Page 576 - 2018_IRC
P. 576

FUEL GAS







                                                                             COMBUSTIBLE
                                                                             WALL
                                   1 INCH MINIMUM
                                   AIRSPACE
                                   BETWEEN
                                   MASONRY AND
                                   COMBUSTIBLE
                                   WALL
                                          4-INCH
                                          NOMINAL
                                          BRICK WALL
                                                                                      CORRUGATED
                                                                                      METAL WALL
                                                                                      TIES
                                     BOTTOM AND TOP
                                     COURSE OF BRICKS
                                     STAGGERED FOR
                                     VENTILATION
                                     A STRIP OF HEAVY-
                                     GAUGE STEEL USED
                                     FOR ADDED SUPPORT
                                       NOTE: DO NOT PLACE
                                       MASONRY WALL TIES
                                       DIRECTLY BEHIND
                                       APPLIANCE OR
                                       CONNECTOR

                                                                MASONRY WALL TIE





             For SI: 1 inch = 25.4 mm.
                                                     FIGURE G2409.2(3) [308.2(3)]
                                               MASONRY CLEARANCE REDUCTION SYSTEM
               G2409.3.4 (308.3.4) Clearance from supply ducts. Sup-  combustible material attached to combustible material, the
               ply air ducts connecting to listed central heating furnaces  clearance shall be measured to the surface of the plaster or
               shall have the same minimum clearance to combustibles as  other noncombustible finish where the clearance specified
               required for the furnace supply plenum for a distance of not  is 2 inches (51 mm) or less.
               less than 3 feet (914 mm) from the supply plenum. Clear-  G2409.4.4 (308.4.5) Clearance from supply ducts. Sup-
               ance is not required beyond the 3-foot (914 mm) distance.  ply air ducts connecting to listed central heating furnaces
             G2409.4  (308.4)  Central-heating  boilers  and  furnaces.  shall have the same minimum clearance to combustibles as
             Clearance requirements for central-heating boilers and  fur-  required for the furnace supply plenum for a distance of
             naces  shall  comply  with  Sections  G2409.4.1  through  not  less  than  3  feet  (914  mm)  from  the  supply  plenum.
             G2409.4.5. The clearance to these appliances shall not inter-  Clearance is not required beyond the 3-foot (914 mm) dis-
             fere with combustion air; draft hood clearance and relief; and  tance.
             accessibility for servicing.                            G2409.4.5 (308.4.3) Clearance for servicing appliances.
               G2409.4.1  (308.4.1)  Appliances  clearances.  Central-  Front clearance shall be sufficient for servicing the burner
               heating  furnaces  and  low-pressure  boilers  shall  be  and the furnace or boiler.
               installed with clearances in accordance with the manufac-
               turer’s instructions.
               G2409.4.2 (308.4.2) Clearance reduction. Central-heating         SECTION G2410 (309)
               furnaces and low-pressure boilers shall be permitted to be           ELECTRICAL
               installed with reduced clearances to combustible material  G2410.1 (309.1) Grounding. Gas piping shall not be used as
               provided that the combustible material or appliance is pro-  a grounding electrode.
               tected as described in Table G2409.2 and such reduction is  G2410.2  (309.2)  Connections.  Electrical  connections
               allowed by the manufacturer’s instructions.        between  appliances  and  the  building  wiring,  including  the

               G2409.4.3 (308.4.4) Plenum clearances. Where the fur-  grounding  of  the appliances,  shall  conform to  Chapters  34
               nace plenum is adjacent to plaster on metal lath or non-  through 43.