WALL CONSTRUCTION



              R602.10.4.2 Continuous sheathing methods. Contin-         3. Blocking  at  horizontal  joints  shall  not  be
              uous sheathing methods require structural panel sheath-     required in wall segments that are not counted
              ing to be used on all sheathable surfaces on one side of    as braced wall panels.
              a  braced wall line  including  areas  above  and  below  4. Where Method GB panels are installed hori-
              openings  and  gable  end  walls  and  shall  meet  the     zontally,  blocking  of  horizontal  joints  is  not
              requirements of Section R602.10.7.                          required.
              R602.10.4.3 Braced wall panel interior finish mate-  R602.10.5 Minimum length of a braced wall panel. The
              rial. Braced wall panels shall have gypsum wall board  minimum length of a braced wall panel shall comply with
              installed on  the  side of the wall  opposite the  bracing  Table R602.10.5.  For Methods CS-WSP and CS-SFB, the
                                                        1
              material. Gypsum wall board shall be not less than  / 2  minimum panel length shall be based on the adjacent clear
              inch (12.7 mm) in thickness and be fastened with nails  opening height in accordance with Table R602.10.5 and
              or screws in accordance with Table R602.3(1) for exte-  Figure R602.10.5.  Where a panel has an opening on either
              rior  sheathing  or Table  R702.3.5  for  interior  gypsum  side of differing heights, the taller opening height shall be
              wall  board.   Spacing  of  fasteners  at  panel  edges  for  used to determine the panel length.
              gypsum wall board opposite Method LIB bracing shall
              not exceed 8 inches (203 mm). Interior finish material  R602.10.5.1  Contributing  length.  For  purposes  of
              shall not be glued in Seismic Design Categories D , D 1  computing  the  required  length  of  bracing  in  Tables
                                                      0
              and D .                                              R602.10.3(1) and R602.10.3(3), the contributing length
                   2
                                                                   of each braced wall panel shall be as specified in Table
                Exceptions:                                        R602.10.5.
                   1. Interior finish material is not required opposite  R602.10.5.2 Partial credit. For Methods DWB, WSP,
                     wall panels that are braced in accordance with  SFB, PBS, PCP and HPS in Seismic Design Categories
                     Methods GB, BV-WSP, ABW, PFH, PFG and         A, B and C, panels between 36 inches and 48 inches
                     CS-PF, unless otherwise required by Section   (914 mm and 1219 mm) in length shall be considered a
                     R302.6.                                       braced wall panel  and  shall  be  permitted  to  partially
                   2. An  approved  interior  finish  material  with  an  contribute  toward  the  required  length  of  bracing  in
                     in-plane shear resistance equivalent to gypsum  Tables R602.10.3(1) and R602.10.3(3), and the contrib-
                     board  shall  be  permitted  to  be  substituted,  uting  length  shall  be  determined  from  Table
                     unless otherwise required by Section R302.6.  R602.10.5.2.
                   3. Except for  Method LIB, gypsum wall board is  R602.10.6 Construction of Methods ABW, PFH, PFG,
                     permitted  to  be  omitted  provided  that  the  CS-PF and BV-WSP. Methods ABW, PFH, PFG, CS-PF
                     required  length  of  bracing  in  Tables   and BV-WSP shall be constructed as specified in Sections
                     R602.10.3(1)  and  R602.10.3(3)  is  multiplied  R602.10.6.1 through R602.10.6.5.
                     by the appropriate adjustment factor in Tables  R602.10.6.1  Method  ABW:  Alternate  braced  wall
                     R602.10.3(2) and R602.10.3(4), respectively,  panels. Method ABW braced wall panels shall be con-
                     unless otherwise required by Section R302.6.  structed  in  accordance  with  Figure  R602.10.6.1.  The
              R602.10.4.4  Panel  joints.  Vertical  joints  of  panel  hold-down  force  shall  be  in  accordance  with  Table
              sheathing shall occur over and be fastened to common  R602.10.6.1.
              studs.  Horizontal  joints  of  panel  sheathing  in  braced  R602.10.6.2 Method PFH: Portal frame with hold-
              wall panels shall occur over and be fastened to com-  downs. Method PFH braced wall panels shall be con-
                                         1
              mon blocking of a thickness of 1 /  inches (38 mm) or  structed in accordance with Figure R602.10.6.2.
                                          2
              greater.                                             R602.10.6.3  Method  PFG:  Portal  frame  at  garage
                Exceptions:                                        door  openings  in  Seismic  Design  Categories  A,  B
                   1. For methods WSP and CS-WSP, blocking of      and  C.   Where  supporting  a  roof  or  one  story  and  a
                     horizontal  joints  is  permitted  to  be  omitted  roof, a Method PFG braced wall panel constructed in
                     when  adjustment  factor  No.  8  of  Table   accordance with Figure R602.10.6.3 shall be permitted
                     R602.10.3(2) or No. 9 of Table R602.10.3(4)   on either side of garage door openings.
                     is applied.                                   R602.10.6.4 Method CS-PF: Continuously sheathed
                   2. Vertical joints of panel sheathing shall be per-  portal  frame.  Continuously  sheathed  portal  frame
                     mitted  to  occur  over  double  studs,  where  braced wall panels shall be constructed in accordance
                     adjoining panel edges are attached to separate  with  Figure  R602.10.6.4  and  Table  R602.10.6.4.  The
                     studs  with  the  required  panel  edge  fastening  number of continuously sheathed portal frame panels in
                     schedule, and the adjacent studs are attached  a single braced wall line shall not exceed four.
                     together  with  two  rows  of  10d  box  nails  [3
                     inches by 0.128 inch (76.2 mm by 3.25 mm)]
                     at 10 inches o.c. (254 mm).





         204                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.