P. 962

APPENDIX S



             AS106.10 Support of plaster skins. Plaster skins on straw-  2. Assembly shall be the width of the strawbale wall
             bale  structural  walls  shall  be  continuously  supported along  and shall comply with Section AS106.11.
             their bottom edge. Acceptable supports include: a concrete or  3. Discontinuous lumber shall be spliced with a metal
             masonry stem wall, a concrete slab-on-grade, a wood-framed  strap with not less than a 500-pound (2224 N) allow-
             floor in accordance with Figure AS105.1(2) and an approved  able wind or seismic load tension capacity. Where
             engineered design or a steel angle anchored with an approved  the wall line includes a braced wall panel the strap
             engineered  design.  A  weep  screed  as  described  in  Section  shall  have  not  less  than  a  2,000-pound  (8896  N)
             R702.7.2.1 is not an acceptable support.                    capacity.
             AS106.11  Transfer  of  loads  to  and  from  plaster  skins.  4. Panel joints shall be blocked.
             Where plastered strawbale walls are used to support superim-
             posed  vertical  loads,  such  loads  shall  be  transferred  to  the  5. Roof  and  ceiling  framing  shall  be  attached  to  the
             plaster skins by continuous direct bearing in accordance with  roof-bearing  assembly  in  accordance  with  Table
             Figure  AS105.1(3)  or  by  an  approved  engineered  design.  R602.3(1), Items 2 and 6.
             Where plastered strawbale walls are used to resist in-plane  6. Where the roof-bearing assembly spans wall open-
             lateral loads, such loads shall be transferred to the reinforcing  ings, it shall comply with Section AS106.12.3.1
             mesh from the structural member or assembly above in accor-  AS106.12.3.1  Roof-bearing  assembly  spanning
             dance with Figure AS105.1(3) or AS105.1(4) and to the sill  openings. Roof-bearing assemblies that span openings
             plate  in  accordance with  Figure AS105.1(1) or  AS105.1(2)  in strawbale walls shall comply with the following at
             and with Table AS106.13(1).
                                                                       each opening:
             AS106.12 Load-bearing walls. Bearing capacities for plas-   1. Lumber on each side of the assembly shall be of
             tered strawbale walls used as load-bearing walls in one-story  the  dimensions  and  quantity  required  to  span
             buildings to support vertical loads imposed in accordance with  each  opening  in  accordance  with  Table
             Section R301 shall be in accordance with Table AS106.12.
                                                                            R602.7(1).
               AS106.12.1 Precompression of load-bearing strawbale       2. The required lumber in the assembly shall be sup-
               walls. Prior to application of plaster, walls designed to be  ported at each side of the opening by the number
               load-bearing shall be precompressed by a uniform load of     of  jack  studs  required  by  Table  R602.7(1),  or
               not less than 100 plf (1459 N/m).
                                                                            shall  shall  extend  beyond  the  opening  on  both
               AS106.12.2  Concentrated  loads.  Concentrated  loads        sides a distance, D, using the following formula:
               shall be distributed by structural elements capable of dis-  D = S  R/2 / (1-R)      (Equation AS-1)
               tributing the loads to the bearing wall within the allowable
               bearing capacity listed in Table AS106.12 for the plaster    where:
               type used.                                                   D = Minimum  distance  (in  feet)  for  required
                                                                                 spanning  lumber  to  extend  beyond  the
               AS106.12.3  Roof-bearing  assembly.  Roof-bearing
               assemblies shall be of nominal 2-inch by 6-inch (51 mm            opening
               by 152 mm) lumber with  / -inch (12 mm) plywood or           S = Span in feet
                                     15
                                       32
               OSB panels fastened with 8d nails at 6 inches (152 mm)       R = B / B
                                                                                  L
                                                                                     C
               on center in accordance with Figure AS105.1(3) and Items     B = Design  load  on  the  wall  (in  pounds  per
               1 through 6, or be of an approved engineered design.          L   lineal  foot)  in  accordance  with  Sections
                  1. Assembly shall be a box assembly on the top course          R301.4 and R301.6
                    of bales, with the panels horizontal.                   B = Allowable bearing capacity of the wall in
                                                                             C
                                                                                 accordance with Table AS106.12
                                                          TABLE AS106.12
                   ALLOWABLE SUPERIMPOSED VERTICAL LOADS (LBS/FOOT) FOR PLASTERED LOAD-BEARING STRAWBALE WALLS
                                        PLASTER a                                                    ALLOWABLE
                WALL DESIGNATION     (both sides) Minimum     MESH b             STAPLES c        BEARING CAPACITY d
                                  thickness in inches each side                                         (plf)
                       A                 C  l  a  y     1  1 / 2  None required  None required          400
                       B               Soil-cement 1         Required            Required               800
                       C                 L  i  m  e     7 / 8  Required          Required               500
                                                7
                       D              Cement-lime  / 8       Required            Required               800
                       E                Cement  / 8          Required            Required               800
                                              7
             For SI: 1 inch = 25.4mm, 1 pound per foot = 14.5939 N/m.
             a. Plasters shall conform to Sections AS104.4.3 through AS104.4.8, AS106.7 and AS106.10.
             b. Any metal mesh allowed by this appendix and installed in accordance with Section AS106.9.
             c. In accordance with Section AS106.9.2, except as required to transfer roof loads to the plaster skins in accordance with Section AS106.11.
             d. For walls with a different plaster on each side, the lower value shall be used.


             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               937
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.