Planning Instruction 66571759GB0 Fire Detection 3
1. System devices
Note! Technical information for the devices can be found in the data sheets.
1.1 Control equipment
Basic panels
FX 3NET Basic control panel without detection circuits. Expandable
to max. 8 detection circuits in steps of 2.
Number of card slots for option boards is 5.
FXL 3NET Basic control panel without detection circuits. Expandable
to max. 8 detection circuits in steps of 2.
Number of card slots for option boards is 9
Control panels FXM 3NET Basic control panel without detection circuits. Expandable
to max 4 detection circuits in steps of 2.
Number of card slots for option boards is 2.
FXS 3NET User interface panel without detection circuits and built-in
power supply. Needs power supply feed from an FX, FXL
or FXM panel.
One card slot for an option board.
Card slot option boards
FX-SLC Addressable loop controller: expansion 2 - > 4 or 4 - > 6 or
6 - > 8 loops
Loop controllers Maximum number of SLCs and CLCs together is 4
FX-CLC Expansion with 16 conventional loops.
Maximum number of SLCs and CLCs together is 4
FX-IOC For clean contact input monitoring, clean contact control
outputs and alarm device line outputs:
4 clean contact inputs
2 clean contact outputs
Input and/or Output 4 alarm device line outputs
controllers
FX-OCA 16 clean contact outputs
REPX-OB Protocol repeater
MCOX-OB Logical control unit
ZLPX-IC Zone Led Control Unit
UI2 option boards
Panel display unit FX-LB32 32 LED indications
Zone display unit FX-LB80 80 LED indications
© 2009 Schneider Electric. All rights reserved.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571759GB0 49 2011