Page 35 - 2018_IFGC
P. 35

GENERAL REGULATIONS



              For purposes of this calculation, an infiltration rate  ducts with the outdoors or spaces that freely communicate
           greater than 0.60 ACH shall not be used in Equations 3-1  with the outdoors.
           and 3-2.                                                Where directly communicating with the outdoors,  or
           304.5.3 Indoor opening size and location. Openings used  where communicating with the outdoors through vertical
           to connect indoor spaces  shall be sized and located in  ducts, each opening shall have a minimum free area of 1
                                                                                               2
           accordance with Sections 304.5.3.1 and  304.5.3.2 (see  square inch per 4,000 Btu/h (550 mm /kW) of total input
           Figure 304.5.3).                                      rating of  all  appliances in the enclosure  [see  Figures
              304.5.3.1  Combining spaces on  the same story.    304.6.1(1) and 304.6.1(2)].
              Where combining spaces on the same story, each open-
              ing shall have a minimum free area of 1 square inch per                            VENTILATION LOUVERS
                                2
              1,000 Btu/h (2200 mm /kW) of the total input rating of  CHIMNEY OR GAS VENT        (EACH END OF ATTIC)
              all appliances in the space, but not less than 100 square
                          2
              inches (0.06 m ). One permanent opening shall com-
              mence within 12 inches (305 mm) of the top and one
              permanent opening shall  commence within 12 inches
              (305  mm)  of  the bottom of the enclosure. The mini-
              mum dimension of air openings shall be not less than 3
              inches (76 mm).                                                                        OUTLET AIR
              304.5.3.2 Combining spaces in different stories. The
              volumes of spaces in different stories shall be consid-  ALTERNATE   FURNACE
                                                                  AIR INLET                 WATER
              ered to be communicating spaces where such spaces are  OPENING TO            HEATER
              connected by one or more permanent openings in doors  OUTDOORS
              or floors having a total minimum free area of 2 square                                 INLET AIR
                                          2
              inches per 1,000 Btu/h (4402 mm /kW) of total input
              rating of all appliances.
         304.6 Outdoor combustion air. Outdoor  combustion air
         shall be provided through opening(s) to the outdoors in accor-
         dance with Section 304.6.1 or 304.6.2. The minimum dimen-  VENTILATION LOUVERS
                                                                 FOR UNHEATED CRAWL SPACE
         sion of air openings shall be not less than 3 inches (76 mm).
           304.6.1 Two-permanent-openings method. Two perma-                    FIGURE 304.6.1(1)
           nent openings, one commencing within 12 inches (305  ALL AIR FROM OUTDOORS—INLET AIR FROM VENTILATED
           mm) of  the  top and one commencing within 12  inches  CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC
                                                                               (see Section 304.6.1)
           (305 mm) of the  bottom of the enclosure,  shall  be pro-
           vided. The openings shall communicate directly or by
                                                                               CHIMNEY OR GAS VENT
                           CHIMNEY OR GAS VENT
                                                                                           VENTILATION LOUVERS
                                                                                           (EACH END OF ATTIC)







                                                                                                OUTLET AIR


                                                                            FURNACE  WATER
                                                OPENING                              HEATER
                      FURNACE
                                WATER                                                           INLET AIR DUCT
                                HEATER                                                          [ENDS 1 FOOT
                                                                                                ABOVE FLOOR]






                                                              For SI: 1 foot = 304.8 mm.
                            FIGURE 304.5.3                                      FIGURE 304.6.1(2)
                   ALL AIR FROM INSIDE THE BUILDING             ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC
                           (see Section 304.5.3)                               (see Section 304.6.1)

         22                                                                     2018 INTERNATIONAL FUEL GAS CODE  ®