APPENDIX H


                                                                                  1
         AH106.3 Screen enclosures.  Screen enclosures shall com-  R506, be not less than 3 /  inches (89 mm) thick and the col-
                                                                                   2
         ply with Sections AH106.3.1 and AH106.3.2.           umns shall not support loads in excess of 750 pounds (3.36
           AH106.3.1 Thickness. Actual wall thickness of extruded  kN) per column.
           aluminum members shall be not less than 0.040 inch (1.02
           mm).
           AH106.3.2 Density. Screen density shall be not more than
                                                                                TABLE AH106.4(2)
           20 threads per inch by 20 threads per inch mesh.                 ADJUSTMENT FACTOR FOR
         AH106.4 Design.   The structural design of screen enclosures    BUILDING HEIGHT AND EXPOSURE
         shall comply with Sections AH106.4.1 through AH106.4.3.  MEAN ROOF              EXPOSURE
                                                                  HEIGHT
           AH106.4.1  Wind  load.  Structural  members  supporting  (feet)      B            C           D
           screen enclosures shall be designed to support the mini-  15        1.00         1.21        1.47
           mum  wind  loads  given  in  Tables  AH106.4(1)  and
           AH106.4(2) for the ultimate design wind speed, V , deter-  20       1.00         1.29        1.55
                                                   ult
           mined from Figure  AH106.4.1. Where  any value is less   25         1.00         1.35        1.61
           than 10 pounds per square foot (psf) (0.479 kN/m ) use 10  30       1.00         1.40        1.66
                                                   2
                                        2
           pounds per square foot (0.479 kN/m ).                    35         1.05         1.45        1.70
           AH106.4.2  Deflection  limit.  For  members  supporting  40         1.09         1.49        1.74
           screen  surfaces  only,  the  total  load  deflection  shall  not
           exceed l/60. Screen surfaces shall be permitted to include  45      1.12         1.53        1.78
           not more than 25-percent solid flexible finishes.        50         1.16         1.56        1.81
           AH106.4.3 Roof live load. The roof live load shall be not  55       1.19         1.59        1.84
                                   2
           less than 10 psf (0.479 kN/m ).                          60         1.22         1.62        1.87
         AH106.5 Footings. In areas with a frost line depth of zero,  For SI: 1 foot = 304.8 mm.
         screen  enclosures  supported  on  a  concrete  slab-on-grade
         without footings shall conform to the provisions of Section



                                                     TABLE AH106.4(1)
                                DESIGN WIND PRESSURES FOR SCREEN ENCLOSURE FRAMING a, b, e, f, g, h
                                                                       ULTIMATE DESIGN WIND SPEED, V ult
                                                                                 (mph)
           LOAD                   WALL
           CASE                                         100   105   110  120   130   140  150   160   170  180
                                                                    Exposure Category B Design Pressure (psf)
            A c     Windward and leeward walls (flow thru) and   6  7  8  9    11    13    14   16    18    21
                     windward wall (nonflow thru) L/W = 0-1
            A c     Windward and leeward walls (flow thru) and   7  8  9  1  1  1  2  1  4  1  6  1  9  2  1  2  4
                      windward wall (nonflow thru) L/W = 2
            B d           W  i  n  d  w  a  r  d  :     N  o  n  g  a  b  l  e     r  o  o  f  9  1  0  1  1  1  3  1  5  1  8  2  1  2  3  2  6  3  0
            B d             Windward: Gable roof        11    13    14   16    19    22    26   29    33    37
                                  ROOF
            All e               R  o  o  f  -  s  c  r  e  e  n  2  3  3  3     4    4     5     6    7     7
            All e               R  o  o  f  -  s  o  l  i  d  7  8  8     1  0  1  2  1  3  1  5  1  8  2  0  2  2
         For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.44 m/s, 1 pound per square foot = 0.0479 kPa, 1 foot = 304.8 mm.
         a. Design pressure shall be not less than 10 psf in accordance with Section AH106.4.1.
         b. Loads are applicable to screen enclosures with a mean roof height of 30 feet or less in Exposure B. For screen enclosures of different heights or exposure, the
           pressures given shall be adjusted by multiplying the table pressure by the adjustment factor given in Table AH106.4(2).
         c. For Load Case A flow thru condition, the pressure given shall be applied simultaneously to both the upwind and downwind screen walls acting in the same
           direction as the wind. The structure shall be analyzed for wind coming from the opposite direction. For the nonflow thru condition, the screen enclosure wall
           shall be analyzed for the load applied acting toward the interior of the enclosure.
         d. For Load Case B, the table pressure multiplied by the projected frontal area of the screen enclosure is the total drag force, including drag on screen surfaces
           parallel to the wind, that must be transmitted to the ground. Use Load Case A for members directly supporting the screen surface perpendicular to the wind.
           Load Case B loads shall be applied only to structural members that carry wind loads from more than one surface.
         e. The roof structure shall be analyzed for the pressure given occurring both upward and downward.
         f. Table pressures are MWFRS loads. The design of solid roof panels and their attachments shall be based on component and cladding loads for enclosed or
           partially enclosed structures as appropriate.
         g. Table pressures apply to 20-inch by 20-inch by 0.013-inch mesh screen. For 18-inch by 14-inch by 0.013-inch mesh screen, pressures on screen surfaces shall
           be permitted to be multiplied by 0.88. For screen densities greater than 20 inches by 20 inches by 0.013 inch, pressures for enclosed buildings shall be used.
         h. Linear interpolation shall be permitted.