CHIMNEYS AND VENTS
504.2.14 Table interpolation. Interpolation shall be per- 504.3.3 Connectors with longer lengths. Connectors
mitted in calculating capacities for vent dimensions that with longer horizontal lengths than those listed in Section
fall between the table entries. 504.3.2 are permitted under the following conditions:
504.2.15 Extrapolation prohibited. Extrapolation 1. The maximum capacity (FAN Max or NAT Max) of
beyond the table entries shall not be permitted. the vent connector shall be reduced 10 percent for
each additional multiple of the length allowed by
504.2.16 Engineering calculations. For vent heights less Section 504.3.2. For example, the maximum length
than 6 feet (1829 mm) and greater than shown in the listed in Table 504.3.2 for a 4-inch (102 mm) con-
tables, engineering methods shall be used to calculate vent nector is 6 feet (1829 mm). With a connector length
capacities. greater than 6 feet (1829 mm) but not exceeding 12
feet (3658 mm), the maximum capacity must be
504.2.17 Height entries. Where the actual height of a
vent falls between entries in the height column of the reduced by 10 percent (0.90 × maximum vent con-
applicable table in Tables 504.2(1) through 504.2(6), nector capacity). With a connector length greater
either interpolation shall be used or the lower appliance than 12 feet (3658 mm) but not exceeding 18 feet
input rating shown in the table entries shall be used for (5486 mm), the maximum capacity must be reduced
FAN MAX and NAT MAX column values and the by 20 percent (0.80 × maximum vent capacity).
higher appliance input rating shall be used for the FAN 2. For a connector serving a fan-assisted appliance, the
MIN column values. minimum capacity (FAN Min) of the connector
shall be determined by referring to the correspond-
504.3 Application of multiple appliance vent Tables ing single-appliance table. For Type B double-wall
504.3(1) through 504.3(7). The application of Tables connectors, Table 504.2(1) shall be used. For single-
504.3(1) through 504.3(7b) shall be subject to the require- wall connectors, Table 504.2(2) shall be used. The
ments of Sections 504.3.1 through 504.3.28.
height (H) and lateral (L) shall be measured accord-
504.3.1 Vent obstructions. These venting tables shall not ing to the procedures for a single-appliance vent, as
be used where obstructions, as described in Section if the other appliances were not present.
503.15, are installed in the venting system. The installa- 504.3.4 Vent connector manifold. Where the vent con-
tion of vents serving listed appliances with vent dampers nectors are combined prior to entering the vertical portion
shall be in accordance with the appliance manufacturer’s of the common vent to form a common vent manifold, the
instructions or in accordance with the following: size of the common vent manifold and the common vent
shall be determined by applying a 10-percent reduction
1. The maximum capacity of the vent connector shall (0.90 × maximum common vent capacity) to the common
be determined using the NAT Max column. vent capacity part of the common vent tables. The length
2. The maximum capacity of the vertical vent or chim- of the common vent connector manifold (L ) shall not
m
1
ney shall be determined using the FAN+NAT col- exceed 1 / feet for each inch (18 mm per mm) of common
2
umn where the second appliance is a fan-assisted vent connector manifold diameter (D).
appliance, or the NAT+NAT column where the sec- TABLE 504.3.2
ond appliance is equipped with a draft hood. MAXIMUM VENT CONNECTOR LENGTH
CONNECTOR MAXIMUM
3. The minimum capacity shall be determined as if the CONNECTOR DIAMETER HORIZONTAL LENGTH (feet)
(inches)
appliance were a fan-assisted appliance.
1
3 4 / 2
3.1. The minimum capacity of the vent connector
shall be determined using the FAN Min col- 4 6
1
umn. 5 7 / 2
3.2. The FAN+FAN column shall be used where 6 9
the second appliance is a fan-assisted appli- 7 10 / 2
1
ance, and the FAN+NAT column shall be 8 12
used where the second appliance is equipped
1
with a draft hood, to determine whether the 9 13 / 2
vertical vent or chimney configuration is not 10 15
permitted (NA). Where the vent configura-
tion is NA, the vent configuration shall not 12 18
be permitted and an alternative venting con- 14 21
figuration shall be utilized. 16 24
504.3.2 Connector length limit. The vent connector shall 18 27
be routed to the vent utilizing the shortest possible route. 20 30
Except as provided in Section 504.3.3, the maximum vent
1
connector horizontal length shall be 1 / feet for each inch 22 33
2
(18 mm per mm) of connector diameter as shown in Table 24 36
504.3.2.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
98 2018 INTERNATIONAL FUEL GAS CODE ®