Page 874 - 2018_IRC
P. 874

APPENDIX D



                     d. OFF.  Where  required  by  the  local  building    b. ON. Measure the CO in the firebox (log sets
                         code  in  earthquake  prone  locations,  inspect     installed in wood burning fireplaces or in the
                         that  the  water  heater  is  secured  to  the  wall  vent  (gas  fireplace)  after  5  minutes  of  main
                         studs  in  two  locations  (high  and  low)  using   burner  operation.  The  CO  should  not  exceed
                         appropriate metal strapping and bolts.               threshold in Table D.6.
                     e. ON. Measure the CO in the vent after 5 min-  (8) Gas Clothes Dryer
                         utes of main burner operation. The CO should      a. OFF. Where installed in a closet, verify that a
                         not exceed threshold in Table D.6.                   source of make-up air is provided and inspect
               (4) Cooking Appliances                                         that  any  make-up  air  openings,  louvers,  and
                                                                              ducts are free of blockage.
                     a. OFF.  Inspect  oven  cavity  and  range-top
                         exhaust vent for blockage with aluminum foil      b. OFF. Inspect for excess amounts of lint around
                         or other materials.                                  the  dryer  and  on  dryer  components.  Inspect
                                                                              that there is a lint trap properly installed and it
                     b. OFF. Inspect cook top to verify that it is free       does not have holes or tears. Verify that it is in
                         from a build-up of grease.                           a clean condition.
                     c. ON. Measure the CO above each burner and at        c.   OFF. Inspect visible  portions  of  the  exhaust
                         the  oven  exhaust  vents  after  5  minutes  of     duct  and  connections  for  loose  fittings  and
                         burner  operation.  The  CO  should  not  exceed     connections, blockage, and signs of corrosion.
                         threshold in Table D.6.                              Verify that the duct termination is not blocked
               (5) Vented Room Heaters                                        and  that  it  terminates  in  an  outdoor  location.
                                                                              Verify that only approved metal vent ducting
                     a. OFF.  For  built-in  room heaters  and  wall  fur-
                         naces, inspect that the burner compartment is        material is installed (plastic and vinyl materials
                         free of lint and debris.                             are not approved for gas dryers).
                                                                           d. ON. Verify mechanical components including
                     b. OFF. Inspect that furnishings and combustible         drum and blower are operating properly.
                         building  components  are  not  blocking  the
                         heater.                                           e. ON. Operate the clothes dryer and verify that
                                                                              exhaust system is intact and exhaust is exiting
                     a. ON. Measure the CO in the vent after 5 min-           the termination.
                         utes of main burner operation. The CO should
                         not exceed threshold in Table D.6.                f. ON. Measure the CO at the exhaust duct or ter-
                                                                              mination after 5 minutes of main burner opera-
               (6) Vent-Free (unvented) Heaters                               tion.  The  CO  should  not  exceed  threshold  in
                     a. OFF. Verify that the heater input is not more         Table D.6.
                         than  40,000  Btu  input,  but  not  more  than               TABLE D.6
                         10,000 Btu where installed in a bedroom, and               CO THRESHOLDS
                         6,000 Btu where installed in a bathroom.  Boilers (all categories)  400 ppm air free
                     b. OFF.  Inspect  the  ceramic  logs  provided  with  Central Furnace (all categories)  400 ppm  air free 2, 3
                                                                                                  1
                         gas  log  type  vent  free  heaters  that  they  are  Floor Furnace  400 ppm air free
                         properly located and aligned.
                                                                   Gravity Furnace         400 ppm air free
                     c. OFF. Inspect the heater that it is free of excess
                         lint build-up and debris.                 Wall Furnace (BIV)      200 ppm air free
                                                                   Wall Furnace (Direct Vent)  400 ppm air free
                     c. OFF. Verify that the oxygen depletion safety
                         shutoff  system  has  not  been  altered  or  Vented Room Heater  200 ppm air free
                         bypassed.                                 Vent-Free Room Heater   200 ppm air free
                     d. ON.  Verify  that  the  main  burner  shuts  down  Water Heater    200 ppm air free
                         within  3  minutes  by  extinguishing  the  pilot  Oven/Broiler   225 ppm as measured
                         light. The test is meant to simulate the opera-  Top Burner       25 ppm as measured (per burner)
                         tion of the oxygen depletion system (ODS).
                                                                   Clothes Dryer           400 ppm air free
                     e. ON. Measure the CO after 5 minutes of main
                         burner  operation.  The  CO  should  not  exceed  Refrigerator    25 ppm as measured
                         threshold in Table D.6.                   Gas Log (gas fireplace)  25 ppm as measured in vent
               (7) Gas Log Sets and Gas Fireplaces                 Gas Log (installed in wood  400 ppm air free in firebox
                                                                    burning fireplace)
                     a. OFF.  For  gas  logs  installed  in  wood  burning
                         fireplaces equipped with a damper, verify that  1. Parts per million
                         the  fireplace  damper  is  in  a fixed open  posi-  2. Air free emission levels are based on a mathematical equation (involving
                                                                    carbon monoxide and oxygen or carbon dioxide readings) to convert an
                         tion.                                      actual diluted flue gas carbon monoxide testing sample to an undiluted air


             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               849
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   869   870   871   872   873   874   875   876   877   878   879