ENERGY EFFICIENCY



         N1106.3 (R406.3) Energy rating index. The Energy Rating   3. Name  of  individual  completing  the  compliance
         Index  (ERI)  shall  be  determined  in  accordance  with  RES-  report.
         NET/ICC 301 except that the ERI reference design ventila-  4. Name and version of the compliance software tool.
         tion rate shall be in accordance with Equation 11-1.
                                                                   Exception:  Where  an  otherwise  identical  building
         Ventilation rate, CFM = (0.01 × total square foot area of   model  is  offered  in  multiple  orientations,  compliance
         house) + [7.5 × (number of bedrooms + 1)]                 for any orientation shall be permitted by documenting
                                             (Equation 11-1)
                                                                   that the building meets the performance requirements
           Energy used to recharge or refuel a vehicle used for trans-  in each of the four (north, east, south and west) cardinal
         portation on roads that are not on the building site shall not be  orientations.
         included in the ERI reference design or the rated design.
                                                                N1106.6.3  (R406.6.3)  Additional  documentation.  The
         N1106.4  (R406.4)  ERI-based  compliance.  Compliance   code official  shall  be  permitted  to  require  the  following
         based on an ERI analysis requires that the rated design be  documents:
         shown to have an ERI less than or equal to the appropriate  1. Documentation  of  the  building  component  charac-
         value indicated in Table N1106.4 when compared to the ERI   teristics of the ERI reference design.
         reference design.
                                                                   2. A certification signed by the builder providing the
                        TABLE N1106.4 (R406.4)
                    MAXIMUM ENERGY RATING INDEX                      building  component  characteristics  of  the  rated
                CLIMATE ZONE          ENERGY RATING INDEX a          design.
                     1                       5  7                  3. Documentation of the actual values used in the soft-
                     2                       5  7                    ware calculations for the rated design.
                     3                       5  7                N1106.6.4  (R406.6.4)  Specific  approval.  Performance
                     4                       6  2                analysis tools meeting the applicable sections of Section
                                                                 N1106 shall be approved. Documentation demonstrating
                     5                       6  1
                                                                 the approval of performance analysis tools in accordance
                     6                       6  1                with Section N1106.6.1 shall be provided.
                     7                       5  8                N1106.6.5  (R406.6.5)  Input  values.  Where  calculations
                     8                       5  8                require  input  values  not  specified  by  Sections  N1102,
                                                                 N1103,  N1104  and  N1105,  those  input  values  shall  be
         a. Where on-site renewable energy is included for compliance using the ERI
           analysis  of  Section  N1106.4,  the  building  shall  meet  the  mandatory  taken from RESNET/ICC 301.
           requirements of Section N1106.2, and the building thermal envelope shall
           be greater than or equal to the levels of efficiency and SHGC in Table
           N1102.1.2 or Table N1102.1.4.                                    SECTION N1107 (R501)
         N1106.5 (R406.5) Verification by approved agency. Verifi-    EXISTING BUILDINGS—GENERAL
         cation of compliance with Section N1106 shall be completed
         by an approved third party.                          N1107.1 (R501.1) Scope. The provisions of Sections N1107
                                                              through N1111 shall control the alteration, repair, addition
         N1106.6  (R406.6)  Documentation.  Documentation  of  the  and change of occupancy of existing buildings and structures.
         software used to determine the ERI and the parameters for the
         residential building  shall  be  in  accordance  with  Sections  N1107.1.1 (R501.1.1) Additions, alterations, or repairs:
         N1106.6.1 through N1106.6.3.                            General. Additions, alterations, or repairs to an existing
                                                                 building, building system or portion thereof shall comply
           N1106.6.1 (R406.6.1) Compliance software tools. Soft-  with Section N1108, N1109 or N1110. Unaltered portions
           ware  tools  used for  determining  ERI  shall  be  Approved  of the existing building or building supply system shall not
           Software Rating Tools in accordance with RESNET/ICC   be required to comply with this chapter.
           301.
                                                              N1107.2 (R501.2) Existing buildings. Except as specified in
           N1106.6.2  (R406.6.2)  Compliance  report.  Compliance  this  chapter,  this  code  shall  not  be  used  to  require  the
           software tools shall generate a report that documents that  removal, alteration or abandonment of, nor prevent the con-
           the  ERI  of  the  rated design  complies  with  Sections  tinued use and maintenance of, an existing building or build-
           N1106.3  and  N1106.4.  The  compliance  documentation  ing system lawfully in existence at the time of adoption of
           shall include the following information:           this code.
              1. Address  or  other  identification  of  the  residential  N1107.3  (R501.3)  Maintenance.  Buildings  and  structures,
                building.
                                                              and parts thereof, shall be maintained in a safe and sanitary
              2. An  inspection  checklist  documenting  the  building  condition. Devices and systems that are required by this code
                component characteristics of the rated design. The  shall be maintained in compliance with the code edition under
                inspection checklist shall show results for both the  which installed. The owner or the owner’s authorized agent
                ERI reference design and the rated design, and shall  shall  be  responsible  for  the  maintenance  of  buildings  and
                document all inputs entered by the user necessary to  structures. The requirements of this chapter shall not provide
                reproduce the results.                        the basis for removal or abrogation of energy conservation,

         492                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®