P. 569

FUEL GAS



         means for support and restraint of that appliance shall be pro-  premises that is required to be changed or replaced shall be
         vided.                                               left  in  a  safe  structural  condition  in  accordance  with  the
                                                              requirements of this code.
         G2404.5 (301.9) Repair. Defective material or parts shall be
         replaced or repaired in such a manner so as to preserve the  G2405.2 (302.4) Alterations to trusses. Truss members and
         original approval or listing.                        components shall not be cut, drilled, notched, spliced or oth-
                                                              erwise  altered  in  any  way  without  the  written  concurrence
         G2404.6 (301.10) Wind resistance. Appliances and supports
         that are exposed to wind shall be designed and installed to  and approval of a registered design professional. Alterations
         resist the wind pressures determined in accordance with this  resulting  in  the  addition  of  loads  to  any  member,  such  as
         code.                                                HVAC equipment and water heaters, shall not be permitted
                                                              without  verification  that  the  truss  is  capable  of  supporting
         G2404.7  (301.11)  Flood  hazard.  For  structures  located  in  such additional loading.
         flood  hazard  areas,  the  appliance,  equipment  and  system  G2405.3  (302.3.1)  Engineered  wood  products.  Cuts,
         installations  regulated  by  this  code  shall  be  located  at  or  notches and holes bored in trusses, structural composite lum-
         above the elevation required by Section R322 for utilities and  ber, structural glued-laminated members and I-joists are pro-
         attendant equipment.
                                                              hibited  except  where  permitted  by  the  manufacturer’s
           Exception: The appliance, equipment and system installa-  recommendations or where the effects of such alterations are
           tions  regulated  by  this  code  are  permitted  to  be  located  specifically considered in the design of the member by a reg-
           below the elevation required by Section R322 for utilities  istered design professional.
           and attendant equipment provided that they are designed
           and installed to prevent water from entering or accumulat-
           ing  within  the  components  and  to  resist  hydrostatic  and  SECTION G2406 (303)
           hydrodynamic loads and stresses, including the effects of        APPLIANCE LOCATION
           buoyancy, during the occurrence of flooding to such ele-  G2406.1  (303.1)  General.  Appliances  shall  be  located  as
           vation.                                            required by this section, specific requirements elsewhere in
         G2404.8  (301.12)  Seismic  resistance.  Where  earthquake  this code and the conditions of the equipment and appliance
         loads are applicable in accordance  with this  code, the sup-  listing.
         ports shall be designed and installed for the seismic forces in  G2406.2 (303.3) Prohibited locations. Appliances shall not
         accordance with this code.                           be located in sleeping rooms, bathrooms, toilet rooms, stor-
         G2404.9  (301.14) Rodentproofing.  Buildings or  structures  age closets or surgical rooms, or in a space that opens only
         and the  walls  enclosing  habitable  or  occupiable rooms  and  into such rooms or spaces, except where the installation com-
         spaces in which persons live, sleep or work, or in which feed,  plies with one of the following:
         food or foodstuffs are stored, prepared, processed, served or  1. The  appliance  is  a  direct-vent  appliance  installed  in
         sold,  shall  be  constructed  to  protect  against  the  entry  of  accordance  with  the  conditions  of  the  listing  and  the
         rodents.                                                  manufacturer’s instructions.
         G2404.10  (307.5)  Auxiliary  drain  pan.  Category  IV  con-  2. Vented room heaters, wall furnaces, vented decorative
         densing appliances shall be provided with an auxiliary drain  appliances, vented gas fireplaces, vented gas fireplace
         pan where damage to any building component will occur as a  heaters  and  decorative  appliances  for  installation  in
         result of stoppage in the condensate drainage system. Such  vented  solid  fuel-burning  fireplaces  are  installed  in
         pan shall be installed in accordance with the applicable provi-  rooms that meet the required volume criteria of Section
         sions of Section M1411.                                   G2407.5.
           Exception: An auxiliary drain pan shall not be required  3. A  single  wall-mounted  unvented room heater  is
           for appliances that automatically shut down operation in  installed in a bathroom and such unvented room heater
           the event of a stoppage in the condensate drainage system.  is equipped as specified in Section G2445.6 and has an
         G2404.11  (307.6)  Condensate  pumps.  Condensate  pumps  input  rating  not  greater  than  6,000  Btu/h  (1.76  kW).
         located  in  uninhabitable  spaces,  such  as  attics  and  crawl  The bathroom shall meet the required volume criteria
         spaces,  shall  be  connected  to  the  appliance  or  equipment  of Section G2407.5.
         served such that when the pump fails, the appliance or equip-  4. A  single  wall-mounted  unvented room heater  is
         ment  will  be  prevented  from  operating.  Pumps  shall  be  installed in a bedroom and such unvented room heater
         installed in accordance with the manufacturer’s instructions.  is equipped as specified in Section G2445.6 and has an
                                                                   input rating not greater than 10,000 Btu/h (2.93 kW).
                                                                   The bedroom shall meet the required volume criteria of
                       SECTION G2405 (302)                         Section G2407.5.
                       STRUCTURAL SAFETY                         5. The appliance is installed in a room or space that opens
         G2405.1 (302.1) Structural safety. The building shall not be  only  into  a  bedroom  or  bathroom,  and  such  room  or
         weakened by the installation of any gas piping. In the process  space is used for no other purpose and is provided with
         of installing or repairing any gas piping, the finished floors,  a  solid  weather-stripped  door  equipped  with  an
         walls, ceilings, tile work or any other part of the building or  approved self-closing device. Combustion air shall be