GENERAL PLUMBING REQUIREMENTS


                                                          TABLE P2605.1
                                                         PIPING SUPPORT
                                                                               MAXIMUM HORIZONTAL   MAXIMUM VERTICAL
                                      PIPING MATERIAL
                                                                                  SPACING (feet)      SPACING (feet)
             ABS pipe                                                                  4                  1  0  b
             Aluminum tubing                                                          10                  15
             Cast-iron pipe                                                           5 a                 15
             Copper or copper-alloy pipe                                              12                  10
                                     1
             Copper or copper-alloy tubing (1 / inches in diameter and smaller)        6                  10
                                      4
                                     1
             Copper or copper-alloy tubing (1 / inches in diameter and larger)        10                  10
                                      2
             Cross-linked polyethylene (PEX) pipe, 1 inch and smaller            2.67 (32 inches)         10 b
                                           1
             Cross-linked polyethylene (PEX) pipe, 1 /  inch and larger                4                  10 b
                                            4
             Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe   2.67 (32 inches)  4 b
             CPVC pipe or tubing (1 inch in diameter and smaller)                      3                  10 b
                              1
             CPVC pipe or tubing (1 / inches in diameter and larger)                   4                  10 b
                               4
             Lead pipe                                                             Continuous              4
             PB pipe or tubing                                                   2.67 (32 inches)          4
             Polyethylene of raised temperature (PE-RT) pipe, 1 inch and smaller  2.67 (32 inches)        10 b
                                                  1
             Polyethylene of raised temperature (PE-RT) pipe, 1 /  inch and larger     4                  10 b
                                                   4
             Polypropylene (PP) pipe or tubing (1 inch and smaller)              2.67 (32 inches)         10 b
                                        1
             Polypropylene (PP) pipe or tubing (1 / inches and larger)                 4                  10 b
                                         4
             PVC pipe                                                                  4                  1  0  b
             Stainless steel drainage systems                                         10                  10 b
             Steel pipe                                                               12                  15
             For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
             a. The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed.
             b. For sizes 2 inches and smaller, a guide shall be installed midway between required vertical supports. Such guides shall prevent pipe movement in a direction
               perpendicular to the axis of the pipe.

                              SECTION P2607                                        SECTION P2609
                     WATERPROOFING OF OPENINGS                          MATERIALS EVALUATION AND LISTING
             P2607.1 Pipes penetrating roofs. Where a pipe penetrates a  P2609.1  Identification. Each  length  of  pipe  and  each  pipe
             roof,  a  flashing  of  lead,  copper,  galvanized  steel  or  an  fitting, trap, fixture, material and device utilized in a plumb-
             approved elastomeric material shall be installed in a manner  ing system shall bear the identification of the manufacturer
             that prevents water entry into the building. Counterflashing  and any markings required by the applicable referenced stan-
             into the opening of pipe serving as a vent terminal shall not  dards.  Nipples  created  from  the  cutting  and  threading  of
             reduce the required internal cross-sectional area of the vent  approved pipe shall not be required to be identified.
             pipe to less than the internal cross-sectional area of one pipe  Exception: Where the manufacturer identification cannot
             size smaller.                                           be marked on pipe fittings and pipe nipples because of the
             P2607.2  Pipes  penetrating  exterior  walls.  Where  a  pipe  small  size  of  such  fittings,  the  identification  shall  be
             penetrates an exterior wall, a waterproof seal shall be made  printed on the item packaging or on documentation pro-
             on the exterior of the wall by one of the following methods:  vided with the item.
               1. A waterproof sealant applied at the joint between the  P2609.2  Installation  of  materials.  Materials  used  shall  be
                  wall and the pipe.                              installed in strict accordance with the standards under which
               2. A flashing of an approved elastomeric material.  the materials are accepted and approved. In the absence of
                                                                  such installation procedures, the manufacturer’s instructions
                                                                  shall be followed. Where the requirements of referenced stan-
                              SECTION P2608                       dards or manufacturer’s instructions do not conform to  the
                              WORKMANSHIP                         minimum provisions of this code, the provisions of this code
             P2608.1 General. Valves, pipes and fittings shall be installed  shall apply.
             in  correct  relationship  to  the  direction  of  the  flow.  Burred  P2609.3 Plastic pipe, fittings and components. Plastic pipe,
             ends shall be reamed to the full bore of the pipe.   fittings and components shall be third-party certified as con-
                                                                  forming to NSF 14.