0.90 × maximum vent con-
           applicable table in Tables 504.2(1) through 504.2(6),     nector capacity).  With a  connector length  greater
           either interpolation shall be used or the lower appliance  than 12 feet (3658 mm) but not exceeding 18 feet
           input rating shown in the table entries shall be used for  (5486 mm), the maximum capacity must be reduced
           FAN MAX and NAT MAX  column values and the                by 20 percent (0.80 × maximum vent capacity).
           higher appliance input rating shall be used for the FAN  2. For a connector serving a fan-assisted appliance, the
           MIN column values.                                        minimum capacity (FAN Min) of the connector
                                                                     shall be determined by referring to the correspond-
         504.3  Application of multiple appliance vent Tables        ing single-appliance table. For Type B double-wall
         504.3(1) through 504.3(7). The application of Tables        connectors, Table 504.2(1) shall be used. For single-
         504.3(1) through 504.3(7b) shall be  subject to the  require-  wall connectors, Table 504.2(2) shall be used. The
         ments of Sections 504.3.1 through 504.3.28.
                                                                     height (H) and lateral (L) shall be measured accord-
           504.3.1 Vent obstructions. These venting tables shall not  ing to the procedures for a single-appliance vent, as
           be  used where obstructions, as described  in Section     if the other appliances were not present.
           503.15, are installed in the venting system. The installa-  504.3.4 Vent connector manifold. Where the vent con-
           tion of vents serving listed appliances with vent dampers  nectors are combined prior to entering the vertical portion
           shall be in accordance with the appliance manufacturer’s  of the common vent to form a common vent manifold, the
           instructions or in accordance with the following:     size of the common vent manifold and the common vent
                                                                 shall be determined  by  applying a  10-percent reduction
              1. The maximum capacity of the vent connector shall  (0.90 × maximum common vent capacity) to the common
                be determined using the NAT Max column.          vent capacity part of the common vent tables. The length
              2. The maximum capacity of the vertical vent or chim-  of the common vent connector manifold (L ) shall not
                                                                                                      m
                                                                        1
                ney shall be determined using the FAN+NAT col-   exceed 1 /  feet for each inch (18 mm per mm) of common
                                                                         2
                umn where the second appliance is a  fan-assisted  vent connector manifold diameter (D).
                appliance, or the NAT+NAT column where the sec-                  TABLE 504.3.2
                ond appliance is equipped with a draft hood.            MAXIMUM VENT CONNECTOR LENGTH
                                                                                           CONNECTOR MAXIMUM
              3. The minimum capacity shall be determined as if the  CONNECTOR DIAMETER   HORIZONTAL LENGTH (feet)
                                                                        (inches)
                appliance were a fan-assisted appliance.
                                                                                                   1
                                                                          3                       4 / 2
                   3.1. The minimum capacity of the vent connector
                      shall be determined using the FAN Min col-          4                        6
                                                                                                   1
                      umn.                                                5                       7 / 2
                   3.2. The FAN+FAN column shall be used where            6                        9
                      the second appliance is a fan-assisted appli-       7                      10 / 2
                                                                                                   1
                      ance, and the  FAN+NAT column  shall  be            8                       12
                      used where the second appliance is equipped
                                                                                                   1
                      with a draft hood, to determine whether the         9                      13 / 2
                      vertical vent or chimney configuration is not       10                      15
                      permitted (NA). Where the vent configura-
                      tion is NA, the vent configuration shall not        12                      18
                      be permitted and an alternative venting con-        14                      21
                      figuration shall be utilized.                       16                      24
           504.3.2 Connector length limit. The vent connector shall       18                      27
           be routed to the vent utilizing the shortest possible route.   20                      30
           Except as provided in Section 504.3.3, the maximum vent
                                          1
           connector horizontal length shall be 1 /  feet for each inch   22                      33
                                           2
           (18 mm per mm) of connector diameter as shown in Table         24                      36
           504.3.2.
                                                              For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.