CHIMNEYS AND VENTS



               504.3.5 Common vertical  vent  offset. Where the  com-  est draft hood outlet or flue collar entering that segment
               mon vertical vent is offset, the maximum capacity of the  and the centerline of the next higher interconnection tee.
               common vent shall be reduced in accordance with Section  504.3.14 Multistory lowest  portion  sizing.  The size of
               504.3.6. The horizontal length of the common vent offset  the lowest connector and of the vertical vent leading to the
                                  1
               (L ) shall not exceed 1 /  feet for each inch (18 mm per  lowest interconnection of a multistory system shall be in
                                   2
                 o
               mm) of common vent diameter (D). Where multiple off-  accordance with Table 504.2(1) or 504.2(2) for available
               sets occur in a common vent, the total horizontal length of  total height (H) up to the lowest interconnection.
                                              1
               all offsets combined shall not exceed 1 /  feet for each inch
                                               2
               (18 mm per mm) of common vent diameter (D).          504.3.15 Multistory common vents. Where used in mul-
                                                                    tistory systems, vertical common vents shall be Type B
               504.3.6 Elbows in vents. For each elbow up to and includ-  double wall and shall be installed with a listed vent cap.
               ing 45 degrees (0.79 rad) in the common vent, the maxi-
               mum common vent capacity listed in the venting tables  504.3.16 Multistory common  vent offsets.  Offsets in
               shall be reduced by 5 percent. For each elbow greater than  multistory common vent systems shall be limited to a sin-
               45 degrees (0.79 rad) up to and including 90 degrees (1.57  gle offset in each system, and systems with an offset shall
               rad), the maximum common vent capacity listed in the  comply with all of the following:
               venting tables shall be reduced by 10 percent.          1. The offset angle shall not exceed 45 degrees (0.79
                                                                         rad) from vertical.
               504.3.7 Elbows in connectors. The vent connector capac-
               ities listed in the common vent sizing tables include allow-  2. The horizontal length of the offset shall not exceed
                                                                          1
               ance  for two 90-degree (1.57 rad) elbows. For each       1 /  feet for each inch (18 mm per mm) of common
                                                                           2
               additional elbow up  to and including 45 degrees (0.79    vent diameter of the segment in which the offset is
               rad), the maximum vent connector capacity listed in the   located.
               venting tables shall  be reduced by 5 percent.  For each  3. For the segment of the common vertical vent con-
               elbow greater than 45 degrees (0.79 rad) up to and includ-  taining the offset, the common vent capacity listed in
               ing 90 degrees (1.57 rad), the maximum vent connector     the common venting tables shall be reduced by 20
               capacity listed in the venting tables shall be reduced by 10  percent (0.80 × maximum common vent capacity).
               percent.
                                                                       4. A multistory common vent shall not be reduced in
               504.3.8 Common  vent minimum  size. The cross-sec-        size above the offset.
               tional area of the common vent shall be equal to or greater
                                                                    504.3.17 Vertical  vent maximum size.  Where two  or
               than the cross-sectional area of the largest connector.
                                                                    more appliances are connected to a vertical vent or chim-
               504.3.9 Common vent fittings. At the point where tee or  ney, the flow area of the largest section of vertical vent or
               wye fittings connect to a common vent, the opening size of  chimney shall not exceed seven times the smallest listed
               the fitting shall be equal to the size of the common vent.  appliance categorized vent areas, flue collar area or draft
               Such fittings shall not be prohibited from having reduced-  hood outlet area unless  designed in accordance with
               size openings at the point of connection of appliance vent  approved engineering methods.
               connectors.
                                                                    504.3.18 Multiple input rate appliances. For appliances
                  504.3.9.1 Tee and wye fittings. Tee and wye fittings  with more than one input rate, the minimum vent connec-
                  connected to a common gas vent shall be considered to  tor capacity (FAN Min) determined from the tables shall
                  be part of the common gas vent and shall be con-  be less  than  the lowest appliance  input  rating, and the
                  structed of materials consistent with that of the com-  maximum vent connector  capacity  (FAN Max or  NAT
                  mon gas vent.                                     Max) determined from the tables shall be greater than the
               504.3.10 High-altitude installations. Sea-level input rat-  highest appliance input rating.
               ings shall be used when determining maximum capacity  504.3.19 Liner system sizing  and  connections.  Listed,
               for high-altitude installation. Actual input (derated for alti-  corrugated metallic chimney liner systems in masonry
               tude) shall be used for determining minimum capacity for  chimneys shall be sized by using Table 504.3(1) or
               high-altitude installation.                          504.3(2) for Type B vents,  with the maximum capacity
               504.3.11 Connector rise measurement. Connector rise  reduced by 20 percent (0.80 × maximum capacity) and the
               (R) for each appliance connector shall be measured from  minimum  capacity as shown in Table 504.3(1) or
               the draft hood outlet or flue collar to the centerline where  504.3(2). Corrugated metallic liner systems installed with
               the vent gas streams come together.                  bends or offsets shall have their maximum capacity further
                                                                    reduced in accordance with Sections 504.3.5 and 504.3.6.
               504.3.12 Vent height measurement. For multiple appli-
                                                                    The 20-percent reduction for corrugated metallic chimney
               ances all located on one floor, available total height (H)
               shall be measured from  the  highest draft hood  outlet or  liner  systems includes  an  allowance for one long-radius
               flue collar up to the level of the outlet of the common vent.  90-degree (1.57 rad) turn at the bottom of the liner. Where
                                                                    double-wall connectors are required, tee and wye fittings
               504.3.13 Multistory height measurement. For multistory  used to connect to the common vent chimney liner shall be
               installations, available total height (H) for each segment of  listed double-wall fittings. Connections between chimney
               the system shall be the vertical distance between the high-