                About this chapter: Chapter 31 regulates connection locations, various venting system arrangements and the sizing of piping for vent sys-
                tems. The proper operation of a gravity flow drainage system (Chapter 30) depends on maintaining an air path throughout the system to pre-
                vent waste and odor "blow back" into fixtures and siphoning of the trap seal in fixture traps (Chapter 32).
                Code development reminder: Code change proposals to this chapter will be considered by the IRC—Mechanical/Plumbing Code
                Development Committee during the 2018 (Group A) Code Development Cycle. See explanation on page iv.




                              SECTION P3101                       that connects to the building drain. Such vent shall not be an
                              VENT SYSTEMS                        island fixture vent as permitted by Section P3112.
             P3101.1 General. This chapter shall govern the selection and  P3102.3 Size. The required vent shall be sized in accordance
             installation of piping, tubing and fittings for vent systems. This  with Section P3113.1 based on the required size of the build-
             chapter shall control the minimum diameter of vent pipes, cir-  ing drain.
             cuit vents, branch vents and individual vents, and the size and
             length of vents and various aspects of vent stacks and stack
             vents.  Additionally,  this  chapter  regulates  vent  grades  and    SECTION P3103
             connections, height above fixtures and relief vents for stacks       VENT TERMINALS
             and fixture traps, and the venting of sumps and sewers.  P3103.1 Vent pipes terminating outdoors. Vent pipes ter-
             P3101.2 Trap seal protection. The plumbing system shall be  minating outdoors shall be extended to the outdoors through
             provided  with  a  system  of  vent  piping  that  will  allow  the  the roof or a sidewall of the building in accordance with one
             admission or emission of air so that the liquid seal of any fix-  of  the  methods  identified  in  Sections  P3103.1.1  through
             ture trap shall not be subjected to a pressure differential of  P3103.1.4.
             more than 1 inch of water column (249 Pa).              P3103.1.1  Roof  extension.  Open  vent  pipes  that  extend
               P3101.2.1 Venting required. Every trap and trapped fix-  through a roof that do not meet the conditions of Section
               ture shall be vented in accordance with one of the venting  P3103.1.2  or  P3103.1.3  shall  terminate  not  less  than  6
               methods specified in this chapter.                    inches (150 mm) above the roof or 6 inches (150 mm) above
                                                                     the anticipated snow accumulation, whichever is greater.
             P3101.3 Use limitations. The plumbing vent system shall not
             be used for purposes other than the venting of the plumbing  P3103.1.2 Roof used for recreational puposes. Where a roof
             system.                                                 is to be used for assembly, as a promenade, observation deck
                                                                     or sunbathing deck, or for similar purposes, open vent pipes
             P3101.4 Extension outside a structure. In climates where
             the 97.5-percent value for outside design temperature is 0°F  shall terminate not less than 7 feet (2134 mm) above the roof.
             (-18°C) or less (ASHRAE 97.5-percent column, winter, see  P3103.1.3 Roof extension covered. Where an open vent
             Chapter 3), vent pipes installed on the exterior of the structure  pipe  terminates  above  a  sloped  roof  and  is  covered  by
             shall be protected against freezing by insulation, heat or both.  either a roof-mounted panel (such as a solar collector or
             Vent terminals shall be protected from frost closure in accor-  photovoltaic panel  mounted over  the  vent opening) or a
             dance with Section P3103.2.                             roof element (such as an architectural feature or a decora-
                                                                     tive shroud), the vent pipe shall terminate not less than 2
             P3101.5  Flood  resistance.  In  flood  hazard  areas  as  estab-
             lished by Table R301.2(1), vents shall be located at or above  inches  (51  mm)  above  the  roof  surface.  Such  roof  ele-
             the elevation required in Section R322.1 (flood hazard areas  ments shall be designed to prevent the adverse effects of
             including  A  Zones)  or  R322.2  (coastal  high-hazard  areas  snow accumulation and wind on the function of the vent.
             including V Zones).                                     The placement of a panel over a vent pipe and the design
                                                                     of a roof element covering the vent pipe shall provide for
                                                                     an open area for the vent pipe to the outdoors that is not
                              SECTION P3102                          less than the area of the pipe, as calculated from the inside
                     VENT STACKS AND STACK VENTS                     diameter  of  the  pipe.  Such  vent  terminals  shall  be  pro-
             P3102.1 Required vent extension. The vent system serving  tected by a method that prevents birds and rodents from
                                                                     entering or blocking the vent pipe opening.
             each building drain shall have not less than one vent pipe that
             extends to the outdoors.                                P3103.1.4  Sidewall  vent  terminal.  Vent  terminals
                                                                     extending through the wall shall terminate not less than 10
             P3102.2 Installation. The required vent shall be a dry vent  feet (3048 mm) from a lot line and not less than 10 feet
             that connects to the building drain or an extension of a drain  (3048 mm)  above the  highest grade  elevation within  10
                                                                     feet (3048 mm) in any direction horizontally of the vent