Page 441 - 2018_IRC
P. 441
ROOF-CEILING CONSTRUCTION
RAFTER SPAN
WITHOUT RAFTER SUPPORT BRACE
RAFTER RIDGE MEMBER
SEE FIGURE R804.3.2.4
RAFTER SPAN
WITH RAFTER SUPPORT BRACE RAFTER BOTTOM FLANGE
BRACING (FLAT STRAP,
350S162-33 MIL C-SECTION,
OR TRACK SECTION)
HEEL JOINT
SEE FIGURE
C-SECTION OR TRACK INSTALLED R804.3.1.1
AT 4 FT. O.C. TO RAFTER SUPPORT BRACE
350s162-33 MIL C- OR TRACK
45° SECTION OR STRAP FOR CEILING
MIN JOIST TOP FLANGE BRACING
6 IN. MAX. TO CENTER
CEILING JOIST
OF SCREW PATTERN EAVE OVERHANG
2 FT. MAX.
½ IN. GYPSUM BOARD
WHEN INSTALLED RAFTER SUPPORT
BRACE SHALL BE A MINIMUM OF CEILING JOIST SPAN
350s162-33 MIL C-SECTION, CONNECTED
TO EACH CEILING JOIST AND RAFTER LOAD-BEARING WALL SHALL BE
WITH 4 SCREWS AT EACH END (COPE INSTALLED WHEN RAFTER BRACE
FLANGES OF BAR AT CEILING JOIST IS USED
CONNECTION OR USE GUSSET PLATE)
LOAD-BEARING WALL
LOAD-BEARING WALL
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm.
FIGURE R804.3
COLD-FORMED STEEL ROOF CONSTRUCTION
TABLE R804.3
ROOF FRAMING FASTENING SCHEDULE a, b
DESCRIPTION OF BUILDING ELEMENTS NUMBER AND SIZE OF FASTENERS a SPACING OF FASTENERS
6 o.c. on edges and 12
Roof sheathing (oriented strand board or plywood) No. 8 screws o.c. at interior supports. 6
to rafter
o.c. at gable end truss
Gable end truss to endwall top track No. 10 screws 12 o.c.
Minimum No. 10 screws, in accordance with Evenly spaced, not less
Rafter to ceiling joist 1
Table R804.3.1.1(3) than / from all edges.
2
Ultimate Design Wind Speed
Ceiling Joist Roof Span (ft) (mph) and Exposure Category
Spacing (in.) 126 B <139 B 126 C <139 C
110 C 115 C
2 4 2 2 2 3
2 8 2 2 3 3
Ceiling joist or
roof truss to top 16 3 2 2 2 3 4 Each ceiling joist
track of bearing 3 6 2 2 3 4 or roof truss
wall b 4 0 2 2 3 4
2 4 2 2 3 4
2 8 2 2 4 5
24 3 2 2 3 4 5
3 6 2 3 4 6
4 0 2 3 5 6
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 mil = 0.0254 mm.
a. Screws are a minimum No. 10 unless noted otherwise.
b. Indicated number of screws shall be applied through the flanges of the truss or ceiling joist or through each leg of a 54 mil clip angle. See Section R804.3.8
for additional requirements to resist uplift forces.
416 2018 INTERNATIONAL RESIDENTIAL CODE ®
Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.