Operable Partitions
10 22 26 (10650) MODEL 3030 PART 1 - GENERAL SPECIFICATIONS
1.01 WORK INCLUDED
A. Operable Wall System shall be furnished, installed and serviced G. CCC-W-408A-D: Federal Specifi cation which applies to Vinyl
by KWIK-WALL's authorized distributor, in compliance with Coated Wall Coverings.
the architectural drawings and specifi cations contained herein. H. CFFA-W-101-B: Chemical Fabrics and Film Association Quality
Standard for Vinyl Coated Fabric Wall Coverings.
1.02 RELATED WORK
A. Structural Support: Structural support system required for 1.06 SUBMITTALS
suspending the operable wall shall be designed, installed and A. KWIK-WALL shall provide written technical information and
pre-punched by others, in accordance with ASTM E 557 and related detail drawings, which demonstrate that the products
KWIK-WALL's shop drawings. comply with contract documents for each type of operable
B. Insulation: Sound insulation and baffl es for the plenum area partition specifi ed.
above the track system, under the permanent fl oor, inside air B. KWIK-WALL shall provide detailed engineering drawings
ducts passing over or around the operable wall, and in permanent featuring track plan, panel elevation, horizontal and vertical
walls adjoining the operable wall system shall be by others, in details and beam punching template as required.
accordance with ASTM E 557.
C. KWIK-WALL shall provide written test report of the independent
C. Opening Preparation: Proper and complete preparation of the acoustical testing laboratory certifying the attainment of the
operable wall system opening shall be by others in accordance specifi ed STC rating, upon request.
with ASTM E 557, and shall include fl oor leveling; plumbness of
adjoining permanent walls; substrate and / or ceiling tile D. KWIK-WALL shall provide written instructions specifying the
enclosures for the track system; and the painting and fi nishing proper operation and maintenance of the operable wall system.
of trim and other materials adjoining the head and jamb areas of E. KWIK-WALL shall provide a color selector demonstrating the
the operable wall. Any permanent wall(s) receiving an adjustable manufacturer's selections of the specifi ed fi nish material. Samples
or fi xed wall jamb will require internal structural blocking in shall consist of actual swatches of the specifi ed fi nish material.
order to secure the jamb to the permanent wall. Refer to a copy
of the shop drawings for additional details. 1.07 DELIVERY, STORAGE AND HANDLING
A. Panels shall be individually wrapped in a protective plastic
1.03 SYSTEM DESCRIPTION covering to keep panels clean during delivery, storage
A. The operable wall system shall consist of Hinged Pairs operation, and handling.
featuring panels hinged together in evenly matched pairs (groups B. Panels shall be stored on edge and above the fl oor on cushioned
of two (2)), unless otherwise specifi ed. blocking in a dry and ventilated area, protected from humidity
B. The operable wall system shall consist of acoustically rated panels and temperature extremes.
tested in accordance with ASTM E 90 and ASTM E 413 test
procedures, and shall have achieved a STC rating as specifi ed 1.08 SEQUENCING / SCHEDULING
herein (see "Acoustical Performance" article listed under
Part 2 - Products). A. Beam Punching: KWIK-WALL shall provide beam punching
template drawing detailing the anchor locations for the
suspended track system (as required for Drop Rod Mounting), as
1.04 QUALITY ASSURANCE required for the fabrication and installation of structural overhead
A. The operable wall shall have been tested in an independent support by others.
acoustical testing laboratory in accordance with ASTM E 90 and B. Track Installation: Scheduling of operable wall track installation
ASTM E 413 test procedures. shall occur after structural overhead support has been properly
B. The operable wall panel construction and fi nish materials shall and completely fabricated and installed by others.
consist of Class A rated materials in accordance with ASTM E 84. C. Panel Installation: Operable wall panel installation shall occur
C. The operable wall shall be installed by the KWIK-WALL's after fi xed wall substrate construction is properly and completely
authorized distributor in accordance with ASTM E 557. installed by others, as required
1.05 REFERENCES 1.09 WARRANTY
A. KWIK-WALL shall warrant each operable wall panel and its
A. ASTM E 90: Laboratory Measurement of Airborne-Sound component parts to be free from defects in material and
Transmission Loss of Building Partitions. workmanship for a period of fi ve (5) years from the date of
B. ASTM E 413: Determination of Sound Transmission Class (STC). delivery to the original purchaser, when installed by an authorized
KWIK-WALL distributor. KWIK-WALL also warrants the fi xed
C. ASTM E 557: Architectural Application and Installation of top seals, track, carriers, and its component parts to be free from
Operable Partitions.
defects in material and workmanship for a period of ten (10)
D. ASTM E 84: Surface Burning Characteristics of Building Materials. years. (see actual warranty on Page 12 for details and limitations).
E. ASTM A 653: Specifi cation for General Requirements for Steel
Sheet, Alloy-Coated (Galvannealed) by the Hot Dip Process.
F. ASTM C 423: Standard Test Method for Sound Absorption and
Sound Absorption Coeffi cients by the Reverberation Room Method. 2
04-18
Dimensions in [ ] are millimeters. Contact your local distributor for additional assistance or visit www.kwik-wall.com