Operable Partitions
                                        10 22 26 (10650)  MODEL 3020 WT PART 1 - GENERAL SPECIFICATIONS


        1.01 WORK INCLUDED                                       F. ASTM C 423: Standard Test Method for Sound Absorption and
        A. Operable Wall System shall be furnished, installed and serviced by         Sound Absorption Coeffi cients by the Reverberation
             KWIK-WALL’s authorized distributor, in compliance with the         Room Method.
             architectural drawings and specifi cations contained herein.  G. CCC-W-408A: Federal Specifi cation which applies to Vinyl
                                                                      Coated Wall Coverings.
        1.02 RELATED WORK                                        H. CFFA-W-101-D: Chemical Fabrics and Film Association
        A. Structural Support: Structural support system required for        Quality Standard for Vinyl Coated Fabric Wall Coverings.
             suspending the operable wall shall be designed, installed and
             pre-punched by others, in accordance with ASTM E 557 and  1.06 SUBMITTALS
             KWIK-WALL’s shop drawings.                          A. KWIK-WALL shall provide written technical information and
        B. Insulation: Sound insulation and baffl es for the plenum area above              related detail drawings, which demonstrate that the products
             the track system, under the permanent fl oor, inside air ducts        comply with contract documents for each type of operable
             passing over or around the operable wall, and in permanent walls        partition specifi ed.
             adjoining the operable wall system shall be by others, in   B. KWIK-WALL shall provide detailed engineering drawings
             accordance with ASTM E 557.                              featuring track plan, panel elevation, horizontal and vertical
        C. Opening Preparation: Proper and complete preparation of the       details and beam punching template as required.
             operable wall system opening shall be by others in accordance   C. KWIK-WALL shall provide written test report of the
             with ASTM E 557, and shall include fl oor leveling; plumbness        independent acoustical testing laboratory certifying the
             of adjoining permanent walls; substrate and / or ceiling tile        attainment of the specifi ed STC rating, upon request.
             enclosures for the track system; and the painting and fi nishing
             of trim and other materials adjoining the head and jamb areas   D. KWIK-WALL shall provide written instructions specifying the
             of the operable wall. Any permanent wall(s) receiving an        proper operation and maintenance of the operable wall system.
             adjustable or fi xed wall jamb will require internal structural  E. KWIK-WALL shall provide a color selector demonstrating the
             blocking in order to secure the jamb to the permanent wall.       KWIK-WALL’s selections of the specifi ed fi nish material. Samples
             Refer to a copy of the shop drawings for additional details.       shall consist of actual swatches of the specifi ed fi nish material.

        1.03 SYSTEM DESCRIPTION                                  1.07 DELIVERY, STORAGE AND HANDLING
        A. The operable wall system shall consist of Individual Panels that   A. Panels shall be individually wrapped in a protective plastic
             are top supported by two (2) multi-directional carriers that are        covering to keep panels clean during delivery, storage
             capable of negotiating 90  “X”, “L” and “T” intersections.        and handling.
                              o
        B. The operable wall system shall consist of acoustically rated   B. Panels shall be stored on edge and above the fl oor on cushioned
             panels tested in accordance with ASTM E 90 and ASTM E 413        blocking in a dry and ventilated area, protected from humidity
             test procedures, and shall have achieved a STC rating as        and temperature extremes.
             specifi ed herein (see “Acoustical Performance” article listed
             under Part 2 – Products).                           1.08 SEQUENCING / SCHEDULING

        1.04 QUALITY ASSURANCE                                   A. Beam Punching: KWIK-WALL shall provide beam punching
                                                                      template drawing detailing the anchor locations for the
        A. The operable wall shall have been tested in an independent        suspended track system (as required for Drop Rod Mounting),
             acoustical testing laboratory in accordance with ASTM E 90 and        as required for the fabrication and installation of structural
             ASTM E 413 test procedures.                              overhead support by others.
        B. The operable wall panel construction and fi nish materials shall  B. Track Installation: Scheduling of operable wall track installation
             consist of Class A rated materials in accordance with ASTM E 84.       shall occur after structural overhead support has been properly
        C. The operable wall shall be installed by KWIK-WALL’s        and completely fabricated and installed by others.
             authorized distributor in accordance with ASTM E 557.  C. Panel Installation: Operable wall panel installation shall occur
                                                                      after fi xed wall substrate construction is properly and completely
        1.05 REFERENCES                                               installed by others, as required to protect panels from ongoing
        A. ASTM E 90: Laboratory Measurement of Airborne-Sound        adjacent construction.
             Transmission Loss of Building Partitions.
        B. ASTM E 413: Determination of Sound Transmission Class (STC).  1.09 WARRANTY
        C. ASTM E 557: Architectural Application and Installation of   A. KWIK-WALL shall warrant each operable wall panel and its
             Operable Partitions.                                    component parts to be free from defects in material and
                                                                     workmanship for a period of fi ve  years from the date of
        D. ASTM E 84: Surface Burning Characteristics of Building Materials.       delivery to the original purchaser, when installed by an authorized
        E. ASTM A 653: Specifi cation for General Requirements for Steel       KWIK-WALL distributor.  KWIK-WALL also warrants the fi xed top
             Sheet, Alloy-Coated (Galvannealed) by the Hot Dip Process.       seals, track, carriers, and its component parts to be free from
                                                                      defects in material and workmanship for a period of ten (10)
                                                                      years. (see actual warranty on Page 12 for details and limitations).