Page 622 - 2018_IRC
P. 622

FUEL GAS



             Category I appliances to maintain a nonpositive vent static  3. Vents for appliance draft hood outlets or flue collars
             pressure  when  tested  in  accordance  with  nationally  recog-  larger than 12 inches (305 mm) in diameter are not
             nized standards.                                            reduced more than two table sizes.
             FAN-ASSISTED COMBUSTION SYSTEM. An appliance              4. The maximum capacity listed in the tables for a fan-
             equipped with an integral mechanical means to either draw or  assisted appliance is reduced by 10 percent (0.90 ×
             force products of combustion through the combustion cham-   maximum table capacity).
             ber or heat exchanger.
                                                                       5. The draft hood outlet is greater than 4 inches (102
             FAN Min. The minimum input rating of a Category I fan-      mm) in diameter. Do not connect a 3-inch-diameter
             assisted appliance attached to a vent or connector.         (76 mm) vent to a 4-inch-diameter (102 mm) draft
             FAN Max. The maximum input rating of a Category I fan-      hood outlet. This provision shall not apply to fan-
             assisted appliance attached to a vent or connector.         assisted appliances.
             NAT Max. The maximum input rating of a Category I draft-  G2428.2.3 (504.2.3) Vent offsets. Single-appliance vent-
             hood-equipped appliance attached to a vent or connector.  ing configurations with zero (0) lateral lengths in Tables
                                                                     G2428.2(1) and G2428.2(2) shall not have elbows in the
             FAN + FAN. The maximum combined appliance input rat-    venting system.  Single-appliance  venting  configurations
             ing  of  two  or  more  Category  I  fan-assisted  appliances  with  lateral  lengths  include  two  90-degree  (1.57  rad)
             attached to the common vent.                            elbows. For each additional elbow up to and including 45
             FAN + NAT. The maximum combined appliance input rat-    degrees  (0.79  rad),  the  maximum  capacity  listed  in  the
             ing  of  one  or  more  Category  I  fan-assisted  appliances  and  venting  tables  shall  be  reduced  by  5  percent.  For  each
             one  or  more  Category  I  draft-hood-equipped  appliances  additional elbow greater than 45 degrees (0.79 rad) up to
             attached to the common vent.                            and including 90 degrees (1.57 rad), the maximum capac-
                                                                     ity listed in the venting tables shall be reduced by 10 per-
             NA. Vent configuration is not allowed due to potential for
             condensate formation or pressurization of the venting system,  cent.  Where  multiple  offsets  occur  in  a  vent,  the  total
             or not applicable due to physical or geometric restraints.  lateral length of all offsets combined shall not exceed that
                                                                     specified in Tables G2428.2(1) and G2428.2(2).
             NAT + NAT. The maximum combined appliance input rat-    G2428.2.4  (504.2.4)  Zero  lateral.  Zero  (0)  lateral  (L)
             ing  of  two  or  more  Category  I  draft-hood-equipped  appli-  shall apply only to a straight vertical vent attached to a top
             ances attached to the common vent.
                                                                     outlet draft hood or flue collar.
             G2428.2  (504.2)  Application  of  single-appliance  vent
             Tables  G2428.2(1)  and  G2428.2(2).  The  application  of  G2428.2.5  (504.2.5)  High-altitude  installations.  Sea-
             Tables  G2428.2(1)  and  G2428.2(2)  shall  be  subject  to  the  level input ratings shall be used when determining maxi-
             requirements of Sections G2428.2.1 through G2428.2.17.  mum capacity for high-altitude installation. Actual input,
                                                                     derated  for  altitude,  shall  be  used for  determining  mini-
               G2428.2.1  (504.2.1)  Vent  obstructions.  These  venting  mum capacity for high-altitude installation.
               tables shall not be used where obstructions, as described in
               Section G2427.15, are installed in the venting system. The  G2428.2.6 (504.2.6) Multiple input rate appliances. For
               installation  of  vents  serving  listed  appliances  with  vent  appliances with more than one input rate, the minimum
               dampers shall be in accordance with the appliance manu-  vent capacity (FAN Min) determined from the tables shall
               facturer’s instructions or in accordance with the following:  be less than the lowest appliance input rating, and the max-
                                                                     imum  vent  capacity  (FAN  Max/NAT  Max)  determined
                  1. The maximum capacity of the vent system shall be  from the tables shall be greater than the highest appliance
                    determined using the “NAT Max” column.           rating input.
                  2. The minimum capacity shall be determined as if the  G2428.2.7  (504.2.7)  Liner  system  sizing  and  connec-
                    appliance were a fan-assisted appliance, using the  tions. Listed corrugated metallic chimney liner systems in
                    “FAN  Min”  column  to  determine  the  minimum  masonry chimneys shall be sized by using Table G2428.2(1)
                    capacity of the vent system. Where the correspond-  or G2428.2(2) for Type B vents with the maximum capacity
                    ing  “FAN  Min”  is  “NA,”  the  vent  configuration  reduced by 20 percent (0.80 × maximum capacity) and the
                    shall  not  be  permitted  and  an  alternative  venting  minimum  capacity  as  shown  in  Table  G2428.2(1)  or
                    configuration shall be utilized.                 G2428.2(2).  Corrugated  metallic  liner  systems  installed
               G2428.2.2 (504.2.2) Minimum size. Where the vent size  with bends or offsets shall have their maximum capacity
               determined from the tables is smaller than the appliance  further reduced in accordance with Section G2428.2.3. The
               draft hood outlet or flue collar, the smaller size shall be  20-percent reduction for corrugated metallic chimney liner
               permitted  to  be  used  provided  that  all  of  the  following  systems  includes  an  allowance  for  one  long-radius  90-
               requirements are met:                                 degree (1.57 rad) turn at the bottom of the liner.
                  1. The total vent height (H) is not less than 10 feet (3048  Connections between chimney liners and listed double-
                    mm).                                             wall  connectors  shall  be  made  with  listed  adapters
                                                                     designed for such purpose.
                  2. Vents for appliance draft hood outlets or flue collars
                    12 inches (305 mm) in diameter or smaller are not  G2428.2.8 (504.2.8) Vent area and diameter. Where the
                    reduced more than one table size.                vertical vent has a larger diameter than the vent connector,

             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               597
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.