                                                                            P7295D



                                                                           SOLID OR STRANDED BARE COPPER
                   TYPE UF/ NMC-B
                                                      PVC JACKET
                   INSULATION: PVC

                   JACKET: PVC                                                         PVC INSULATION

                   SIZES:  14 - 6 AWG, 2 0R 3 CONDUCTOR                                                       ®

                   WITH OR WITHOUT  GROUND, 600 VOLTS,
                   60°C WET OR DRY


                    1.0   SCOPE:                                           2.4    Ground Wire:
                          1.1    This specification covers 2 or 3 conductor       For 2 or 3 conductor cable with ground.
                                 cables, with or without a ground wire, having    Solid, annealed bare copper per ASTM
                                 polyvinyl chloride (PVC) insulation and a        B-3. Sizes as follows:
                                 sunlight-resistant PVC overall jacket, and single
                                 conductor cables having a sunlight-resistant PVC                    GROUND WIRE
                                 insulation.                                         INSULATED
                                                                                    CONDUCTORS    SIZE    NDM. O. D.
                          1.2    Use:                                                SIZE (AWG)   (AWG)     (AWG)
                                 UL Listed and OSHA acceptable.  In accordance         14          14       .0641
                                 with Articles 336 and 339 of the Nat’l Electrical
                                 Code (and subject to local code requirements),        12          12       .0808
                                 Type UF cables may be used for underground            10          10       .1019
                                 feeder or branch-circuit wiring for installation       8          10       .1019
                                 above or below ground, including direct burial,
                                 and in wet or corrosive locations. Multiconductor      6          10       .1019
                                 Type UF (Type NMC-B) cables may also be used
                                 for exposed or concealed interior wiring in wet,  2.5  Cable Assembly:
                                 dry or corrosive locations and in cable trays.   Multiconductor cables are assembled flat
                                                                                  parallel. For cables with ground, the
                          1.3         MAXIMUM CONDUCTOR TEMP.                     ground wire is placed between two of the
                                        AND VOLTAGE RATING:                       insulated conductors.
                                   TYPE   WET    DRY  VOLTAGE
                                                                           2.6    Overall Jacket:  (integral jacket and
                                    UF   60°C   60°C   600V                       insulation for single conductor cable)
                                  *NMC-B  60°C  60°C   600V                       Sunlight, moisture and
                                  *14-10AWG only                                  fungus-resistant.  Gray PVC.
                                                                                  UL-493 and UL-719
                   2.0    CONSTRUCTION:
                          2.1    Conductors: (for Multiconductor cables    2.7    Color Code:
                                 only):                                           Two-conductor cable: Black, White
                                 Sizes 14,12 & 10AWG:                             Three-conductor cable: Black, White, Red
                                 Solid,annealed bare copper per ASTM
                                 B-3,UL-493, and UL-719                    2.8    Markings:
                                 Sizes 8 & 6AWG:                                  Single Conductor Cable: Ink print on
                                 Concentric, compressed stranded (class B)        jacket “(size) AWG Type UF 600 Volts
                                                                                  Sunlight Resistant (UL)”
                          2.2    Conductors: (for Single Conductor cable only)    Multiconductor Cable with Ground: Ink
                                 Sizes 14-8AWG: Solid,annealed bare copper        print on jacket “(size) AWG/(# of conds.)
                                 ASTM B-3 and UL-493                              W.G.Type UF 600V
                                 Sizes 6-4/0AWG: Concentric compressed            Sunlight Resistant(UL)”
                                 stranded (class B)ASTM B-3 and UL-493            Multiconductor Cable w/o ground: Ink
                                                                                  print on jacket “ (size) AWG/(#of conds.)
                          2.3    Insulation:
                                 For Multiconductor cable only: Polyvinyl chloride
                                 (PVC). UL-493 and UL-719
   45   46   47   48   49   50   51   52   53   54   55