ROOF ASSEMBLIES



                     3.3. Underlayment  shall  be  attached  using  R905.2.1 Sheathing requirements. Asphalt shingles shall
                         metal or plastic cap nails with a nominal  be fastened to solidly sheathed decks.
                         cap diameter of not less than 1 inch (25  R905.2.2  Slope.  Asphalt  shingles  shall  be  used  only  on
                         mm). Metal caps shall have a thickness  roof slopes of two units vertical in 12 units horizontal (17-
                         of  not  less  than  32-gage  sheet  metal.  percent slope) or greater. For roof slopes from two units
                         Power-driven  metal  caps  shall  have  a  vertical in 12 units horizontal (17-percent slope) up to four
                         thickness  of  not  less  than  0.010  inch  units  vertical  in  12  units  horizontal  (33-percent  slope),
                         (0.25  mm).  Minimum  thickness  of  the  double underlayment application is required in accordance
                         outside  edge  of  plastic  caps  shall  be  with Section R905.1.1.
                         0.035 inch (0.89 mm).
                                                                 R905.2.3  Underlayment.  Underlayment  shall  comply
                     3.4. The cap nail shank shall be not less than  with Section R905.1.1.
                         0.083 inch (2.11 mm) for ring shank cap
                         nails  and  0.091  inch  (2.31  mm)  for  R905.2.4 Asphalt shingles. Asphalt shingles shall comply
                         smooth shank cap nails. Cap nail shank  with ASTM D3462.
                         shall have a length sufficient to penetrate  R905.2.4.1  Wind  resistance  of  asphalt  shingles.
                         through  the  roof  sheathing  or  not  less  Asphalt  shingles  shall  be  tested  in  accordance  with
                              3
                         than  /   inch  (19  mm)  into  the  roof  ASTM D7158. Asphalt shingles shall meet the classifi-
                               4
                         sheathing.                                cation requirements of Table R905.2.4.1 for the appro-
           R905.1.2 Ice barriers. In areas where there has been a his-  priate  ultimate  design  wind  speed.  Asphalt  shingle
           tory of ice forming along the eaves causing a backup of  packaging  shall  bear  a  label  to  indicate  compliance
           water as designated in Table R301.2(1), an ice barrier shall  with  ASTM  D7158  and  the  required  classification  in
           be installed for asphalt shingles, metal roof shingles, min-  Table R905.2.4.1.
           eral-surfaced  roll  roofing,  slate  and  slate-type  shingles,  Exception:  Asphalt  shingles  not  included  in  the
           wood shingles and wood shakes. The ice barrier shall con-  scope of ASTM D7158 shall be tested and labeled in
           sist of not fewer than two layers of underlayment cemented  accordance  with  ASTM  D3161.  Asphalt  shingle
           together,  or  a  self-adhering  polymer-modified  bitumen  packaging shall bear a label to indicate compliance
           sheet shall be used in place of normal underlayment and   with ASTM D3161 and the required classification in
           extend from the lowest edges of all roof surfaces to a point  Table R905.2.4.1.
           not less than 24 inches (610 mm) inside the exterior wall  R905.2.5 Fasteners.  Fasteners for  asphalt shingles shall
           line of the building. On roofs with slope equal to or greater  be  galvanized  steel,  stainless  steel,  aluminum  or  copper
           than eight units vertical in 12 units horizontal (67-percent  roofing  nails,  minimum  12-gage  [0.105  inch  (3  mm)]
           slope), the ice barrier shall also be applied not less than 36  shank with a minimum  / -inch-diameter (9.5 mm) head,
                                                                                    3
                                                                                      8
           inches (914 mm) measured along the roof slope from the  complying  with  ASTM  F1667,  of  a  length  to  penetrate
           eave edge of the building.                            through  the  roofing  materials  and  not  less  than  /   inch
                                                                                                         3
                                                                                                           4
              Exception: Detached accessory structures not contain-  (19.1 mm) into the roof sheathing. Where the roof sheath-
                                                                             3
              ing conditioned floor area.                        ing is less than  /  inch (19.1 mm) thick, the fasteners shall
                                                                              4
         R905.2 Asphalt shingles. The installation of asphalt shingles  penetrate through the sheathing.
         shall comply with the provisions of this section.       R905.2.6  Attachment.  Asphalt  shingles  shall  have  the
                                                                 minimum number of fasteners required by the manufac-
                                                                 turer’s approved installation instructions, but not less than
                                                     TABLE R905.2.4.1
                                         CLASSIFICATION OF ASPHALT ROOF SHINGLES
            MAXIMUM ULTIMATE DESIGN  MAXIMUM BASIC WIND SPEED,               a
                                      V ASD   FROM TABLE R301.2.1.3  ASTM D7158               ASTM D3161
                WIND SPEED, V ult                               SHINGLE CLASSIFICATION    SHINGLE CLASSIFICATION
           FROM FIGURE R301.2(5)A (mph)      (mph)
                    110                        85                    D, G or H                 A, D or F
                    116                        90                    D, G or H                 A, D or F
                    129                       100                      G or H                  A, D or F
                    142                       110                      G or H                     F
                    155                       120                      G or H                     F
                    168                       130                       H                         F
                    181                       140                       H                         F
                    194                       150                       H                         F
         For SI: 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s.
         a. The standard calculations contained in ASTM D7158 assume Exposure Category B or C and a building height of 60 feet or less. Additional calculations are
           required for conditions outside of these assumptions.



         436                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®