Page 704 - 2018_IRC
P. 704

VENTS



                                TABLE P3107.3                     P3108.4 Vertical wet vent permitted. A combination of fix-
                             COMMON VENT SIZES
                                                                  tures located on the same floor level shall be permitted to be
                      PIPE SIZE         MAXIMUM DISCHARGE FROM    vented by a vertical wet vent. The vertical wet vent shall be
                       (inches)        UPPER FIXTURE DRAIN (d.f.u.)  considered  to  be  the  vent  for  the  fixtures  and  shall  extend
                         1
                        1 / 2                    1                from the connection of the dry vent down to the lowest fixture
                         2                       4                drain connection. Each wet-vented fixture shall connect inde-
                       1
                       2 /  to 3                 6                pendently  to  the  vertical  wet  vent.  All  water  closet  drains
                        2
                                                                  shall connect at the same elevation. Other fixture drains shall
             For SI: 1 inch = 25.4 mm.                            connect above or at the same elevation as the water closet fix-
                                                                  ture drains. The dry-vent connection to the vertical wet vent
                                                                  shall be an individual or common vent serving one or two fix-
                              SECTION P3108                       tures.
                               WET VENTING
             P3108.1 Horizontal wet vent permitted. Any combination  P3108.5  Trap  weir  to  wet-vent  distances.  The  maximum
                                                                  developed length of wet-vented fixture drains shall comply
             of fixtures within two bathroom groups located on the same  with Table P3105.1.
             floor level shall be permitted to be vented by a horizontal wet
             vent. The wet vent shall be considered to be the vent for the
             fixtures and shall extend from the connection of the dry vent         SECTION P3109
             along the direction of the flow in the drain pipe to the most       WASTE STACK VENT
             downstream fixture drain connection. Each fixture drain shall
             connect  horizontally  to  the  horizontal  branch  being  wet  P3109.1 Waste stack vent permitted. A waste stack shall be
             vented or shall have a dry vent. Each wet-vented fixture drain  considered to be a vent for all of the fixtures discharging to
             shall connect independently to the horizontal wet vent. Only  the stack where installed in accordance with the requirements
             the fixtures within the bathroom groups shall connect to the  of this section.
             wet-vented horizontal branch drain. Any additional fixtures  P3109.2 Stack installation. The waste stack shall be vertical,
             shall discharge downstream of the horizontal wet vent.  and  both  horizontal  and  vertical  offsets  shall  be  prohibited
             P3108.2 Dry  vent connection.  The  required  dry-vent  con-  between the lowest fixture drain connection and the highest
             nection  for wet-vented  systems  shall  comply with Sections  fixture drain connection to the stack. Every fixture drain shall
             P3108.2.1 and P3108.2.2.                             connect  separately  to  the  waste  stack.  The  stack  shall  not
                                                                  receive the discharge of water closets or urinals.
               P3108.2.1 Horizontal wet vent. The dry-vent connection
               for  a  horizontal  wet-vent  system  shall  be  an  individual  P3109.3 Stack vent. A stack vent shall be installed for the
               vent or a common vent for any bathroom group fixture,  waste stack. The size of the stack vent shall be not less than
               except an emergency floor drain. Where the dry vent con-  the size of the waste stack. Offsets shall be permitted in the
               nects to a water closet fixture drain, the drain shall connect  stack vent and shall be located not less than 6 inches (152
               horizontally to the horizontal wet-vent system. Not more  mm) above the flood level of the highest fixture, and shall be
               than one wet-vented fixture drain shall discharge upstream  in accordance with Section P3104.5. The stack vent shall be
               of the dry-vented fixture drain connection.        permitted to connect with other stack vents and vent stacks in
                                                                  accordance with Section P3113.3.
               P3108.2.2 Vertical wet vent. The dry-vent connection for
               a vertical wet-vent system shall be an individual vent or  P3109.4  Waste  stack  size.  The  waste  stack  shall  be  sized
               common vent for the most upstream fixture drain.   based on the total discharge to the stack and the discharge
                                                                  within a branch interval in accordance with Table P3109.4.
             P3108.3 Size. Horizontal and vertical wet vents shall be not  The waste stack shall be the same size throughout the length
             less than the size as specified in Table P3108.3, based on the  of the waste stack.
             fixture unit discharge to the wet vent. The dry vent serving
                                                                                     TABLE P3109.4
             the wet vent shall be sized based on the largest required diam-     WASTE STACK VENT SIZE
             eter  of  pipe  within  the  wet-vent  system  served  by  the  dry
             vent.                                                    STACK SIZE   MAXIMUM NUMBER OF FIXTURE UNITS (d.f.u.)
                                                                        (inches)    Total discharge into   Total discharge
                                TABLE P3108.3                                       one branch interval  for stack
                               WET VENT SIZE                             1 /              1                2
                                                                          1
                  WET VENT PIPE SIZE       FIXTURE UNIT LOAD               2
                       (inches)                 (d.f.u.)                  2               2                4
                         1
                        1 /                      1                       2 /            No limit           8
                                                                          1
                          2                                                2
                         2                       4                        3             N  o     l  i  m  i  t  2  4
                         1
                        2 /                      6                        4             N  o     l  i  m  i  t  5  0
                          2
                         3                       1  2             For SI: 1 inch = 25.4 mm.
                         4                       3  2
             For SI: 1 inch = 25.4 mm.



             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               679
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.