SWIMMING POOLS


             E4206.3 Wiring on load side of ground-fault circuit-inter-  The end of flexible-cord jackets and flexible-cord conduc-
             rupters  and  transformers.  For  other  than  grounding  con-  tor terminations within a luminaire shall be covered with, or
             ductors, conductors  installed  on  the  load  side  of  a  ground-  encapsulated in, a suitable potting compound to prevent the
             fault circuit-interrupter  or transformer used  to comply with  entry of water into the luminaire through the cord or its con-
             the  provisions  of  Section  E4206.4,  shall  not  occupy  race-  ductors. If present, the grounding connection within a lumi-
             ways,  boxes,  or  enclosures  containing  other  conductors  naire  shall  be  similarly  treated  to  protect  such  connection
             except where the other conductors are protected by ground-  from  the  deteriorating  effect  of  pool  water  in  the  event  of
             fault circuit-interrupters or are grounding conductors. Supply  water entry into the luminaire. [680.23(B)(4)]
             conductors to a feed-through type ground-fault circuit-inter-  Luminaires shall be bonded to and secured to the forming
             rupter shall be permitted in the same enclosure. Ground-fault  shell by a positive locking device that ensures a low-resis-
             circuit-interrupters  shall  be  permitted  in  a  panelboard  that  tance  contact  and  requires  a  tool  to  remove  the  luminaire
             contains circuits protected by other than ground-fault circuit-  from the forming shell. [680.23(B)(5)]
             interrupters. [680.23(F)(3)]
                                                                     E4206.5.1  Servicing.  All  wet-niche  luminaires  shall  be
             E4206.4 Underwater luminaires. The design of an under-  removable  from  the  water  for  inspection,  relamping,  or
             water luminaire supplied from a branch circuit either directly  other maintenance. The forming shell location and length
             or  by  way  of  a  transformer  or  power  supply  meeting  the  of cord in the forming shell shall permit personnel to place
             requirements of Section E4206.1, shall be such that, where  the removed luminaire on the deck or other dry location
             the fixture is properly installed without a ground-fault circuit-  for such maintenance. The luminaire maintenance location
             interrupter, there is no shock hazard with any likely combina-  shall be accessible without entering or going into the pool
             tion of fault conditions during normal use (not relamping). In  water. [680.23(B)(6)]
             addition,  ground-fault  circuit-interrupter  protection  for  per-
             sonnel shall be installed in the branch circuit supplying lumi-  E4206.6 Dry-niche luminaires. Dry-niche luminaires shall
             naires  operating  at  voltages  greater  than  the  low-voltage  have provisions for drainage of water. Other than listed low-
             contact  limit  to  protect  personnel  performing  lamping,  voltage luminaires not requiring grounding, a dry-niche lumi-
             relamping or servicing. The installation of the ground-fault  naire  shall  have  means  for  accommodating  one  equipment
             circuit-interrupter shall be such that there is no shock hazard  grounding conductor for each conduit entry. Junction boxes
             with any likely  fault-condition  combination  that  involves  a  shall not be required but, if used, shall not be required to be ele-
             person in a conductive path from any ungrounded part of the  vated or located as specified in Section E4206.9 if the lumi-
             branch circuit or the luminaire to ground. Compliance with  naire is specifically identified for the purpose. [680.23(C)(1)
             this  requirement  shall  be  obtained  by  the  use  of  a  listed  and (C)(2)]
             underwater luminaire and by installation of a listed ground-  E4206.7 No-niche luminaires. No-niche luminaires shall be
             fault circuit-interrupter in the branch circuit or a listed trans-  listed  for  the  purpose  and  shall  be  installed  in  accordance
             former or power supply for luminaires operating at more than  with the requirements of Section E4206.5. Where connection
             the low-voltage contact limit. Luminaires that depend on sub-  to a forming shell is specified, the connection shall be to the
             mersion  for  safe  operation  shall  be  inherently  protected  mounting bracket. [680.23(D)]
             against  the  hazards  of  overheating  when  not  submerged.  E4206.8 Through-wall lighting  assembly.  A through-wall
             [680.23(A)(1), (A)(3), (A)(7) and (A)(8)]
                                                                  lighting assembly shall be equipped with a threaded entry or
               E4206.4.1  Maximum  voltage.  Luminaires  shall  not  be  hub, or a nonmetallic hub, for the purpose of accommodating
               installed  for  operation  on  supply  circuits  over  150  volts  the termination of the supply conduit. A through-wall lighting
               between conductors. [680.23(A)(4)]                 assembly shall meet the construction requirements of Section
               E4206.4.2  Luminaire  location.  Luminaires  mounted  in  E4205.4 and be installed in accordance with the requirements
               walls shall be installed with the top of the fixture lens not  of Section E4206.5 Where connection to a forming shell is
               less  than  18  inches  (457  mm)  below  the  normal  water  specified, the connection shall be to the conduit termination
               level of the pool, except where the luminaire is listed and  point. [680.23(E)]
               identified for use at a depth of not less than 4 inches (102  E4206.9 Junction boxes and enclosures for transformers
               mm) below the normal water level of the pool. A lumi-  or  ground-fault  circuit-interrupters.  Junction  boxes  for
               naire  facing  upward  shall  have  the  lens  adequately  underwater  luminaires  and  enclosures  for  transformers  and
               guarded to prevent contact by any person or shall be listed  ground-fault circuit-interrupters that supply underwater lumi-
               for use without a guard. [680.23(A)(5) and (A)(6)]  naires shall comply with the following: [680.24(A)]
             E4206.5  Wet-niche  luminaires.  Forming  shells  shall  be  E4206.9.1 Junction boxes. A junction box connected to a
             installed for the mounting of all wet-niche underwater lumi-  conduit that extends directly to a forming shell or mount-
             naires  and  shall  be  equipped  with  provisions  for  conduit  ing bracket of a no-niche luminaire shall be:
             entries. Conduit shall extend from the forming shell to a suit-
             able junction box or other enclosure located as provided in  1. Listed  as  a  swimming  pool  junction  box;
             Section E4206.9. Metal parts of the luminaire and forming   [680.24(A)(1)]
             shell in contact with the pool water shall be of brass or other  2. Equipped with threaded entries or hubs or a nonme-
             approved corrosion-resistant metal. [680.23(B)(1)]          tallic hub; [680.24(A)(1)(1)]