Objectives                                           The BMS engineer also further shared that suction pressure
            The  primary  objective  is  to  develop  a  solution  to  reduce  should not fall below 90 psi for R32 air conditioning for more
            greenhouse gas emissions for air conditioning products and  than  10  minutes.  This  indicates  a  low  refrigerant  pressure
            their  servicing  process.  The  primary  carbon  emissions  are  condition  for  the  air  conditioning  system  and  requires  the
            the refrigerant used in their products, recharging refrigerant  technician to check the air conditioning system immediately.
            during maintenance and fugitive emission leakages from their  Prolonged operation under low suction pressure is adverse to
            products. The secondary objective is to develop a solution to  the air conditioning system.
            minimise the fire risk of the R32 air conditioning system.
                                                                 Chart 1.4 (below) shows the relationship between insufficient
                                                                 charge and efficiency and cooling capacity.












               Fig 1.2. The Daikin engineering team shares with ITE students


            BMS and Daikin shared their products and service procedure
            with us (See Figure 1.2). They have stopped selling and installing
            the  R410A  air  conditioning  system  due  to  regulations  that   Chart 1.4. Insufficient refrigerant charge chart
            reduce the high GWP (Global Warming Potential). Currently,   Source: https://www.daikin.com.sg/product-series/vrv-x/
            they are focusing on distributing the new R32 air conditioning
            system.  However,  they  also  highlighted  that  R32  is  an  A2L
            flammable gas (See Figure 1.3). It has fire risk potential should  BMS  shared  that  if  the  air  conditioning  is  not  cold  during
            there be a leakage in the system. They are also in discussion  servicing,  the  technician  will  check  the  refrigerant  charge
            with SCDF to enhance the safety process in handling R32 air  level. If the refrigerant, after being recharged, drops gradually
            conditioning.                                        within 1 1-week period, there is leakage in the air conditioning
                                                                 system.  Frequent  recharge  of  the  leaking  air  conditioning
                                                                 system  will  not  solve  the  problem.  Identifying  the  issue  of
                                                                 the  leakages  and  rectifying  it  early  will  be  a  more  feasible
                                                                 solution. Leakages can come from several sources, as shown
                                                                 in Figure 1.5.





                 Fig 1.3. Advisory label on R32's Daikin Air conditioning