Page 472 - 2018_IRC
P. 472

CHAPTER 10

                                         CHIMNEYS AND FIREPLACES




             User note:
                About this chapter: Chapter 10 contains requirements for the construction, seismic reinforcing and anchorage of masonry chimneys and
                fireplaces; and establishes standards for the use and installation of factory-built chimneys, fireplaces and masonry heaters. Chimneys and
                fireplaces constructed of masonry rely on prescriptive requirements for the details of their construction; factory-built versions rely on the listing
                and labeling method of approval.



                              SECTION R1001                       above grade, except where constructed completely within the
                          MASONRY FIREPLACES                      exterior walls. Anchorage shall conform to the requirements
             R1001.1 General. Masonry fireplaces shall be constructed in  of Section R1001.4.1.
             accordance with this section and the applicable provisions of  R1001.4.1 Anchorage. Two  / -inch by 1-inch (5 mm by
                                                                                            3
             Chapters 3 and 4.                                       25 mm) straps shall be embedded not less than 12 inches
                                                                                             16
             R1001.2  Footings  and  foundations.  Footings  for  masonry  (305 mm) into the chimney. Straps shall be hooked around
             fireplaces and their chimneys shall be constructed of concrete  the outer bars and extend 6 inches (152 mm) beyond the
             or solid masonry not less than 12 inches (305 mm) thick and  bend.  Each  strap  shall  be  fastened  to  not  less  than  four
                                                                                                              1
             shall extend not less than 6 inches (152 mm) beyond the face of  floor  ceiling  or  floor  joists  or  rafters  with  two  / -inch
                                                                                                               2
             the fireplace or foundation wall on all sides. Footings shall be  (12.7 mm) bolts.
             founded on natural, undisturbed earth or engineered fill below
             frost depth. In areas not subjected to freezing, footings shall be  R1001.4.1.1 Cold-formed steel framing. Where cold-
                                                                                                                 1
             not less than 12 inches (305 mm) below finished grade.    formed steel framing is used, the location where the  / -
                                                                                                                  2
                                                                       inch (12.7 mm) bolts are used to attach the straps to the
               R1001.2.1  Ash  dump  cleanout.  Cleanout  openings     framing shall be reinforced with not less than a 3-inch
               located  within  foundation  walls  below  fireboxes,  where   3-inch  0.229-inch (76 mm  76 mm  5.8 mm)
               provided, shall be equipped with ferrous metal or masonry  steel  plate  on  top  of  the  strap  that  is  screwed  to  the
               doors  and  frames  constructed  to  remain  tightly  closed  framing  with  not  fewer  than  seven  No.  6  screws  for
               except when in use. Cleanouts shall be  located to allow  each bolt.
               access so that ash removal will not create a hazard to com-
               bustible materials.                                R1001.5  Firebox  walls.  Masonry  fireboxes  shall  be  con-
                                                                  structed of solid masonry units, hollow masonry units grouted
             R1001.3  Seismic  reinforcing.  Masonry  or  concrete  chim-  solid, stone or concrete. Where a lining of firebrick not less
             neys in Seismic Design Category D , D  or D  shall be rein-  than 2 inches (51 mm) thick or other approved lining is pro-
                                                  2
                                             1
                                          0
             forced.  Reinforcing  shall  conform  to  the  requirements  set  vided,  the  minimum  thickness  of  back  and  sidewalls  shall
             forth in Table R1001.1 and Section R606.
                                                                  each be 8 inches (203 mm) of solid masonry, including the
               R1001.3.1 Vertical reinforcing. For chimneys up to 40  lining.  The  width  of  joints  between  firebricks  shall  not  be
               inches  (1016  mm)  wide,  four  No.  4  continuous  vertical  greater than  /  inch (6.4 mm). Where a lining is not provided,
                                                                            1
                                                                             4
               bars shall be placed between wythes of solid masonry or  the total minimum thickness of back and side walls shall be
               within  the  cells  of  hollow  unit  masonry  and  grouted  in  10 inches (254 mm) of solid masonry. Firebrick shall con-
               accordance with Section R606. Grout shall be prevented  form to ASTM C27 or C1261 and shall be laid with medium-
               from bonding with the flue liner so that the flue liner is  duty refractory mortar conforming to ASTM C199.
               free to move with thermal expansion. For chimneys more
               than 40 inches (1016 mm) wide, two additional No. 4 ver-  R1001.5.1 Steel fireplace units. Installation of steel fire-
               tical bars shall be provided for each additional flue incor-  place units with solid masonry to form a masonry fireplace
               porated into the chimney or for each additional 40 inches  is permitted where installed either in accordance with the
               (1016 mm) in width or fraction thereof.               requirements  of  their  listing  or  the  requirements  of  this
                                                                     section. Steel fireplace units incorporating a steel firebox
               R1001.3.2  Horizontal  reinforcing.  Vertical  reinforce-  lining shall be constructed with steel not less than  /  inch
                                                                                                              1
                                      1
                                                                                                               4
               ment shall be placed within  / -inch (6.4 mm) ties, or other  (6.4  mm)  thick,  and  an  air-circulating  chamber  that  is
                                       4
               reinforcing of equivalent net cross-sectional area, placed  ducted to the interior of the building. The firebox lining
               in the bed joints in accordance with Section R606 at not  shall  be  encased  with  solid masonry  to  provide  a  total
               less than every 18 inches (457 mm) of vertical height. Two  thickness at the back and sides of not less than 8 inches
               such ties shall be installed at each bend in the vertical bars.  (203 mm), of which not less than 4 inches (102 mm) shall
             R1001.4 Seismic anchorage. Masonry or concrete chimneys  be of solid masonry or concrete. Circulating air ducts used
             in Seismic Design Category D , D  or D  shall be anchored at  with steel fireplace units shall be constructed of metal or
                                             2
                                        1
                                     0
             each floor, ceiling or roof line more than 6 feet (1829 mm)  masonry.
             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               447
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   467   468   469   470   471   472   473   474   475   476   477