FUEL GAS


                           SECTION G2411 (310)                    and includes the design, materials, components, fabrication,
                          ELECTRICAL BONDING                      assembly,  installation,  testing,  inspection,  operation  and
             G2411.1 (310.1) Pipe and tubing other than CSST. Each  maintenance of such piping systems.
             above-ground portion of a gas piping system other than corru-  G2412.1.1  (401.1.1)  Utility  piping  systems  located
             gated stainless steel tubing (CSST) that is likely to become  within  buildings.  Utility  service  piping  located  within
             energized shall be electrically continuous and bonded to an  buildings shall be installed in accordance with the struc-
             effective  ground-fault  current  path.  Gas piping  other  than  tural safety and fire protection provisions of this code.
             CSST shall be considered to be bonded where it is connected
             to an appliance that is connected to the equipment grounding  G2412.2  (401.2)  Liquefied  petroleum  gas  storage.  The
             conductor of the circuit that supplies that appliance.  storage system for liquefied petroleum gas shall be designed
                                                                  and installed in accordance with the International Fire Code
             G2411.2  (310.2)  CSST.  This  section  applies  to  corrugated  and NFPA 58.
             stainless steel tubing (CSST) that is not listed with an arc-
             resistant jacket or coating system in accordance with ANSI  G2412.3 (401.3) Modifications to existing systems. In mod-
             LC1/CSA 6.26. CSST gas piping systems and piping systems  ifying  or  adding  to  existing  piping systems,  sizes  shall  be
             containing one or more segments of CSST shall be electri-  maintained in accordance with this chapter.
             cally continuous and bonded to the electrical service ground-  G2412.4  (401.4)  Additional  appliances.  Where  an  addi-
             ing  electrode  system  or,  where  provided,  the  lightning  tional appliance is to be served, the existing piping shall be
             protection grounding electrode system.               checked to determine if it has adequate capacity for all appli-
               G2411.2.1  (310.2.1)  Point  of  connection.  The  boding  ances  served.  If  inadequate,  the  existing  system  shall  be
               jumper  shall  connect  to  a  metallic  pipe,  pipe  fitting  or  enlarged as required or separate piping of adequate capacity
               CSST fitting.                                      shall be provided.
               G2411.2.2 (310.2.2) Size and material of jumper. The  G2412.5  (401.5)  Identification.  For  other  than  steel  pipe,
               bonding jumper shall be not smaller than 6 AWG copper  exposed piping shall be identified by a yellow label marked
               wire or equivalent.                                “Gas” in black letters. The marking shall be spaced at inter-
                                                                  vals not exceeding 5 feet (1524 mm). The marking shall not
               G2411.2.3 (310.2.3) Bonding jumper length. The length
               of  the  bonding  jumper  between  the  connection  to  a  gas  be required on pipe located in the same room as the appliance
                                                                  served.
               piping system and the connection to a grounding electrode
               system shall not exceed 75 feet (22 860 mm). Any addi-  G2412.6  (401.6)  Interconnections.  Where  two  or  more
               tional grounding electrodes installed to meet this require-  meters are installed on the same premises but supply separate
               ment shall be bonded to the electrical service grounding  consumers, the piping systems shall not be interconnected on
               electrode system or, where provided, the lightning protec-  the outlet side of the meters.
               tion grounding electrode system.
                                                                  G2412.7 (401.7) Piping meter identification. Piping from
               G2411.2.4 (310.2.4) Bonding connections. Bonding con-  multiple meter installations shall be marked with an approved
               nections shall be in accordance with NFPA 70.      permanent  identification  by  the  installer  so  that  the  piping
               G2411.2.5  (310.2.5)  Connection  devices.  Devices  used  system supplied by each meter is readily identifiable.
               for making the bonding connections shall be listed for the  G2412.8 (401.8) Minimum sizes. Pipe utilized for the instal-
               application in accordance with UL 467.             lation, extension and alteration of any piping system shall be
             G2411.3 (310.3) Arc-resistant CSST. This section applies to  sized  to  supply  the  full  number  of  outlets  for  the  intended
             corrugated stainless steel tubing (CSST) that is listed with an  purpose and shall be sized in accordance with Section G2413.
             arc-resistant  jacket  or  coating  system  in  accordance  with  G2412.9 (401.9) Identification. Each length of pipe and tub-
             ANSI LC1/CSA 6.26. The CSST shall be electrically contin-  ing and each pipe fitting, utilized in a fuel gas system, shall
             uous  and  bonded  to  an effective  ground fault  current path.  bear the identification of the manufacturer.
             Where  any  CSST  component  of  a  piping  system  does  not
             have an arc-resistant jacket  or coating system, the  bonding  Exceptions:
             requirements of Section G2411.2 shall apply. Arc-resistant-  1. Steel pipe sections that are 2 feet (610 mm) and less
             jacketed CSST shall be considered to be bonded where it is  in length and are cut from longer sections of pipe.
             connected to an appliance that is connected to the appliance
             grounding  conductor  of  the  circuit  that  supplies  that  appli-  2. Steel pipe fittings 2 inches and less in size.
             ance.                                                     3. Where  identification  is  provided  on  the  product
                                                                         packaging or crating.
                           SECTION G2412 (401)                         4. Where other approved documentation is provided.
                                 GENERAL                          G2412.10 (401.10) Piping materials standards. Piping, tub-
             G2412.1 (401.1) Scope. This section shall govern the design,  ing and fittings shall be manufactured to the applicable refer-
             installation, modification and maintenance of piping systems.  enced  standards,  specifications  and  performance  criteria
             The applicability of this code to piping systems extends from  listed in Section G2414 and shall be identified in accordance
             the point of delivery to the connections with the appliances  with Section G2412.9.