ROOF-CEILING CONSTRUCTION



                  R804.3.7.2 Roof diaphragm. A roof diaphragm shall                 SECTION R806
                                                3
                  be provided by attaching not less than  / -inch (9.5 mm)       ROOF VENTILATION
                                                  8
                  wood structural panel that complies with Section R803  R806.1 Ventilation required. Enclosed attics and enclosed
                  to roof rafters or truss top chords in accordance with  rafter spaces formed where ceilings are applied directly to the
                  Table R804.3. Buildings with 3:1 or larger plan aspect  underside of roof rafters shall have cross ventilation for each
                  ratio and with roof rafter slope (pitch) of 9:12 or larger  separate space by ventilating openings protected against the
                  shall have the roof rafters and ceiling joists blocked in  entrance of rain or snow. Ventilation openings shall have a
                  accordance with Figure R804.3.7.2.              least dimension of  /  inch (1.6 mm) minimum and  /  inch
                                                                                                              1
                                                                                  1
                                                                                                               4
                                                                                   16
               R804.3.8 Roof tie-down. Roof assemblies shall be con-  (6.4  mm)  maximum.  Ventilation  openings  having  a  least
                                                                                     1
               nected to walls below in accordance with Table R804.3. A  dimension  larger  than  /   inch  (6.4  mm)  shall  be  provided
                                                                                      4
               continuous load path  shall be provided to transfer uplift  with corrosion-resistant wire cloth screening, hardware cloth,
               loads to the foundation.                           perforated vinyl or similar material with openings having a
                                                                                  1
                                                                                                              1
                                                                  least dimension of  /  inch (1.6 mm) minimum and  /  inch
                                                                                                               4
                                                                                   16
                                                                  (6.4 mm) maximum. Openings in roof framing members shall
                              SECTION R805                        conform  to  the  requirements  of  Section  R802.7.  Required
                             CEILING FINISHES                     ventilation openings shall open directly to the outside air and
             R805.1  Ceiling  installation.  Ceilings  shall  be  installed  in  shall  be  protected  to  prevent  the  entry  of  birds,  rodents,
             accordance with the requirements for interior wall finishes as  snakes and other similar creatures.
             provided in Section R702.


















                           1
                           1 / IN. × 33 MIL CONT.
                            2
                           STRAP LAP 12 IN. WITH
                           4 NO. 5 SCREWS WHERE
                           SPLICE REQUIRED
                                   SCREW THROUGH ROOF
                                   SHEATHING TO STRAP
                                   NO. 8 AT 6 IN. O.C.
                                                         SHADED AREA INDICATES
                                        2IN.             BLOCKING BREAK SHAPE
                                                         AT 12 FT O.C.
                          43 MIL                      SCREWS THROUGH STRAP
                          BLKG LENGTH          ROOF   TO BLKG AND BLKG TO TOP
                          REQUIRED TO          SLOPE  OF WALL TRACK FLANGE
                          LAP WALL TRACK              NO. 8 AT 6 IN. O.C.
                          FLANGE A MIN.        TOP
                           1
                          1/ IN.               TRACK
                           4
                             NOTE: BLKG SHALL
                             BE PERMITTED TO
                             BE ATTACHED TO
                             OUTSIDE FACE OF
                             SHEATHING OR PREFERABLY
                             DIRECTLY TO TRACK
                             FLANGE PRIOR TO SHEATHING
                             PLACEMENT AS SHOWN
             For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm.
                                                         FIGURE R804.3.7.2
                                                       ROOF BLOCKING DETAIL