Page 13 - Priesgaisrine signalizacija FX 3NET_Schneider Electric_Projktavimo instrukcija_ENG
P. 13
Planning Instruction 66571758GB0 Fire Detection 13
4. Mechanical installation
4.1 Installation, FX 3NET and FXL 3NET control panels
The mounting surface must be flat and it must bear the
weight of the control panel and the chart file cabinet.
The weight of the control panel excl. batteries is 11 kg
and incl. batteries (2 x 17 Ah) 23 kg. The weight of the
chart file cabinet is 9 kg.
The mounting must be made directly on the wall surface,
without any distance bushings or similar, to ensure IP30
rating.
The weight of the battery cabinet excl. batteries is 7 kg
and incl. batteries (4 x 17 Ah) 31 kg.
FX control panel
Chart cabinet
Battery cabinet
© 2009 Schneider Electric. All rights reserved.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571758GB0 49 2011