WALL CONSTRUCTION


               R608.6.3 Continuity of wall reinforcement between sto-  splicing it with the bar in the other wall in accordance with
               ries. Vertical reinforcement required by this section shall  Section R608.5.4.3 and Figure R608.5.4(1).
               be continuous between elements providing lateral support  In  required  solid  wall  segments  where  the  reduction
               for the wall. Reinforcement in the wall of the story above  factor for design strength, R , is based on the wall having
                                                                                           3
               shall be continuous with the reinforcement in the wall of  horizontal and vertical shear reinforcement in accordance
               the story below, or the foundation wall, if applicable. Lap  with Section R608.7.2.2.1, horizontal wall reinforcement
               splices,  where  required,  shall  comply  with  Section  shall be terminated with a standard hook complying with
               R608.5.4.3  and  Figure  R608.5.4(1).  Where  the  above-  Section  R608.5.4.5  and  Figure  R608.5.4(3)  or  in  a  lap-
               grade  wall  is  supported  by  a  monolithic  slab-on-ground  splice, except at corners where the reinforcement shall be
               and footing, dowel bars with a size and spacing to match  continuous as required.
               the vertical above-grade concrete wall reinforcement shall
               be embedded in the monolithic slab-on-ground and footing  Exception: In lieu of bending horizontal reinforcement
               the distance required to develop the dowel bar in tension  at corners, separate bent reinforcing bars shall be per-
               in  accordance  with  Section  R608.5.4.4  and  Figure  mitted provided that the bent bar is lap-spliced with the
               R608.5.4(2)  and  lap-spliced  with  the  above-grade  wall  horizontal  reinforcement  in  both  walls  in  accordance
               reinforcement in accordance with Section R608.5.4.3 and  with Section R608.5.4.3 and Figure R608.5.4(1).
               Figure R608.5.4(1).                                   R608.6.5 Location of reinforcement in wall. Except for
                  Where a construction joint in the wall is located below  vertical reinforcement at the ends of required solid wall seg-
               the level of the floor and less than the distance required to  ments,  which  shall  be  located  as  required  by  Section
               develop the bar in tension, the distance required to develop  R608.7.2.2.2,  the  location  of  the  vertical  reinforcement
               the bar in tension shall be measured from the top of the  shall not vary from the center of the wall by more than the
                                                                                                          3
               concrete below the joint. See Section R608.5.5.       greater of 10 percent of the wall thickness and  / -inch (10
                                                                                                            8
                                                                     mm). Horizontal and vertical reinforcement shall be located
                  Exception:  Where  reinforcement  in  the  wall  above  to provide not less than the minimum cover required by Sec-
                  cannot be made continuous with the reinforcement in  tion R608.5.4.1.
                  the wall below, the bottom of the reinforcement in the
                  wall above shall be terminated in accordance with one  R608.7 Solid walls for resistance to lateral forces.
                  of the following:                                  R608.7.1 Length of solid wall. Each exterior wall line in
                    1. Extend  below  the  top  of  the  floor  the  distance  each story shall have a total length of solid wall required by
                       required to develop the bar in tension in accor-  Section R608.7.1.1. A solid wall is a section of flat, waffle-
                       dance  with  Section  R608.5.4.4  and  Figure  grid or screen-grid wall, extending the full story height with-
                       R608.5.4(2).                                  out openings or penetrations, except those permitted by Sec-
                                                                     tion  R608.7.2.  Solid  wall  segments that  contribute  to  the
                    2. Lap-spliced      accordance   with   Section  total  length  of  solid  wall  shall  comply  with  Section
                       R608.5.4.3 and Figure R608.5.4(1) with a dowel  R608.7.2.
                       bar that extends into the wall below the distance
                       required  to  develop  the  bar  in  tension  in  accor-  R608.7.1.1 Length of solid wall for wind. Buildings
                       dance  with  Section  R608.5.4.4  and  Figure   shall have solid walls in each exterior endwall line (the
                       R608.5.4(2).                                    side of a building that is parallel to the span of the roof or
               R608.6.4  Termination  of  reinforcement.  Where  indi-  floor framing) and sidewall line (the side of a building
                                                                       that is perpendicular to the span of the roof or floor fram-
               cated in Items 1 through 3, vertical wall reinforcement in  ing) to resist lateral in-plane wind forces. The site-appro-
               the top-most story with concrete walls shall be terminated  priate basic wind speed and exposure category shall be
               with a 90-degree (1.57 rad) standard hook complying with  used in Tables R608.7(1A) through (1C) to determine
               Section R608.5.4.5 and Figure R608.5.4(3).              the unreduced total length, UR, of solid wall required in
                  1. Vertical bars adjacent to door and window openings  each exterior endwall line and sidewall line. For build-
                    required by Section R608.8.1.2.                    ings with a mean roof height of less than 35 feet (10 668
                  2. Vertical bars at the ends of required solid wall seg-  mm),  the  unreduced  values  determined  from  Tables
                    ments (see Section R608.7.2.2.2).                  R608.7(1A) though (1C) are permitted to be reduced by
                                                                       multiplying  by  the  applicable  factor,  R ,  from  Table
                                                                                                        1
                  3. Vertical bars (other than end bars, see Item 2) used as  R608.7(2);  however,  reduced  values  shall  be  not  less
                    shear reinforcement in required solid wall segments  than the minimum values in Tables R608.7(1A) through
                    where  the  reduction factor for  design  strength,  R ,  (1C). Where the floor-to-ceiling height of a story is less
                                                             3
                    used is based on the wall having horizontal and ver-  than  10  feet  (3048  mm),  the  unreduced  values  deter-
                    tical shear reinforcement (see Section R608.7.2.2.3).   mined from Tables R608.7(1A) through (1C), including
                  The bar extension of the hook shall be oriented parallel  minimum values, are permitted to be reduced by multi-
               to the horizontal wall reinforcement and be within 4 inches  plying  by  the  applicable  factor,  R ,  from  Table
                                                                                                       2
               (102 mm) of the top of the wall.                        R608.7(3). To account for different design strengths than
                                                                       assumed in determining the values in Tables R608.7(1A)
                  Horizontal  reinforcement  shall  be  continuous  around
               the building corners by bending one of the bars and lap-  through  (1C),  the unreduced  lengths determined from
                                                                       Tables  R608.7(1A) through (1C), including minimum