CLASS 2 REMOTE-CONTROL, SIGNALING AND POWER-LIMITED CIRCUITS



           E4303.2.2 Type CL2 cables. Cables for general-purpose     operate at 150 volts or less to ground and the Class 2
           use, shall be listed  as resistant to the spread  of fire and  circuits  are  installed  using  Types  CL3,  CL3R,  or
           listed for the use. [725.179 (C)]                         CL3P  or  permitted  substitute  cables,  and  provided
           E4303.2.3  Type  CL2X  cables.  Type  CL2X  limited-use   that these Class 3 cable conductors extending beyond
                                                                                                          1
           cable shall be listed as suitable for use in dwellings and  their jacket are separated by a minimum of  /  inch
                                                                                                           4
           raceways and shall be listed as resistant to flame spread.  (6.4 mm) or by a nonconductive sleeve or nonconduc-
           [725.179 (D)]                                             tive barrier from all other conductors. [725.136(D)]
           E4303.2.4 Type CL2R cables. Cables installed in a verti-  E4304.2 Other applications. Conductors of Class 2 circuits
           cal run in a shaft or installed from floor to floor shall be  shall be separated by not less than 2 inches (51 mm) from
           listed as suitable for use in a vertical run in a shaft or from  conductors of any electric light, power, Class 1 or nonpower-
           floor  to  floor  and  shall  be  listed  as  having  fire-resistant  limited fire alarm circuits except where one of the following
           characteristics capable of preventing fire from being con-  conditions is met:
           veyed from floor to floor. [725.179(B)]               1. All of the electric light, power, Class 1 and nonpower-
              Exception: CL2X and CL3X cables with a diameter of   limited fire alarm circuit conductors are in raceways or
                      1
              less  than  /  inch (6.4 mm) and  CL2P, CL3P,  CL3R,  in metal-sheathed, metal-clad, nonmetallic-sheathed or
                       4
              CL2 and CL3 cables shall be permitted in risers in one-  Type UF cables.
              and two-family dwelling units. [725.133 (G)]       2. All of the Class 2 circuit conductors are in raceways or
           E4303.2.5  Marking.  Cables  shall  be  marked  in  accor-  in metal-sheathed, metal-clad, nonmetallic-sheathed or
           dance with Table E4303.2.5. Voltage ratings shall not be  Type UF cables. [725.136(I)]
           marked on cables.                                  E4304.3  Class  2  circuits  with  communications  circuits.
                     Table E4303.2.5 [Table 725.179(J)]       Where  Class  2  circuit  conductors  are  in  the  same  cable  as
                           CABLE MARKING                      communications circuits, the Class 2 circuits shall be classi-
               CABLE MARKING                TYPE              fied as communications circuits and shall meet the require-
                                                              ments of Article 800 of NFPA 70. The cables shall be listed

          CL2P                        Class 2 plenum cable
                                                              as communications cables or multipurpose cables.
          CL2R                         Class 2 riser cable
                                                                 Cables constructed of individually listed Class 2 and com-
          CL2                            Class 2 cable        munications cables under a common jacket shall be permitted
          CL2X                       Class 2 cable, limited use  to be classified as communications cables. The fire-resistance
                                                              rating of the composite cable shall be determined by the per-
                                                              formance of the composite cable. [725.139 (D)(1)]
                          SECTION E4304                       E4304.4 Class 2 cables with other circuit cables. Jacketed
                  INSTALLATION REQUIREMENTS                   cables of Class 2 circuits shall be permitted in the same enclo-
         E4304.1 Separation from other conductors. In cables, com-  sure or raceway with jacketed cables of any of the following:
         partments, enclosures, outlet boxes, device boxes, and race-  1. Power-limited  fire  alarm  systems  in  compliance  with
         ways, conductors of Class 2 circuits shall not be placed in any  Article 760 of NFPA 70.
         cable, compartment, enclosure, outlet box, device box, race-
         way, or similar fitting with conductors of electric light, power,  2. Nonconductive and conductive optical fiber cables in
         Class 1 and nonpower-limited fire alarm circuits. (725.136)  compliance with Article 770 of NFPA 70.
           Exceptions:                                           3. Communications  circuits  in  compliance  with  Article
                                                                   800 of NFPA 70.
              1. Where  the  conductors  of  the  electric  light,  power,
                Class 1 and nonpower-limited fire alarm circuits are  4. Community  antenna  television  and  radio  distribution
                separated by a barrier from the Class 2 circuits. In  systems in compliance with Article 820 of NFPA 70.
                enclosures, Class 2 circuits shall be permitted to be  5. Low-power, network-powered broadband communica-
                installed in a raceway within the enclosure to sepa-  tions  in  compliance  with  Article  830  of  NFPA  70.
                rate  them  from  Class  1,  electric  light,  power  and  [725.139(E)]
                nonpower-limited fire alarm circuits. [725.136(B)]  E4304.5 Installation of conductors and cables. Cables and
              2. Class  2  conductors  in  compartments,  enclosures,  conductors installed exposed on the surface of ceilings and
                device boxes, outlet boxes and similar fittings where  sidewalls shall be supported by the building structure in such
                electric light, power, Class 1 or nonpower-limited fire  a manner that they will not be damaged by normal building
                alarm circuit conductors are introduced solely to con-  use. Such cables shall be supported by straps, staples, hangers,
                nect to the equipment connected to the Class 2 cir-  cable ties or similar fittings designed so as to not damage the
                cuits.  The  electric  light,  power,  Class  1  and  cable. Nonmetallic cable ties and other nonmetallic accesso-
                nonpower-limited fire alarm circuit conductors shall  ries used to secure and support cables located in stud cavity
                                             1
                be routed to maintain a minimum of  /  inch (6.4 mm)  and joist space plenums shall be listed as having low smoke
                                              4
                separation  from  the  conductors  and  cables  of  the  and heat release properties. The installation shall comply with
                Class 2 circuits; or the electric light power, Class 1  Table  E3802.1  regarding  cables  run  parallel  with  framing
                and nonpower-limited fire alarm circuit conductors  members  and  furring  strips.  The  installation  of  wires  and