P. 571

FUEL GAS



              of all appliances in the space, but not less than 100 square  Where  directly  communicating  with  the  outdoors,  or
                            2
              inches  (0.06  m ).  One  permanent  opening  shall  where communicating with the outdoors through vertical
              commence within 12 inches (305 mm) of the top and one  ducts, each opening shall have a minimum free area of 1
                                                                                               2
              permanent  opening  shall  commence  within  12  inches  square inch per 4,000 Btu/h (550 mm /kW) of total input
              (305 mm) of the bottom of the enclosure. The minimum  rating  of  all  appliances  in  the  enclosure  [see  Figures
              dimension of air openings shall be not less than 3 inches  G2407.6.1(1) and G2407.6.1(2)].
              (76 mm).
                                                                   Where communicating with the outdoors through hori-
              G2407.5.3.2 (304.5.3.2) Combining spaces in differ-  zontal ducts, each opening shall have a minimum free area
                                                                                                              2
              ent stories. The volumes of spaces in different stories  of not less than 1 square inch per 2,000 Btu/h (1100 mm /
              shall be considered to be communicating spaces where  kW) of total input rating of all appliances in the enclosure
              such spaces are connected by one or more permanent  [see Figure G2407.6.1(3)].
              openings in doors or floors having a total minimum free  G2407.6.2  (304.6.2)  One-permanent-opening  method.
                                                     2
              area of 2 square inches per 1,000 Btu/h (4402 mm /kW)  One  permanent  opening,  commencing  within  12  inches
              of total input rating of all appliances.           (305 mm) of the top of the enclosure, shall be provided.
         G2407.6 (304.6) Outdoor combustion air. Outdoor combus-  The  appliance  shall  have  clearances  of  not  less  than  1
         tion air shall be provided through opening(s) to the outdoors in  inch (25 mm) from the sides and back and 6 inches (152
         accordance with Section G2407.6.1 or G2407.6.2. The mini-  mm) from the front of the appliance. The opening shall
         mum dimension of air openings shall be not less than 3 inches  directly communicate with the outdoors or through a verti-
         (76 mm).                                                cal or horizontal duct to the outdoors, or spaces that freely
           G2407.6.1  (304.6.1)  Two-permanent-openings  method.  communicate  with  the  outdoors  (see  Figure  G2407.6.2)
           Two permanent openings, one commencing within 12 inches  and shall have a minimum free area of 1 square inch per
                                                                                  2
           (305 mm) of the top and one commencing within 12 inches  3,000 Btu/h (734 mm /kW) of the total input rating of all
           (305 mm) of the bottom of the enclosure, shall be provided.  appliances located in the enclosure and not less than the
           The openings shall communicate directly or by ducts with  sum of the areas of all vent connectors in the space.
           the outdoors or spaces that freely communicate with the out-
           doors.










































                                                FIGURE G2407.6.1(1) [304.6.1(1)]
               ALL AIR FROM OUTDOORS—INLET AIR FROM VENTILATED CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC
                                                   (see Section G2407.6.1)


         546                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.