HEATING AND COOLING EQUIPMENT AND APPLIANCES



               3. Floor  furnaces  shall  be  installed  not  closer  than  6  in accordance with their listing, the manufacturer’s installa-
                  inches (152 mm) to the ground. The minimum clear-  tion instructions and the requirements of this code.
                  ance  shall  be  2  inches  (51  mm),  where  the  lower  6  M1410.2 Floor mounting. Room heaters shall be installed
                  inches  (152  mm)  of  the  furnace  is  sealed  to  prevent  on  noncombustible  floors  or  approved  assemblies  con-
                  water entry.                                    structed of noncombustible materials that extend not less than
               4. Where excavation is required for a floor furnace instal-  18 inches (457 mm) beyond the appliance on all sides.
                  lation, the excavation shall extend 30 inches (762 mm)  Exceptions:
                  beyond  the  control  side  of  the  floor  furnace  and  12
                  inches (305 mm) beyond the remaining sides. Excava-  1. Listed  room  heaters  shall be  installed  on  noncom-
                  tions shall slope outward from the perimeter of the base  bustible floors, assemblies constructed of noncom-
                  of the excavation to the surrounding grade at an angle  bustible  materials  or  floor  protectors  listed  and
                  not exceeding 45 degrees (0.79 rad) from horizontal.   labeled in accordance with UL 1618. The materials
                                                                         and  dimensions  shall  be  in  accordance  with  the
               5. Floor furnaces shall not be supported from the ground.  appliance manufacturer’s instructions.

                                                                       2. Room heaters listed for installation on combustible
                              SECTION M1409                              floors without floor protection shall be installed in
                         VENTED WALL FURNACES                            accordance  with  the  appliance  manufacturer’s
                                                                         instructions.
             M1409.1 General. Oil-fired vented wall furnaces shall com-
             ply with  UL 730 and shall  be  installed in  accordance with
             their listing, the manufacturer’s instructions and the require-
             ments of this code.                                                   SECTION M1411
                                                                         HEATING AND COOLING EQUIPMENT
             M1409.2  Location.  The  location  of  vented  wall  furnaces  M1411.1 Approved refrigerants. Refrigerants used in direct
             shall conform to the following requirements:         refrigerating systems shall conform to the applicable provi-
               1. Vented wall furnaces shall be located where they will  sions of ANSI/ASHRAE 34.
                  not cause a fire hazard to walls, floors, combustible fur-  M1411.2 Refrigeration coils in warm-air furnaces. Where
                  nishings  or  doors.  Vented  wall  furnaces  installed  a cooling coil is located in the supply plenum of a warm-air
                  between bathrooms and adjoining rooms shall not cir-  furnace, the furnace blower shall be rated at not less than 0.5-
                  culate air from bathrooms to other parts of the building.
                                                                  inch water column (124 Pa) static pressure unless the furnace
               2. Vented wall furnaces shall not be located where a door  is listed and labeled for use with a cooling coil. Cooling coils
                  can swing within 12 inches (305 mm) of the furnace air  shall  not  be  located  upstream  from  heat  exchangers  unless
                  inlet or outlet measured at right angles to the opening.  listed and labeled for such use. Conversion of existing fur-
                  Doorstops  or  door  closers  shall  not  be  installed  to  naces for use with cooling coils shall be permitted provided
                  obtain this clearance.                          that the furnace will operate within the temperature rise spec-
             M1409.3 Installation. Vented wall furnace installations shall  ified for the furnace.
             conform to the following requirements:               M1411.3  Condensate  disposal.  Condensate  from  cooling
               1. Required wall thicknesses shall be in accordance with  coils and evaporators shall be conveyed from the drain pan
                  the manufacturer’s installation instructions.   outlet  to  an  approved  place  of  disposal.  Such  piping  shall
                                                                  maintain a minimum horizontal slope in the direction of dis-
               2. Ducts shall not be attached to a wall furnace. Casing  charge of not less than  /  unit vertical in 12 units horizontal
                                                                                     1
                                                                                      8
                  extensions or boots shall be installed only where listed  (1-percent  slope).  Condensate  shall  not  discharge  into  a
                  as part of a listed and labeled appliance.      street, alley or other area where it would cause a nuisance.
               3. A manual shutoff valve shall be installed ahead of all  M1411.3.1 Auxiliary and secondary drain systems. In
                  controls.                                          addition to the requirements of Section M1411.3, a sec-
             M1409.4  Access.  Vented  wall  furnaces  shall  be  provided  ondary drain or auxiliary drain pan shall be required for
             with access for cleaning of heating surfaces; removal of burn-  each  cooling  or  evaporator  coil  where  damage  to  any
             ers;  replacement  of  sections,  motors,  controls,  filters  and  building  components  will  occur  as  a  result  of  overflow
             other working parts; and for adjustments and lubrication of  from the equipment drain pan or stoppage in the conden-
             parts requiring such attention. Panels, grilles and access doors  sate drain piping. Such piping shall maintain a minimum
             that must be removed for normal servicing operations shall  horizontal slope in the direction of discharge of not less
                                                                         1
             not be attached to the building construction.           than  /   unit  vertical  in  12  units  horizontal  (1-percent
                                                                          8
                                                                                                      3
                                                                     slope). Drain piping shall be not less than  / -inch (19 mm)
                                                                                                       4
                                                                     nominal pipe size. One of the following methods shall be
                              SECTION M1410                          used:
                         VENTED ROOM HEATERS                           1. An auxiliary drain pan with a separate drain shall be
             M1410.1  General.  Vented  room  heaters  shall  be  tested  in  installed under the coils on which condensation will
             accordance  with  ASTM  E1509  for  pellet-fuel  burning,  UL  occur. The auxiliary pan drain shall discharge to a
             896 for oil-fired or UL 1482 for solid fuel-fired and installed  conspicuous point of disposal to alert occupants in

             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               505
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   525   526   527   528   529   530   531   532   533   534   535