GENERAL MECHANICAL SYSTEM REQUIREMENTS


                          SECTION M1305                          of the appliance. If the depth of the passageway or the ser-
                       APPLIANCE ACCESS                          vice space exceeds 12 inches (305 mm) below the adjoin-
         M1305.1  Appliance  access  for  inspection  service,  repair  ing grade, the walls of the passageway shall be lined with
         and replacement. Appliances shall be located to allow for  concrete or masonry extending 4 inches (102 mm) above
         access for inspection, service, repair and replacement without  the  adjoining  grade  in  accordance  with  Chapter  4.  The
         removing  permanent  construction,  other appliances,  or  any  rough-framed access opening dimensions shall be not less
         other piping or ducts not connected to the appliance being  than 22 inches by 30 inches (559 mm by 762 mm), and
         inspected,  serviced,  repaired  or  replaced.  A  level  working  large enough to remove the largest appliance.
         space not less than 30 inches deep and 30 inches wide (762  Exceptions:
         mm by 762 mm) shall be provided in front of the control side  1. The passageway is not required where the level
         to service an appliance.
                                                                       service space is present when the access is open,
           M1305.1.1 Appliances in rooms. Appliances installed in       and the appliance can be serviced and removed
           a compartment, alcove, basement or similar space shall be    through the required opening.
           accessed by an opening or door and an unobstructed pas-   2. Where  the  passageway  is  unobstructed  and  not
           sageway measuring not less than 24 inches (610 mm) wide      less  than 6 feet high (1929 mm) and 22 inches
           and large enough to allow removal of the largest appliance   (559 mm) wide for its entire length, the passage-
           in the space, provided there is a level service space of not  way shall not be limited in length.
           less than 30 inches (762 mm) deep and the height of the
           appliance, but not less than 30 inches (762 mm), at the  M1305.1.3.1 Ground clearance. Equipment and appli-
           front or service side of the appliance with the door open.  ances  supported  from  the  ground  shall  be  level  and
                                                                   firmly supported on a concrete slab or other approved
           M1305.1.2 Appliances in attics. Attics containing appli-  material  extending  not  less  than  3  inches  (76  mm)
           ances shall be provided with an opening and a clear and  above the adjoining ground. Such support shall be in
           unobstructed passageway large enough to allow removal   accordance with the manufacturer’s installation instruc-
           of the largest appliance, but not less than 30 inches (762  tions. Appliances suspended from the floor shall have a
           mm) high and 22 inches (559 mm) wide and not more than  clearance of not less than 6 inches (152 mm) from the
           20 feet (6096 mm) long measured along the centerline of  ground.
           the  passageway  from  the  opening  to  the  appliance.  The
           passageway shall have continuous solid flooring in accor-  M1305.1.3.2 Pit locations. Appliances installed in pits
           dance with Chapter 5 not less than 24 inches (610 mm)   or excavations shall not come in direct contact with the
           wide. A level service space not less than 30 inches (762  surrounding soil and shall be installed not less than 3
           mm) deep and 30 inches (762 mm) wide shall be present   inches (76 mm) above the pit floor. The sides of the pit
           along all sides of the appliance where access is required.  or excavation shall be held back not less than 12 inches
           The clear access opening dimensions shall be not less than  (305 mm) from the appliance. Where the depth exceeds
           of 20 inches by 30 inches (508 mm by 762 mm), and large  12 inches (305 mm) below adjoining grade, the walls of
           enough to allow removal of the largest appliance.       the  pit  or  excavation  shall  be  lined  with  concrete  or
                                                                   masonry.  Such  concrete  or  masonry  shall  extend  not
              Exceptions:
                                                                   less than 4 inches (102 mm) above adjoining grade and
                1. The passageway and level service space are not  shall  have  sufficient  lateral  load-bearing  capacity  to
                   required where the appliance can be serviced and  resist  collapse.  Excavation  on  the  control  side  of  the
                   removed through the required opening.           appliance  shall  extend  horizontally  not  less  than  30
                2. Where  the  passageway  is  unobstructed  and  not  inches  (762  mm).  The  appliance  shall  be  protected
                   less than 6 feet (1829 mm) high and 22 inches (559  from flooding in an approved manner.
                   mm)  wide for  its  entire  length,  the  passageway  M1305.1.3.3  Electrical  requirements.  A  luminaire
                   shall be not more than 50 feet (15 250 mm) long.  controlled by a switch located at the required passage-
              M1305.1.2.1  Electrical  requirements.  A  luminaire  way opening and a receptacle outlet shall be installed at
              controlled by a switch located at the required passage-  or  near  the  appliance  location  in  accordance  with
              way opening and a receptacle outlet shall be installed at  Chapter  39.  Exposed  lamps  shall  be  protected  from
              or  near  the  appliance  location  in  accordance  with  damage by location or lamp guards.
              Chapter  39.  Exposed  lamps  shall  be  protected  from
              damage by location or lamp guards.
                                                                               SECTION M1306
           M1305.1.3 Appliances under floors. Underfloor spaces              CLEARANCES FROM
           containing  appliances  shall  be  provided  with  an  unob-  COMBUSTIBLE CONSTRUCTION
           structed  passageway  large  enough  to  remove  the  largest
           appliance, but not less than 30 inches (762 mm) high and  M1306.1 Appliance clearance. Appliances shall be installed
           22 inches (559 mm)  wide,  nor more  than 20 feet (6096  with the clearances from unprotected combustible materials
           mm) long measured along the centerline of the passage-  as indicated on the appliance label and in the manufacturer’s
           way  from  the  opening  to  the appliance.  A  level service  installation instructions.
           space not less than 30 inches (762 mm) deep and 30 inches  M1306.2  Clearance  reduction.  The  reduction  of  required
           (762 mm) wide shall be present at the front or service side  clearances to combustible assemblies or combustible materi-

         498                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®