P. 519

ENERGY EFFICIENCY



                2. Existing  ceiling,  wall  or  floor  cavities  exposed   SECTION N1110 (R504)
                   during  construction  provided  that  these  cavities          REPAIRS
                   are filled with insulation.                N1110.1  (R504.1)  General.  Buildings,  structures  and  parts
                3. Construction  where  the  existing  roof,  wall  or  thereof shall be repaired in compliance with Section N1107.3
                   floor cavity is not exposed.               and  this  section.  Work  on  nondamaged  components  neces-
                                                              sary for the required repair of damaged components shall be
                4. Roof recover.
                                                              considered to be part of the repair and shall not be subject to
                5. Roofs without insulation in the cavity and where  the  requirements  for  alterations  in  this  chapter.  Routine
                   the  sheathing  or  insulation  is  exposed  during  maintenance required by Section N1107.3, ordinary repairs
                   reroofing shall be insulated either above or below  exempt from permit, and abatement of wear due to normal
                   the sheathing.                             service conditions shall not be subject to the requirements for
                6. Surface-applied window film installed on exist-  repairs in this section.
                   ing single-pane fenestration assemblies to reduce  N1110.2  (R504.2)  Application.  For  the  purposes  of  this
                   solar  heat gain  provided that the code does not  code, the following shall be considered to be repairs:
                   require the glazing or fenestration assembly to be  1. Glass-only replacements in an existing sash and frame.
                   replaced.                                     2. Roof repairs.
              N1109.1.1.1 (R503.1.1.1) Replacement fenestration.
              Where  some  or  all  of  an  existing  fenestration  unit  is  3. Repairs where only the bulb, ballast or both within the
              replaced  with  a  new  fenestration  product,  including  existing  luminaires  in  a  space  are  replaced  provided
              sash and glazing, the replacement fenestration unit shall  that  the  replacement  does  not  increase  the  installed
              meet  the  applicable  requirements  for  U-factor  and  interior lighting power.
              SHGC as specified  in  Table  N1102.1.2.  Where  more
              than  one  replacement  fenestration  unit  is  to  be
              installed,  an  area-weighted  average  of  the  U-factor,    SECTION N1111 (R505)
              SHGC  or  both  of  all  replacement  fenestration  units  CHANGE OF OCCUPANCY OR USE
              shall be an alternative that can be used to show compli-  N1111.1 (R505.1) General. Spaces undergoing a change in
              ance.                                           occupancy  that  would  result  in  an  increase  in  demand  for
           N1109.1.2  (R503.1.2)  Heating  and  cooling  systems.  either fossil fuel or electrical energy shall comply with this
           New heating, cooling and duct systems that are part of the  chapter.
           alteration shall comply with Section N1103.        N1111.2 (R505.2) General. Any space that is converted to a
              Exception: Where ducts from an existing heating and  dwelling  unit  or  portion  thereof  from  another  use  or  occu-
              cooling  system  are  extended,  duct  systems  with  less  pancy shall comply with this chapter.
              than 40 linear feet (12.19 m) in unconditioned spaces  Exception:  Where  the  simulated  performance  option  in
              shall  not  be required  to be  tested  in  accordance  with  Section  N1105  is  used  to  comply  with  this  section,  the
              Section N1103.3.3.                                 annual energy cost of the proposed design is permitted to
           N1109.1.3  (R503.1.3)  Service  hot  water  systems.  New  be 110 percent of the annual energy cost allowed by Sec-
                                                                 tion N1105.3.
           service  hot  water  systems  that  are  part of the alteration
           shall comply with Section N1103.5.
           N1109.1.4  (R503.1.4)  Lighting.  New  lighting  systems
           that are part of the alteration shall comply with Section
           N1104.1.
              Exception: Alterations that replace less than 50 percent
              of the luminaires in a space, provided that such alter-
              ations  do  not  increase  the  installed  interior  lighting
              power.
         N1109.2 (R503.2) Change in space conditioning. Any non-
         conditioned  or  low  energy  space  that  is  altered  to  become
         conditioned space  shall  be  required  to  be  brought  into  full
         compliance with this chapter.
           Exception:  Where  the  simulated  performance  option  in
           Section  N1105  is  used  to  comply  with  this  section,  the
           annual energy cost of the proposed design is permitted to
           be  110  percent  of  the  annual  energy  cost  otherwise
           allowed by Section N1105.3.







         494                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®