FUEL GAS



           rad)  turn  at  the  bottom  of  the  liner.  Where  double-wall  must be sized using Table G2428.3(2) or G2428.3(4), as
           connectors are required, tee and wye fittings used to con-  appropriate.
           nect to the common vent chimney liner shall be listed dou-  G2428.3.19 (504.3.23) Draft hood conversion accesso-
           ble-wall fittings. Connections between chimney liners and  ries.  Draft hood  conversion  accessories  for  use  with
           listed  double-wall  fittings  shall  be  made  with  listed  masonry chimneys venting listed Category I fan-assisted
           adapter fittings designed for such purpose.           appliances shall be listed and installed in accordance with
           G2428.3.16  (504.3.20)  Chimney  and  vent  location.  the manufacturer’s instructions for such listed accessories.
           Tables  G2428.3(1),  G2428.3(2),  G2428.3(3)  and     G2428.3.20 (504.3.24) Multiple sizes permitted. Where
           G2428.3(4) shall be used only for chimneys and vents not  a table permits more than one diameter of pipe to be used
           exposed  to  the  outdoors  below  the  roof  line.  A  Type  B  for a connector or vent, all of the permitted sizes shall be
           vent or listed chimney lining system passing through an  permitted to be used.
           unused masonry chimney flue shall not be considered to
           be exposed to the outdoors. Where vents extend outdoors  G2428.3.21 (504.3.25) Table interpolation. Interpolation
           above the roof more than 5 feet (1524 mm) higher than  shall be permitted in calculating capacities for vent dimen-
           required by Figure G2427.6.4 and where vents terminate  sions that fall between table entries.
           in accordance with Section G2427.6.4, Item 2, the outdoor  G2428.3.2   (504.3.2   Extrapolatio   prohibited.
           portion of the vent shall be enclosed as required by this  Extrapolation beyond the table entries shall not be permit-
           section for vents not considered to be exposed to the out-  ted.
           doors or such venting system shall be engineered. A Type  G2428.3.23  (504.3.27)  Engineering  calculations.  For
           B vent shall not be considered to be exposed to the out-  vent heights less than 6 feet (1829 mm) and greater than
           doors where it passes through an unventilated enclosure or  shown in the tables, engineering methods shall be used to
           chase insulated to a value of not less than R8.
                                                                 calculate vent capacities.
           G2428.3.17 (504.3.21) Connector maximum and mini-     G2428.3.24 (504.3.28) Height entries. Where the actual
           mum size. Vent connectors shall not be increased in size  height of a vent falls between entries in the height column
           more than two sizes greater than the listed appliance cate-  of  the  applicable  table  in  Tables  G2428.3(1)  through
           gorized vent diameter, flue collar diameter or draft hood  G2428.3(4), either interpolation shall be used or the lower
           outlet diameter. Vent connectors for draft-hood-equipped  appliance input rating shown in the table shall be used for
           appliances shall not be smaller than the draft hood outlet  FAN Max and NAT Max column values and the higher
           diameter. Where a vent connector size(s) determined from  appliance input rating shall be used for the FAN Min col-
           the tables for a  fan-assisted appliance(s)  is smaller than  umn values.
           the flue collar diameter, the use of the smaller size(s) shall
           be permitted provided that the installation complies with
           all of the following conditions:                                 SECTION G2429 (505)
              1. Vent connectors for fan-assisted appliance flue col-  DIRECT-VENT, INTEGRAL VENT,
                lars 12 inches (305 mm) in diameter or smaller are         MECHANICAL VENT AND
                not reduced by more than one table size [for exam-  VENTILATION/EXHAUST HOOD VENTING
                ple, 12 inches to 10 inches (305 mm to 254 mm) is a  G2429.1 (505.1) General. The installation of direct-vent and
                one-size reduction] and those larger than 12 inches  integral vent appliances shall be in accordance with Section
                (305 mm) in diameter are not reduced more than two  G2427.  Mechanical  venting systems  shall  be  designed  and
                table sizes [for example, 24 inches to 20 inches (610  installed in accordance with Section G2427.
                mm to 508 mm) is a two-size reduction].
              2. The  fan-assisted  appliance(s)  is  common  vented
                with a draft-hood-equipped appliance(s).                    SECTION G2430 (506)
              3. The vent connector has a smooth interior wall.          FACTORY-BUILT CHIMNEYS
                                                              G2430.1 (506.1) Listing. Factory-built chimneys for building
           G2428.3.18 (504.3.22) Component commingling. Com-  heating appliances producing flue gases having a temperature
           binations  of  pipe  sizes  and  combinations  of  single-wall  not greater than 1,000ºF (538ºC), measured at the entrance to
           and double-wall  metal  pipe  shall be  allowed within  any  the chimney, shall be listed and labeled in accordance with
           connector run(s) or within the common vent, provided that  UL 103 and shall be installed and terminated in accordance
           all of the appropriate tables permit all of the desired sizes  with the manufacturer’s instructions.
           and types of pipe, as if they were used for the entire length
           of the  subject connector or  vent.  Where single-wall and  G2430.2 (506.2) Support. Where factory-built chimneys are
           Type B double-wall metal pipes are used for vent connec-  supported by structural members, such as joists and rafters,
           tors  within  the  same  venting  system,  the  common  vent  such  members  shall  be  designed  to  support  the  additional
                                                              load.