Page 319 - 2018_IRC
P. 319

WALL CONSTRUCTION


                                                 TABLE R608.7(1B)—continued
                           UNREDUCED LENGTH, UR, OF SOLID WALL REQUIRED IN EACH EXTERIOR ENDWALL
                              FOR WIND PERPENDICULAR TO RIDGE FIRST STORY OF TWO STORY a, c, d, e, f, g
                                    UNREDUCED LENGTH, UR, OF SOLID WALL REQUIRED IN ENDWALLS FOR WIND PERPENDICULAR TO RIDGE
                                                                        (feet)
          SIDEWALL  ENDWALL   ROOF                            Basic Wind Speed (mph) Exposure
           LENGTH    LENGTH   SLOPE    115B      120B       130B      140B       150B       160B
            (feet)    (feet)
                                         —          —       110C      119C       127C       136C      Minimum b
                                         —          —         —       110D       117D       125D
                              < 1:12   9.87      10.74      12.61     14.62      16.79     19.10       10.10
                              5:12    13.71      14.93      17.52     20.32      23.33     26.54       10.87
                       15
                              7:12    15.08      16.42      19.27     22.35      25.66     29.20       11.22
                              12:12   18.67      20.33      23.86     27.67      31.77     36.14       12.19
                              < 1:12   9.87      10.74      12.61     14.62      16.79     19.10       10.30
                              5:12    13.71      14.93      17.52     20.32      23.33     26.54       11.85
                       30
                              7:12    17.44      18.99      22.29     25.85      29.67     33.76       12.54
                              12:12   24.62      26.81      31.46     36.49      41.89     47.66       14.48
             60
                              < 1:12  10.27      11.18      13.12     15.21      17.47     19.87       10.50
                              5:12    14.26      15.52      18.22     21.13      24.26     27.60       12.82
                       45
                              7:12    20.21      22.01      25.83     29.95      34.39     39.12       13.86
                              12:12   31.20      33.97      39.87     46.23      53.07     60.39       16.76
                              < 1:12  10.64      11.59      13.60     15.77      18.11     20.60       10.70
                              5:12    14.77      16.09      18.88     21.90      25.14     28.60       13.79
                       60
                              7:12    23.05      25.09      29.45     34.15      39.21     44.61       15.18
                              12:12   37.97      41.34      48.52     56.27      64.60     73.49       19.05
         For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s, 1 pound force per linear foot = 0.146 kN/m, 1 pound per square foot = 47.88 Pa.
         a. Tabulated lengths were derived by calculating design wind pressures in accordance with Figure 28.4-1 of ASCE 7 for a building with a mean roof height of 35
           feet, topographic factor, K  equal to 1.0, and Risk Category II. For wind perpendicular to the ridge, the effects of a 2-foot overhang on each endwall are
                            zt,
           included. The design pressures were used to calculate forces to be resisted by solid wall segments in each endwall. The forces to be resisted by each wall line
           were then divided by the default design strength of 840 pounds per linear foot of length to determine the unreduced length, UR, of solid wall length required
           in each endwall. The actual mean roof height of the building shall not exceed the least horizontal dimension of the building.
         b. Tabulated lengths in the “minimum” column are based on the requirement of Section 28.4.4 of ASCE 7 that the main windforce-resisting system be designed
           for a minimum pressure of 1016 psf multiplied by the wall area of the building and 8 psf multiplied by the roof area of the building projected onto a vertical
           plane  normal to  the  assumed wind direction. Tabulated lengths in  shaded cells  are  less than the “minimum” value.  Where  the  minimum controls, it  is
           permitted to be reduced in accordance with Notes c, d and e. See Section R608.7.1.1.
         c. For buildings with a mean roof height of less than 35 feet, tabulated lengths are permitted to be reduced by multiplying by the appropriate factor, R , from
                                                                                                           1
           Table R608.7(2). The reduced length shall be not less than the “minimum” value shown in the table.
         d. Tabulated lengths for “one story or top story of two story” are based on a floor-to-ceiling height of 10 feet. Tabulated lengths for “first story of two story” are
           based on floor-to-ceiling heights of 10 feet each for the first and second story. For floor-to-ceiling heights less than assumed, use the lengths in this table or
           Table R608.7(1A) or (1C), or multiply the value in the table by the reduction factor, R , from Table R608.7(3).
                                                                  2
         e. Tabulated lengths are based on the default design shear strength of 840 pounds per linear foot of solid wall segment. The tabulated lengths are permitted to be
           reduced by multiplying by the applicable reduction factor for design strength, R 3 , from Table R608.7(4).
         f. The reduction factors, R , R  and R , in Tables R608.7(2), R608.7(3), and R608.7(4), respectively, are permitted to be compounded, subject to the limitations
                             2
                                 3
                          1
           of Note b. However, the minimum number and minimum length of solid wall segments in each wall line shall comply with Sections R608.7.1 and R608.7.2.1,
           respectively.
         g. For intermediate values of sidewall length, endwall length, roof slope and basic wind speed, use the next higher value, or determine by interpolation.
















         294                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.