Page 650 - 2018_IRC
P. 650

PLUMBING FIXTURES



               P2706.1.1 Hub drains. Hub drains shall be in the form of  from the finished interior dimension of the compart-
               a hub or a pipe that extends not less than 1 inch (25 mm)  ment provided that  the  shower compartment has a
               above a water-impervious floor.                           cross-sectional  area  of  not  less  than  1,300  square
                                                                                      2
               P2706.1.2  Standpipes.  Standpipes  shall  extend  not  less  inches (0.838 m ).
               than 18 inches (457 mm) and not greater than 42 inches  P2708.1.1  Access.  The  shower  compartment  access  and
               (1067 mm) above the trap weir.                        egress  opening  shall  have  a  clear  and  unobstructed  fin-
                  P2706.1.2.1 Laundry tray connection to standpipe.  ished width of not less than 22 inches (559 mm).
                  Where a laundry tray waste line connects into a stand-  P2708.2 Shower drain. Shower drains shall have an outlet
                  pipe for an automatic clothes washer drain, the stand-  size of not less than 1 /  inches [38 mm] in diameter.
                                                                                   1
                  pipe  shall  extend  not  less  than  30  inches  (762  mm)        2
                  above the standpipe trap weir and shall extend above  P2708.3 Water supply riser. Water supply risers from the
                  the flood level rim of the laundry tray. The outlet of the  shower valve to the shower head outlet, whether exposed or
                  laundry tray shall not  be  greater than 30  inches (762  concealed,  shall  be  attached  to  the  structure  using  support
                  mm) horizontally from the standpipe trap.       devices designed for use with the specific piping material or
                                                                  fittings anchored with screws.
             P2706.2 Prohibited waste receptors. Plumbing fixtures that
             are used for washing or bathing shall not be used to receive  P2708.4 Shower control valves. Individual shower and tub/
             the discharge of indirect waste piping.              shower  combination  valves  shall  be  equipped  with  control
                                                                  valves of the pressure-balance, thermostatic-mixing or com-
               Exceptions:                                        bination  pressure-balance/thermostatic-mixing  valve  types
                  1. A kitchen sink trap is acceptable for use as a recep-  with a high limit stop in accordance with ASSE 1016/ASME
                    tor for a dishwasher.                         A112.1016/CSA B125.16. The high limit stop shall be set to
                  2. A laundry tray is acceptable for use as a receptor for  limit the water temperature to not greater than 120°F (49°C).
                    a clothes washing machine.                    In-line thermostatic valves shall not be used for compliance
                                                                  with this section.
                                                                  P2708.5 Hand showers. Hand-held showers shall conform to
                              SECTION P2707                       ASME  A112.18.1/CSA  B125.1.  Hand-held  showers  shall
                          DIRECTIONAL FITTINGS                    provide  backflow  protection  in  accordance  with  ASME
             P2707.1 Directional fitting required. Approved directional-  A112.18.1/CSA  B125.1 or  shall  be  protected against back-
             type  branch  fittings  shall  be  installed  in  fixture  tailpieces  flow by a device complying with ASME A112.18.3.
             receiving  the  discharge  from  food-waste  disposer  units  or
             dishwashers.
                                                                                   SECTION P2709
                                                                                SHOWER RECEPTORS
                              SECTION P2708                       P2709.1 Construction. Where a shower receptor has a fin-
                                SHOWERS                           ished curb threshold, it shall be not less than 1 inch (25 mm)
             P2708.1 General. Shower compartments shall have not less  below the sides and back of the receptor. The curb shall be
                                       2
             than  900  square  inches  (0.6  m )  of  interior  cross-sectional  not less than 2 inches (51 mm) and not more than 9 inches
             area. Shower compartments shall be not less than 30 inches  (229 mm) deep when measured from the top of the curb to the
             (762 mm) in minimum dimension measured from the finished  top  of  the  drain.  The  finished  floor  shall  slope  uniformly
                                                                                          1
             interior dimension of the shower compartment, exclusive of  toward the drain not less than  /  unit vertical in 12 units hori-
                                                                                           4
             fixture  valves,  shower  heads,  soap  dishes,  and  safety  grab  zontal (2-percent slope) nor more than  /  unit vertical per 12
                                                                                                  1
                                                                                                   2
             bars or rails. The minimum required area and dimension shall  units  horizontal  (4-percent  slope)  and  floor  drains  shall  be
             be measured from the finished interior dimension at a height  flanged to provide a water-tight joint in the floor.
             equal to the top of the threshold and at a point tangent to its  P2709.2  Lining  required.  The  adjoining  walls  and  floor
             centerline and shall be continued to a height of not less than  framing enclosing on-site built-up shower receptors shall be
             70 inches (1778 mm) above the shower drain outlet. Hinged
             shower doors shall open outward. The wall area above built-  lined with one of the following materials:
             in tubs having installed shower heads and in shower compart-  1. Sheet lead.
             ments  shall  be  constructed  in  accordance  with  Section  2. Sheet copper.
             R702.4. Such walls shall form a water-tight joint with each
             other and with either the tub, receptor or shower floor.  3. Plastic liner material that complies with ASTM D4068
                                                                       or ASTM D4551.
               Exceptions:
                                                                     4. Hot mopping in accordance with Section P2709.2.3.
                  1. Fold-down  seats  shall  be  permitted  in  the  shower,
                                                             2
                    provided that the required 900-square-inch (0.6 m )  5. Sheet-applied  load-bearing,  bonded  waterproof  mem-
                    dimension  is  maintained  when  the  seat  is  in  the  branes that comply with ANSI A118.10.
                    folded-up position.                              The lining material shall extend not less than 2 inches (51
                  2. Shower  compartments  having  not  less  than  25  mm) beyond or around the rough jambs and not less than 2
                    inches (635 mm) in minimum dimension measured  inches (51 mm) above finished thresholds. Sheet-applied load