Page 873 - 2018_IRC
P. 873

APPENDIX D



           (3) Spillage Test. Verify that all appliances located within  complete inspection. These inspections are performed either
               the same room are in their standby mode and ready  with the appliance in the off or standby mode (indicated by
               for  operation.  Follow  lighting  instructions  for  each  “OFF”)  or  on  an  appliance  that  is  operating  (indicated  by
               appliance as necessary. Test for spillage at the draft  “ON”). The CO measurements are to be undertaken only after
               hood relief opening as follows:                the appliance is determined to be properly venting. The CO
                                                              detector  should  be  capable  of  calculating  CO  emissions  in
                  a.  After  5  minutes  of  main  burner  operation,
                     check for spillage using smoke.          ppm air free.
                  b. Immediately  after  the  first  check,  turn  on  all  (1) Forced Air Furnaces:
                     other  fuel  gas  burning  appliances  within  the  a. OFF. Verify that an air  filter is installed  and
                     same  room  so  they  will  operate  at  their  full  that it is not excessively blocked with dust.
                     inputs and repeat the spillage test.              b. OFF.  Inspect  visible  portions  of  the  furnace
                  c. Shut down all appliances to their standby mode       combustion  chamber  for  cracks,  ruptures,
                     and wait for 15 minutes.                             holes, and corrosion. A heat exchanger leakage
                                                                          test should be conducted.
                  d. Repeat  the  spillage  test  steps  a  through  c  on
                     each appliance being inspected.                   c. ON. Verify both the limit control and the fan
                                                                          control  are  operating  properly.  Limit  control
           (4) Additional Spillage Tests: Determine if the appliance      operation can be checked by blocking the cir-
               venting is impacted by other door and air handler set-     culating air inlet or temporarily disconnecting
               tings by performing the following tests.
                                                                          the electrical supply to the blower motor and
                  a. Set  initial  test  condition  in  accordance  with  determining that the limit control acts to shut
                     D.5.2 (1).                                           off the main burner gas.
                  b. Place the appliance(s) being inspected in oper-   d. ON. Verify that the blower compartment door
                     ation. Adjust the thermostat or control so the       is  properly  installed  and  can  be  properly  re-
                     appliance(s) will operate continuously.              secured if opened. Verify that the blower com-
                  c. Open the door between the space in which the         partment door safety switch operates properly.
                     appliance(s) is located and the rest of the build-  e. ON.  Check  for  flame  disturbance  before  and
                     ing. After 5 minutes of main burner operation,       after blower comes on which can indicate heat
                     check  for  spillage  at  each  appliance  using     exchanger leaks.
                     smoke.                                            f.  ON. Measure the CO in the vent after 5 min-
                  d. Turn on any other central heating or cooling air     utes of main burner operation. The CO should
                     handler fan that is located outside of the area      not exceed threshold in Table D.6.
                     where the appliances are being inspected. After  (2) Boilers:
                     5 minutes of main burner operation, check for     a. OFF  and  ON.  Inspect  for  evidence  of  water
                     spillage  at  each  appliance  using  smoke.  The    leaks around boiler and connected piping.
                     test  should  be  conducted  with  the  door
                     between the space in which the appliance(s) is    b. ON. Verify that the water pumps are in operat-
                     located and the rest of the building in the open     ing  condition.  Test  low  water  cutoffs,  auto-
                     and in the closed position.                          matic feed controls, pressure and temperature
                                                                          limit controls, and relief valves in accordance
           (5) Return doors, windows, exhaust fans, fireplace damp-       with  the  manufacturer’s  recommendations  to
               ers, and any other fuel gas burning appliance to their     determine that they are in operating condition.
               previous conditions of use.
                                                                       c. ON. Measure the CO in the vent after 5 min-
           (6) If, after completing the spillage test it is believed suf-  utes of main burner operation. The CO should
               ficient  combustion  air  is  not  available,  the  owner  not exceed threshold in Table D.6.
               should be notified that an alternative combustion air  (3) Water Heaters:
               source is needed in accordance with Section G2407 of
               the International Fuel Gas Code. Where it is believed   a. OFF.  Verify  that  the  pressure-temperature
               that the venting system does not provide adequate nat-     relief valve is in operating condition. Water in
               ural draft, the owner should be notified that alterna-     the heater should be at operating temperature.
               tive vent sizing, design or configuration is needed in  b. OFF. Verify that inspection covers, glass, and
               accordance with Chapter 24 of the International Fuel       gaskets are intact and in place on a flammable
               Gas Code.  If  spillage  occurs,  the  owner  should  be   vapor  ignition  resistant  (FVIR)  type  water
               notified as to its cause, be instructed as to which posi-  heater.
               tion  of  the  door  (open  or  closed)  would  lessen  its  c. ON. Verify that the thermostat is set in accor-
               impact, and that corrective action by a HVAC profes-       dance  with  the  manufacturer’s  operating
               sional should be taken.
                                                                          instructions and measure the water temperature
         D.6  Appliance-Specific  Inspections.  The  following  appli-    at the closest tub or sink to verify that it is not
         ance-specific  inspections  are  to  be  performed  as  part  of  a  greater than 120ºF.


         848                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   868   869   870   871   872   873   874   875   876   877   878