Page 664 - 2018_IRC
P. 664

WATER SUPPLY AND DISTRIBUTION


                                                           2
                    3. Bathrooms not more than 55 square feet (5.1 m ) in  shall  be  separated  from  heat  sources  as  required  by  the
                       area.                                         sprinkler manufacturer’s installation instructions.
                    4. Garages;  carports;  exterior  porches;  unheated  P2904.2.2 Intermediate temperature sprinklers. Sprin-
                       entry areas, such as mud rooms, that are adjacent  klers shall have an intermediate temperature rating not less
                       to an exterior door; and similar areas.       than  175°F  (79°C)  and  not  more  than  225°F  (107°C)
             P2904.2 Sprinklers. Sprinklers shall be new listed residen-  where installed in the following locations:
             tial sprinklers and shall be installed in accordance with the  1. Directly  under  skylights,  where  the  sprinkler  is
             sprinkler manufacturer’s instructions.                      exposed to direct sunlight.
               P2904.2.1  Temperature  rating  and  separation  from   2. In attics.
               heat sources. Except as provided for in Section P2904.2.2,  3. In concealed spaces located directly beneath a roof.
               sprinklers shall have a temperature rating of not less than
               135°F (57°C) and not more than 170°F (77°C). Sprinklers  4. Within the distance to a heat source as specified in
                                                                         Table P2904.2.2.


                                                          TABLE P2903.9.4
                                                             VALVES
                             MATERIAL                                           STANDARD
                                                     ASME A112.4.14, ASME A112.18.1/CSA B125.1, ASTM F1970, CSA B125.3,
              Chlorinated polyvinyl chloride (CPVC) plastic
                                                     MSS SP-122
                                                     ASME A112.4.14, ASME A112.18.1/CSA B125.1, ASME B16.34, CSA B125.3,
              Copper or copper alloy
                                                     MSS SP-67, MSS SP-80, MSS SP-110, MSS SP-139
                                                     ASTM A126, AWWA C500, AWWA C504, AWWA C507, MSS SP-42, MSS SP-67,
              Gray and ductile iron
                                                     MSS SP-70, MSS SP-71, MSS SP-72, MSS SP-78
              Cross-linked polyethylene (PEX) plastic  ASME A112.4.14, ASME A112.18.1/CSA B125.1, CSA B125.3, NSF 359
              Polypropylene (PP) plastic             ASME A112.4.14, ASTM F2389
              Polyvinyl chloride (PVC) plastic       ASME A112.4.14, ASTM F1970, MSS SP-122











                                                                                   INSULATED
                                                                                   FRAME WALL

                                          FLOOR
                                                                                             FREEZE-PROOF
                                                                                             SILL FAUCET

                          SUPPLY PIPE               LONG VALVE
                                                    STEM



                              VALVE SEAT
                                                  SHANK




                                                                                   FOUNDATION WALL
                             HEATED BASEMENT


                                                         FIGURE P2903.10
                              TYPICAL FROSTPROOF HOSE BIBB INSTALLATION NOT REQUIRING SEPARATE VALUE

             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               639
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   659   660   661   662   663   664   665   666   667   668   669