Page 233 - 2018_IRC
P. 233

WALL CONSTRUCTION


              R602.10.6.5  Wall  bracing  for  dwellings  with  stone  Where  detached  one-  or  two-family  dwellings  in
              and  masonry  veneer  in  Seismic  Design  Categories  Seismic Design Categories D , D  and D  have exterior
                                                                                           0
                                                                                              1
                                                                                                    2
              D , D  and D . Where stone and masonry veneer are    veneer installed in accordance with Section R703.8 and
                   1
                         2
               0
              installed in accordance with Section R703.8, wall brac-  are  braced  in  accordance  with  Method  WSP  or  CS-
              ing on exterior braced wall lines and braced wall lines  WSP, veneer shall be permitted in the second story in
              on the interior of the building, backing or perpendicular  accordance with Item 1 or 2, provided that the dwelling
              to and laterally supporting veneered walls shall comply  does  not  extend  more  than  two  stories  above  grade
              with this section.                                   plane, the veneer does not exceed 5 inches (127 mm) in
                                                                   thickness, the height of veneer on gable-end walls does
                 Where dwellings in Seismic Design Categories D ,
                                                         0
              D   and  D  have stone or masonry veneer  installed  in  not extend more than 8 feet (2438 mm) above the bear-
                      2
               1
              accordance with Section R703.8, and the veneer does  ing  wall  top  plate  elevation,  and  the  total  length  of
              not exceed the first-story height, wall bracing shall be  braced wall panel specified by Table R602.10.3(3) is
              in accordance with Section R602.10.3.                multiplied  by  1.2  for  each  first-  and  second-story
                                                                   braced wall line.
                 Where  detached  one-  or  two-family  dwellings  in  1. The total area of the veneer on the second-story
              Seismic Design Categories D , D  and D  have stone or     exterior walls shall be permitted to extend up to
                                        1
                                     0
                                              2
              masonry  veneer  installed  in  accordance  with  Section  25 percent of the occupied second floor area.
              R703.8, and the veneer exceeds the first-story height,
              wall bracing at exterior braced wall lines and braced   2. The  veneer  on  the  second-story  exterior  walls
              wall lines on the interior of the building shall be con-  shall be permitted to cover one side of the dwell-
              structed  using  Method  BV-WSP  in  accordance  with     ing, including walls on bay windows and similar
              this section and Figure R602.10.6.5. Cripple walls shall  appurtenances within the one dwelling side.
              not  be  permitted,  and  required  interior  braced wall  Townhouses  in  Seismic  Design  Categories  D ,  D 1
                                                                                                           0
              lines shall be supported on continuous foundations.  and  D   with  stone  or  masonry  veneer  exceeding  the
                                                                        2
                                                                   first-story height shall be designed in accordance with
                                                                   accepted engineering practice.
                               EXTENT OF HEADER WITH DOUBLE PORTAL FRAMES (TWO BRACED WALL PANELS)
                          EXTENT OF HEADER WITH SINGLE PORTAL FRAME
                                (ONE BRACED WALL PANEL)
                                                                                                  FASTEN KING STUD
                               2′-18′ FINISHED WIDTH OF OPENING                                   TO HEADER WITH 6
                               FOR SINGLE OR DOUBLE PORTAL                                        16D SINKERS
                                                                      TENSION STRAP PER
                                                                      TABLE 602.10.6.4
           PONY WALL                                                  (ON OPPOSITE SIDE
            HEIGHT                                                    OF SHEATHING)
                         MIN. 3″ x 11¼″ NET HEADER STEEL HEADER PROHIBITED
                        IF ½″ SPACER IS USED, PLACE ON BACK-SIDE OF HEADER  IF NEEDED, PANEL         FASTEN TOP
            12′ MAX. TOTAL WALL HEIGHT  10′ MAX.  HEIGHT  PATTERN AS SHOWN  BLOCKING WITHIN THE      HEADER WITH
                                                                     SPLICE EDGES SHALL
                            FASTEN SHEATHING TO HEADER WITH 8D
                                                                     OCCUR OVER AND BE
                            COMMON OR GALVANIZED BOX NAILS IN 3″ GRID
                                                                                                     PLATE TO
                                                                     NAILED TO COMMON
                                                                     MIDDLE 24″ OF THE
                                                                                                     TWO
                            HEADER TO JACK-STUD STRAP PER TABLE
                                                                                                     ROWS OF 16D
                                                                     PORTAL-LEG HEIGHT.
                            R602.10.6.4 ON BOTH SIDES OF OPENING
                                                                     ONE ROW OF 3″ O.C.
                                                                                                     SINKER NAILS AT
                            OPPOSITE SIDE OF SHEATHING
                                                                                                     3″ O.C. TYP.
                                                                     NAILING IS REQUIRED
                                                                     IN EACH PANEL EDGE.
                             MIN. DOUBLE 2″ x 4″ FRAMING COVERED WITH MIN.
                             7 /16″ THICK WOOD STRUCTURAL PANEL SHEATHING
                                                                                                    STRUCTURAL
                             WITH 8D COMMON OR GALVANIZED BOX NAILS AT
                                                                    FRAME CONSTRUCTION
                                                                                                    PANEL
                             3″ O.C. IN ALL FRAMING (STUDS AND SILLS) AS
                                                                                                    SHEATHING
                             SHOWN TYP.                             TYPICAL PORTAL                  MIN.  7 /16″ WOOD
                                                                    MIN. DOUBLE 2 x 4 POST
                            MIN. LENGTH OF PANEL PER TABLE R602.10.5  (KING AND JACK STUD)
                                                                    NUMBER OF JACK
                                                                    STUDS PER TABLES
                            MIN. (2) ½″ DIAMETER ANCHOR BOLTS       R602.7(1) & (2)
                            INSTALLED PER SECTION R403.1.6 WITH
                            2″ x 2″ x  3 /16″ PLATE WASHER
                                                                    INTERMITTENT BRACED
                                                                    WALL PANEL REQUIRED
                                                                    ADJACENT OPENING
                                                                    FOR SINGLE PORTAL
                                                                    FRAME
                                                                      ANCHOR BOLTS PER
                                                                      SECTION R403.1.6
                             FRONT ELEVATION                                                 SECTION
         For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
                                                     FIGURE R602.10.6.3
                 METHOD PFG—PORTAL FRAME AT GARAGE DOOR  OPENINGS IN SEISMIC DESIGN CATEGORIES A, B AND C
         208                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®