CHAPTER 30

                                               SANITARY DRAINAGE



             User notes:
                About this chapter: Chapter 30 regulates methods and piping systems that remove water that has been used for purposes such as flushing
                water closets, bathing, culinary activities and equipment discharges. The types of materials, drainage fitting and connection methods for these
                systems, beginning at the receiving fixtures and ending at the point of disposal for the liquid waste, are covered. A design method for a gravity
                flow system of vertical and horizontal piping is provided based on the probability of flows from specific fixtures.
                Code development reminder: Code change proposals to this chapter will be considered by the IRC—Mechanical/Plumbing Code Develop-
                ment Committee during the 2018 (Group A) Code Development Cycle. See explanation on page iv.


                              SECTION P3001                       P3001.3 Flood-resistant installation. In flood hazard areas
                                 GENERAL                          as established by Table R301.2(1), drainage, waste and vent
             P3001.1 Scope. The provisions of this chapter shall govern  systems shall be located and installed to prevent infiltration
             the materials, design, construction and installation of sanitary  of floodwaters into the systems and discharges from the sys-
             drainage  systems.  Plumbing  materials  shall  conform  to  the  tems into floodwaters.
             requirements  of  this  chapter.  The  drainage,  waste and vent
             (DWV) system shall consist of piping for conveying wastes             SECTION P3002
             from  plumbing  fixtures,  appliances  and  appurtenances,              MATERIALS
             including fixture traps; above-grade drainage piping; below-
             grade  drains  within  the  building,  such  as  a  building drain;  P3002.1  Piping  within  buildings.  Drain,  waste  and  vent
             below- and above-grade venting systems; and piping to the  (DWV)  piping  in  buildings  shall  be  as  indicated  in Tables
             public sewer or private septic system.               P3002.1(1) and P3002.1(2) except that galvanized wrought-
                                                                  iron or galvanized steel pipe shall not be used underground
             P3001.2  Protection  from  freezing.  Portions  of  the  above-  and  shall  be  maintained  not  less  than  6  inches  (152  mm)
             grade DWV system, other than vent terminals, shall not be  above  ground.  Allowance  shall  be  made  for  the  thermal
             located outside of a building, in attics or crawl spaces, con-  expansion and contraction of plastic piping.
             cealed  in  outside  walls,  or  in  any  other  place  subjected  to
             freezing temperatures unless adequate provision is made to  P3002.2 Building sewer. Building sewer piping shall be as
             protect  them  from  freezing  by  insulation  or  heat  or  both,  indicated in Table P3002.2. Forced main sewer piping shall
             except in localities having a winter design temperature greater  conform to one of the standards for ABS plastic pipe, copper
             than 32°F (0°C) (ASHRAE 97.5 percent column, winter, see  or  copper-alloy  tubing,  PVC  plastic  pipe  or  pressure-rated
             Chapter 3).                                          pipe indicated in Table P3002.2.



                                                         TABLE P3002.1(1)
                                              ABOVE-GROUND DRAINAGE AND VENT PIPE
                                       MATERIAL                                           STANDARD
             Acrylonitrile butadiene styrene (ABS) plastic pipe in IPS diameters, including
               schedule 40, DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or ASTM D2661; ASTM F628; ASTM F1488; CSA B181.1
               composite wall
             Cast-iron pipe                                             ASTM A74; ASTM A888; CISPI 301
             Copper or copper-alloy pipe                                ASTM B42; ASTM B43; ASTM B302
                                                                        ASTM B75/B75M; ASTM B88; ASTM B251;
             Copper or copper-alloy tubing (Type K, L, M or DWV)
                                                                        ASTM B306
             Galvanized steel pipe                                      ASTM A53
             Polyolefin pipe                                            CSA B181.3
             Polyvinyl chloride (PVC) plastic pipe in IPS diameters, including schedule 40,
               DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or composite  ASTM D2665; ASTM F891; ASTM F1488; CSA B181.2
               wall
             Polyvinyl chloride (PVC) plastic pipe with a 3.25 inch O.D. and a solid, cellular  ASTM D2949; ASTM F1488
               core or composite wall
             Stainless steel drainage systems, Types 304 and 316L       ASME A112.3.1
             For SI: 1 inch = 25.4 mm.