             E4209.6  Method  of  bonding.  Metal  parts  required  to  be
             bonded by this section shall be bonded together using a solid
             copper  bonding  jumper,  insulated,  covered  or  bare,  not
             smaller  than  8  AWG.  The  bonding  jumper(s)  shall  be
             required for equipotential bonding in the area of the hydro-
             massage bathtub and shall not be required to be extended or
             attached  to  any  remote  panelboard,  service  equipment,  or
             electrode. In all installations, a bonding jumper long enough
             to terminate on a replacement nondouble-insulated pump or
             blower motor shall be provided and shall be terminated to the
             equipment grounding conductor of the branch circuit of the
             motor where a double-insulated circulating pump or blower
             motor is used. (680.74)