Page 38 - 2018_IFGC
P. 38

GENERAL REGULATIONS



               cle impact and installed in accordance with Section 305.3  sageway measuring not less than 36 inches (914 mm) wide
               and NFPA 30A.                                      and 80 inches (2032 mm) high.
             305.5 Private garages. Appliances located in private garages  Exception: Within a dwelling unit, appliances installed in
             shall be installed with a minimum clearance of 6 feet (1829  a compartment, alcove, basement or similar space shall be
             mm) above the floor.                                    provided with access by an opening or door and an unob-
               Exception: The requirements  of  this  section shall not  structed passageway  measuring not less than 24 inches
               apply where the appliances are protected from motor vehi-  (610 mm) wide and large enough to allow removal of the
               cle impact and installed in accordance with Section 305.3.  largest appliance in the space, provided that a level service
                                                                     space of not less than 30 inches (762 mm) deep and the
             305.6 Construction and protection. Boiler rooms and fur-  height of the appliance, but not less than 30 inches (762
             nace rooms shall be protected as required by the International  mm), is present at the front or service side of the appliance
             Building Code.
                                                                     with the door open.
             305.7 Clearances from grade.  Equipment and appliances  [M] 306.3 Appliances in attics. Attics containing appliances
             installed at grade level shall be supported on a level concrete  shall be provided with an opening and unobstructed passage-
             slab or other  approved material extending not less than 3  way large enough to allow removal of the largest appliance.
             inches (76 mm) above adjoining grade or shall be suspended  The passageway shall be not less than 30 inches (762 mm)
             not less than 6 inches (152 mm) above adjoining grade. Such  high and 22 inches (559 mm) wide and not more than 20 feet
             supports shall be installed in accordance with the manufac-  (6096 mm) in length measured  along the  centerline  of  the
             turer’s instructions.
                                                                  passageway from the opening to the appliance. The passage-
             305.8 Clearances  to combustible  construction. Heat-pro-  way shall have continuous  solid flooring not  less  than 24
             ducing equipment and appliances shall be installed to main-  inches (610 mm) wide. A level service space not less than 30
             tain the required clearances to combustible construction as  inches (762 mm) deep and 30 inches (762 mm) wide shall be
             specified in the listing and manufacturer’s instructions. Such  present at the front or service side of the appliance. The clear
             clearances shall be reduced only in accordance with Section  access opening dimensions shall be not less than 20 inches by
             308. Clearances to combustibles shall include such consider-  30 inches (508 mm by 762 mm) and large enough to allow
             ations  as door swing, drawer  pull,  overhead projections  or  removal of the largest appliance.
             shelving and window swing. Devices, such as door stops or  Exceptions:
             limits and closers, shall not be used to provide the required
             clearances.                                               1. The  passageway and  level service  space are not
                                                                         required where the  appliance is capable of being
             305.9 (IFGS) Parking structures. Appliances installed in    serviced and removed through the required opening.
             enclosed, basement and underground parking structures shall
             be installed in accordance with NFPA 88A.                 2. Where the passageway is not less than 6 feet (1829
                                                                         mm) high for its entire length, the passageway shall
             305.10  (IFGS) Repair garages.  Appliances installed in     be not greater than 50 feet (15 250 mm) in length.
             repair garages shall  be  installed in accordance with  NFPA
             30A.                                                    [M] 306.3.1 Electrical requirements.  A luminaire con-
                                                                     trolled by a  switch  located at  the required  passageway
             305.11 (IFGS) Installation in aircraft hangars. Heaters in  opening and a receptacle outlet shall be provided at or near
             aircraft hangars shall be installed in accordance with NFPA  the appliance location in accordance with NFPA 70.
             409.
                                                                  [M] 306.4 Appliances under floors. Under-floor spaces con-
             305.12 (IFGS) Avoid strain on gas piping. Appliances shall  taining appliances shall be provided with an access opening
             be supported and connected to the piping so as not to exert  and unobstructed passageway large  enough to remove  the
             undue strain on the connections.
                                                                  largest appliance. The passageway shall be not less than 30
                                                                  inches (762 mm) high and 22 inches (559  mm) wide, nor
                            SECTION 306 (IFGC)                    more than 20 feet (6096 mm) in length measured along the
                       ACCESS AND SERVICE SPACE                   centerline of the passageway from the opening to the appli-
                                                                  ance. A level service space not less than 30 inches (762 mm)
             [M]  306.1 Access  for maintenance and  replacement.  deep and 30 inches (762 mm)  wide shall be present at  the
             Appliances, control devices, heat  exchangers  and HVAC  front or service side of the appliance. If the depth of the pas-
             components that utilize energy shall be accessible for inspec-  sageway or the service space exceeds 12 inches (305 mm)
             tion, service, repair and  replacement without disabling the  below the adjoining grade, the walls of the passageway shall
             function of a fire-resistance-rated assembly or removing per-  be lined with concrete or masonry extending 4 inches (102
             manent construction, other appliances, or any other piping or  mm) above the adjoining grade and having sufficient lateral-
             ducts  not connected to the  appliance being inspected,  ser-  bearing capacity to resist collapse. The clear access opening
             viced, repaired or replaced. A level working space not less  dimensions shall be not less than 22 inches by 30 inches (559
             than 30 inches (762 mm) deep and 30 inches (762 mm) wide  mm by 762 mm), and large enough to allow removal of the
             shall be provided in front of the control side to service an  largest appliance.
             appliance.
                                                                     Exceptions:
             [M]  306.2 Appliances in  rooms.  Rooms containing appli-
             ances shall be provided with a door and an unobstructed pas-  1. The passageway is not required where the level ser-
                                                                         vice space is present when the access is open and the

             2018 INTERNATIONAL FUEL GAS CODE ®                                                                   25
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.