P7295D
SOLID OR STRANDED BARE COPPER
TYPE UF/ NMC-B
PVC JACKET
INSULATION: PVC
JACKET: PVC PVC INSULATION
SIZES: 14 - 6 AWG, 2 0R 3 CONDUCTOR ®
WITH OR WITHOUT GROUND, 600 VOLTS,
60°C WET OR DRY
1.0 SCOPE: 2.4 Ground Wire:
1.1 This specification covers 2 or 3 conductor For 2 or 3 conductor cable with ground.
cables, with or without a ground wire, having Solid, annealed bare copper per ASTM
polyvinyl chloride (PVC) insulation and a B-3. Sizes as follows:
sunlight-resistant PVC overall jacket, and single
conductor cables having a sunlight-resistant PVC GROUND WIRE
insulation. INSULATED
CONDUCTORS SIZE NDM. O. D.
1.2 Use: SIZE (AWG) (AWG) (AWG)
UL Listed and OSHA acceptable. In accordance 14 14 .0641
with Articles 336 and 339 of the Nat’l Electrical
Code (and subject to local code requirements), 12 12 .0808
Type UF cables may be used for underground 10 10 .1019
feeder or branch-circuit wiring for installation 8 10 .1019
above or below ground, including direct burial,
and in wet or corrosive locations. Multiconductor 6 10 .1019
Type UF (Type NMC-B) cables may also be used
for exposed or concealed interior wiring in wet, 2.5 Cable Assembly:
dry or corrosive locations and in cable trays. Multiconductor cables are assembled flat
parallel. For cables with ground, the
1.3 MAXIMUM CONDUCTOR TEMP. ground wire is placed between two of the
AND VOLTAGE RATING: insulated conductors.
TYPE WET DRY VOLTAGE
2.6 Overall Jacket: (integral jacket and
UF 60°C 60°C 600V insulation for single conductor cable)
*NMC-B 60°C 60°C 600V Sunlight, moisture and
*14-10AWG only fungus-resistant. Gray PVC.
UL-493 and UL-719
2.0 CONSTRUCTION:
2.1 Conductors: (for Multiconductor cables 2.7 Color Code:
only): Two-conductor cable: Black, White
Sizes 14,12 & 10AWG: Three-conductor cable: Black, White, Red
Solid,annealed bare copper per ASTM
B-3,UL-493, and UL-719 2.8 Markings:
Sizes 8 & 6AWG: Single Conductor Cable: Ink print on
Concentric, compressed stranded (class B) jacket “(size) AWG Type UF 600 Volts
Sunlight Resistant (UL)”
2.2 Conductors: (for Single Conductor cable only) Multiconductor Cable with Ground: Ink
Sizes 14-8AWG: Solid,annealed bare copper print on jacket “(size) AWG/(# of conds.)
ASTM B-3 and UL-493 W.G.Type UF 600V
Sizes 6-4/0AWG: Concentric compressed Sunlight Resistant(UL)”
stranded (class B)ASTM B-3 and UL-493 Multiconductor Cable w/o ground: Ink
print on jacket “ (size) AWG/(#of conds.)
2.3 Insulation:
For Multiconductor cable only: Polyvinyl chloride
(PVC). UL-493 and UL-719