Page 802 - 2018_IRC
P. 802
SWIMMING POOLS
E4209.6 Method of bonding. Metal parts required to be
bonded by this section shall be bonded together using a solid
copper bonding jumper, insulated, covered or bare, not
smaller than 8 AWG. The bonding jumper(s) shall be
required for equipotential bonding in the area of the hydro-
massage bathtub and shall not be required to be extended or
attached to any remote panelboard, service equipment, or
electrode. In all installations, a bonding jumper long enough
to terminate on a replacement nondouble-insulated pump or
blower motor shall be provided and shall be terminated to the
equipment grounding conductor of the branch circuit of the
motor where a double-insulated circulating pump or blower
motor is used. (680.74)
2018 INTERNATIONAL RESIDENTIAL CODE ® 777
Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.