gas leaks dispersed in housings (HSE
                 report RR630). The HSL work used   FIGURE 3: Example of outdoor 16bar installation with moderate distance between 16bar
                 the concept contained within     PRS section and 2bar metering section allowing an area where NE is possible
                 BS EN 60079-10-1 that small gas
                 releases (even continuous) can give
                 rise to zones of ‘negligible extent’
                 (designated by the appropriate zone
                 number followed by NE; e.g., zone 2
                 NE), which do not result in a need for
                 any special precautions regarding
                 allowable equipment. This concept did
                 not exist in IGE/SR/25 Edition 1. Any
                 potential release gave rise to a zoned
                 area, resulting in zones even around
                 low pressure pipework in the open air.
                   Thus, in some cases, hazardous area
                 zones as determined by SR/25 Edition
                 2 will be less onerous and have a
                 smaller extent than if determined by
                 earlier versions. To keep in step with
                 IGEM/SR/25, Edition 2 of IGEM/
                 GM/7B now also includes the
                 modified calculation method which, in
                 some cases, includes the negligible
                 extent concept.
                 So what is NE? It is the special case
                 where a number of requirements are
                 met resulting in the distance ‘X’ to be
                 so small that it effectively zero.

                 To achieve a classification of NE the
                 following conditions have to be present:
                 •  MOP (meter operating pressures)
                  not to exceed 10bar
                 •  Potential leak source not confined   electricity meter/electrical apparatus,   an additional zone 2 area near the
                  and not congested (which also   and not less than 25mm away from a   ceiling, but this is no longer required.
                  means the installation housing will   240V electricity supply and distribution  Also, in some situations (typically low
                  have a volume greater than 10m3)  cables. If this is not possible, a non-  pressures and/or moderate distances
                 •  Ventilation “more than adequate”  combustible partition made of an   between the installation and the
                 •  Maintenance procedures in place to   electrically insulating material needs to   walls) there is no longer a hazardous
                  ensure no change in ventilation  be placed between them.         area at the outlet of ventilation grills
                   A hazardous area zone classified as   A zone of negligible extent is not   in the walls. However, hazardous areas
                 NE requires no action to control   the same as a safe area. In particular, it  at the outlets can now be slightly
                 sources of ignition within it. Thus,   may be that a zone of negligible   more onerous in other circumstances
                 items of electrical equipment that are   extent becomes more onerous if   (typically if the interior is not zone 2/
                 not necessary certificated for use in a   ventilation is reduced during   non-hazardous).
                 hazardous area, may be installed in   modifications to buildings and   In installations that have
                 areas designated NE. This could be   housings. If this occurs and ventilation   unconfined and uncongested areas,
                 particularly useful because it means   cannot be improved, the NE status   having high levels of ventilation and
                 that non-certificated, electrically   has to be revoked.          with gas pressures up to 10bar, it
                 operated, gas safety shut-off valves   Hazardous area zones in and   may be possible to assign a zone 2
                 may be used to isolate the gas supply   around meter houses are now   NE designation.
                 in the case of emergency. In addition,   treated slightly differently.  As with previous editions, lower
                 uncertificated motors and lighting                                levels of ventilation are likely to result
                 may also be installed.           SUMMARY                          in the entire housing being classified
                   However, in the specific case of gas   As with previous editions, well   as zone 1, or so low that more
                 meters the following is still required:   ventilated housings that are only   ventilation would be required (to
                 the gas meter, and any equipment   slightly larger than the meter   avoid zone 0). This is still determined
                 electrically connected to it, needs to be  installation will be zone 2 throughout.  by the use of the coloured charts. ■
                 suitable for use in a zone 2 area or to   New to the latest edition is the
                 be suitable for use in the zone in which   situation where the housing is large   ■ Buy these standards and more by
                 it is to be used, whichever is the more   enough that a significant distance is   visiting shop.igem.org.uk. Want to
                 onerous requirement. A gas meter and   present between the installation’s   access our technical standards online?
                 its associated fittings needs to be fitted  zone and the walls or ceiling. The   Email technical@igem.org.uk to find
                 not less than 150mm from a 240V   previous edition would have indicated   out more about our flexible access.