P. 659

WATER SUPPLY AND DISTRIBUTION


                                                      TABLE P2902.3.1
                                                     MINIMUM AIR GAPS
                                                                           MINIMUM AIR GAP
                           FIXTURE                           Away from a wall a             Close to a wall
                                                                 (inches)                      (inches)
                                                        Two times the diameter of the   Three times the diameter of the
         Effective openings greater than 1 inch
                                                             effective opening             effective opening
         Lavatories and other fixtures with effective opening not  1                            1  .  5
                    1
           greater than  /  inch in diameter
                     2
         Over-rim bath fillers and other fixtures with effective   2                             3
           openings not greater than 1 inch in diameter
         Sink, laundry trays, gooseneck back faucets and other
                                              3
           fixtures with effective openings not greater than  /  inch  1.5                      2.5
                                               4
           in diameter
         For SI: 1 inch = 25.4 mm.
         a. Applicable where walls or obstructions are spaced from the nearest inside edge of the spout opening a distance greater than three times the diameter of the
           effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls.
         P2902.5 Protection of potable water connections. Connec-  P2902.5.4.1 Additives or nonpotable source. Where
         tions  to  the  potable  water  shall  conform  to  Sections  systems  contain  chemical  additives  or  antifreeze,  or
         P2902.5.1 through P2902.5.5.                              where systems are connected to a nonpotable secondary
           P2902.5.1 Connections to boilers. Where chemicals will  water  supply,  the  potable  water  supply  shall  be  pro-
           not be introduced into a boiler, the potable water supply to  tected against backflow by a reduced pressure principle
           the boiler shall be protected from the boiler by a backflow  backflow  prevention  assembly  or  a  reduced  pressure
           preventer with an intermediate atmospheric vent comply-  principle fire protection backflow prevention assembly.
           ing with ASSE 1012 or CSA B64.3. Where chemicals will   Where chemical additives or antifreeze is added to only
           be introduced into a boiler, the potable water supply to the  a  portion  of  an  automatic  fire  sprinkler  or  standpipe
           boiler shall be protected from the boiler by an air gap or a  system,  the  reduced  pressure  principle  fire  protection
           reduced pressure principle backflow prevention assembly  backflow preventer shall be permitted to be located so
           complying  with  ASSE  1013,  CSA  B64.4  or  AWWA      as to isolate that portion of the system.
           C511.                                                 P2902.5.5 Solar thermal systems. Where a solar thermal
           P2902.5.2  Heat  exchangers.  Heat  exchangers  using  an  system heats potable water to supply a potable hot water
           essentially toxic transfer fluid shall be separated from the  distribution or any other type of heating system, the solar
           potable water by double-wall construction. An air gap open  thermal  system  shall  be  in  accordance  with  Section
           to the atmosphere shall be provided between the two walls.  P2902.5.5.1, P2902.5.5.2 or P2902.5.5.3 as applicable.
           Single-wall construction heat exchangers shall be used only  P2902.5.5.1 Indirect systems. Water supplies of any
           where an essentially nontoxic transfer fluid is utilized.  type shall not be connected to the solar heating loop of
                                                                   an indirect solar thermal hot water heating system. This
           P2902.5.3  Lawn  irrigation  systems.  The  potable  water
           supply to lawn irrigation systems shall be protected against  requirement shall not prohibit the presence of inlets or
           backflow  by  an atmospheric vacuum  breaker,  a  pressure  outlets on the solar heating loop for the purposes of ser-
           vacuum-breaker assembly or a reduced pressure principle  vicing the fluid in the solar heating loop.
           backflow prevention assembly. Valves shall not be installed  P2902.5.5.2 Direct systems for potable water distri-
           downstream from an atmospheric vacuum breaker. Where    bution systems. Where a solar thermal system directly
           chemicals are introduced into the system, the potable water  heats potable water for a potable water distribution sys-
           supply shall be protected against backflow by a reduced  tem,  the  pipe,  fittings,  valves  and  other  components
           pressure principle backflow prevention assembly.        that are in contact with the potable water in the system
           P2902.5.4 Connections to automatic fire sprinkler sys-  shall comply with the requirements of Chapter 29.
           tems. The potable water supply to automatic fire sprinkler  P2902.5.5.3  Direct  systems  for  other  than  potable
           systems shall be protected against backflow by a double-  water  distribution  systems.  Where  a  solar  thermal
           check backflow prevention assembly, a double-check fire  system directly heats water for a system other than a
           protection backflow prevention assembly, a reduced pres-  potable water distribution system, a potable water sup-
           sure principle backflow prevention assembly or a reduced  ply connected to such system shall be protected by a
           pressure  principle  fire  protection  backflow  prevention  backflow  preventer  with  an  intermediate  atmospheric
           assembly.                                               vent complying with ASSE 1012. Where a solar ther-
              Exception:  Where  sprinkler  systems  are  installed  in  mal system directly heats chemically treated water for a
              accordance with Section P2904.1, backflow protection  system other than a potable water distribution system, a
              for the water supply system shall not be required.   potable water supply connected to such system shall be
                                                                   protected by a reduced pressure principle backflow pre-
                                                                   vention assembly complying with ASSE 1013.