P. 460

ROOF ASSEMBLIES


                                                         TABLE R905.1.1(3)
                                                    UNDERLAYMENT ATTACHMENT
                                               MAXIMUM ULTIMATE DESIGN             MAXIMUM ULTIMATE DESIGN
                ROOF COVERING     SECTION
                                                WIND SPEED, V ult   < 140 MPH       WIND SPEED, V ult    140 MPH


             Asphalt shingles      R905.2
                                                                        The underlayment shall be attached with corrosion-resistant
                                                                        fasteners in a grid pattern of 12 inches between side laps with
                                                                        a 6-inch spacing at side and end laps.
                                                                          Underlayment shall be attached using metal or plastic cap
                                                                        nails or cap staples with a nominal cap diameter of not less
                                                                        than 1 inch. Metal caps shall have a thickness of not less than
                                            Fastened sufficiently       32-gage sheet metal. Power-driven metal caps shall have a
             Clay and concrete tile  R905.3
                                            to hold in place            minimum thickness of 0.010 inch. Minimum thickness of the
                                                                        outside edge of plastic caps shall be 0.035 inch. The cap nail
                                                                        shank shall be not less than 0.083 inch for ring shank cap nails
                                                                        and 0.091 inch for smooth shank cap nails. Staples shall be
                                                                        not less than 21 gage. Cap nail shank and cap staple legs shall
                                                                        have a length sufficient to penetrate through the roof sheath-
                                                                                      3
                                                                        ing or not less than  /  inch into the roof sheathing.
             Photovoltaic         R905.16                                              4




             Metal roof shingles   R905.4

                                                                        The underlayment shall be attached with corrosion-resistant
             Mineral-surfaced roll   R905.5                             fasteners in a grid pattern of 12 inches between side laps with
             roofing                                                    a 6-inch spacing at side and end laps.
                                                                          Underlayment shall be attached using metal or plastic cap
             Slate and slate-type   R905.6                              nails or cap staples with a nominal cap diameter of not less
             shingles                                                   than 1 inch. Metal caps shall have a thickness of not less than
                                            Manufacturer’s installation   32-gage sheet metal. Power-driven metal caps shall have a
                                            instructions.               minimum thickness of 0.010 inch. Minimum thickness of the
             Wood shingles         R905.7                               outside edge of plastic caps shall be 0.035 inch. The cap nail
                                                                        shank shall be not less than 0.083 inch for ring shank cap nails
                                                                        and 0.091 inch for smooth shank cap nails. Staples shall be
                                                                        not less than 21 gage. Cap nail shank and cap staple legs shall
             Wood shakes           R905.8                               have a length sufficient to penetrate through the roof sheath-
                                                                                      3
                                                                        ing or not less than   /  inch into the roof sheathing.
                                                                                       4
             Metal panels         R905.10

             For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.

























             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               435