FIXTURES, FAUCETS AND FIXTURE FITTINGS



             403.4 Signage. Required public facilities shall be  provided  in depth for floor-mounted water closets and not less than
             with signs that designate the sex, as required  by Section  30 inches (762 mm) in width and 56 inches (1422 mm) in
             403.2. Signs shall be readily visible and  located near the  depth for wall-hung water closets.
             entrance to each toilet facility. Signs  for accessible toilet  Exception: An accessible children’s water closet shall
             facilities shall comply with Section 1111 of the International  be set not closer than 12 inches (305 mm) from its cen-
             Building Code.                                            ter to the required partition or to the wall on one side.
               403.4.1 Directional signage. Directional signage indicat-  405.3.2 Public lavatories. In employee and public toilet
               ing the route to the required public toilet facilities shall be  rooms, the required lavatory shall be located in the same
               posted in a lobby, corridor, aisle or similar space, such that  room as the required water closet.
               the sign can be readily seen from the main entrance to the  405.3.3 Location of fixtures and piping. Piping, fixtures
               building or tenant space.
                                                                     or equipment shall not be located in such a manner as to
             403.5 Drinking fountain location. Drinking fountains shall  interfere with the normal operation of windows, doors or
             not be required to be located in individual tenant spaces pro-  other means of egress openings.
             vided that public drinking fountains are located within a dis-  405.3.4 Water  closet compartment.  Each water closet
             tance  of travel of  500 feet (152  m) of the most remote
             location in  the tenant  space and  not more than one story  utilized by the public or employees shall occupy a separate
                                                                     compartment with walls or partitions and a door enclosing
             above or below the tenant space. Where the tenant space is in  the fixtures to ensure privacy.
             a covered or open mall, such distance shall not exceed 300
             feet (91 m). Drinking fountains shall be located on an accessi-  Exceptions:
             ble route.                                                  1. Water closet compartments shall not be required
                                                                            in a single-occupant toilet room with a lockable
                                                                            door.
                               SECTION 404                               2. Toilet rooms located in child day care facilities
                    ACCESSIBLE PLUMBING FACILITIES
                                                                            and containing two or more water closets shall be
             404.1 Where required. Accessible plumbing facilities and       permitted to have one  water closet  without  an
             fixtures shall be provided in  accordance  with  the Interna-  enclosing compartment.
             tional Building Code.
                                                                         3. This provision is not  applicable to  toilet areas
             404.2 Accessible fixture requirements. Accessible plumb-       located within Group I-3 housing areas.
             ing  fixtures shall be installed with  the  clearances, heights,  405.3.5 Urinal partitions. Each urinal utilized by the pub-
             spacings and arrangements in accordance with ICC A117.1.
                                                                     lic or employees shall occupy a separate area with walls or
             404.3 Exposed pipes and surfaces. Water supply and drain  partitions to provide privacy.  The horizontal  dimension
             pipes under accessible lavatories and sinks shall be covered  between walls or partitions at each urinal shall be not less
             or otherwise configured to protect against contact. Pipe cov-  than 30 inches (762 mm). The walls or partitions shall
             erings shall comply with ASME A112.18.9.                begin at a height not greater than 12 inches (305 mm) from
                                                                     and extend not less than 60 inches (1524 mm) above the
                                                                     finished floor surface. The walls or partitions shall extend
                               SECTION 405                           from the wall surface at each side of the urinal not less
                       INSTALLATION OF FIXTURES                      than 18 inches (457 mm) or to a  point  not less  than 6
             405.1 Water supply  protection. The supply  lines and  fit-  inches (152 mm) beyond the outermost front lip of the uri-
             tings for every plumbing fixture shall be installed so as to  nal measured from the finished backwall surface, which-
             prevent backflow.                                       ever is greater.
             405.2 Access for cleaning.  Plumbing fixtures shall be    Exceptions:
             installed so as to afford easy access for cleaning both the fix-  1. Urinal partitions shall not be required in a single-
             ture and the area around the fixture.                          occupant or family/assisted-use toilet room with
             405.3 Setting. Fixtures shall be set level and in proper align-  a lockable door.
             ment with reference to adjacent walls.                      2. Toilet rooms located in child day care facilities
               405.3.1 Water closets, urinals, lavatories and bidets. A     and containing two or more urinals shall be per-
               water closet, urinal, lavatory or bidet shall not be set closer  mitted to have one urinal without partitions.
               than 15 inches (381 mm) from its center to any side wall,  405.4 Floor  and wall drainage connections.  Connections
               partition, vanity or other obstruction. Where partitions or
                                                                  between the drain and floor outlet plumbing fixtures shall be
               other obstructions do not  separate  adjacent fixtures, fix-  made with  a floor flange  or  a waste connector  and sealing
               tures shall not be set closer than 30 inches (762 mm) cen-  gasket. The waste connector and sealing gasket joint shall
               ter to center between adjacent fixtures. There shall be not
                                                                  comply with the joint tightness test of ASME A112.4.3 and
               less than a 21-inch (533 mm) clearance in front of a water  shall be installed  in  accordance  with the manufacturer’s
               closet, urinal, lavatory or bidet to any wall, fixture or door.  instructions. The flange shall be attached to the drain and
               Water closet compartments shall be not less than 30 inches
                                                                  anchored to the structure. Connections between the drain and
               (762 mm) in width and not less than 60 inches (1524 mm)