Page 35 - Priesgaisrine signalizacija FX 3NET_Schneider Electric_Projktavimo instrukcija_ENG
P. 35


Planning Instruction 66571758GB0 Fire Detection 35



9. FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET Technical data

9.1 Technical data, standard panels

FX 3NET FXL 3NET FXM 3NET FXS 3NET
Dimensions (h*w*d) [mm] 578 x 425 x 130 328 x 425 x 130 328 x 417x79
Weight (fully equipped, excl. batteries) 11 kg 12 kg 6 kg 4.4 kg
IP Rating IP30
Operating ambient temperature +5…+40°C
Storage ambient temperature 0…+50°C
Maximum ambient humidity 95% RH
Backframe material sheet steel
Cover material plastic
Cover colour bluish grey
Number of SLC, CLC, IOC and OCA boards
- FX-SLC and/or FX-CLC together 4 4 2 1
- FX-IOC 4 4 2 1
- FX-OCA 4 4 2 1
- REPX-OB 1 1 1 1
- MCOX-OB 1 1 1 1
- ZLPX-IC 1 1 1 1
- FX-SLC, FX-CLC, FX-IOC, REPX-OB, 5 9 2 1
MCOX-OB, ZLPX-IC together
Number of addresses per detection circuit
Detector addresses 159
IO-module addresses 159
Total number of detectors and manual call 512 512 396
points connected to the panel
Mains supply voltage 230 VAC ±10% / 50 ... 60Hz NA
Mains supply power 160 VA 80 VA
Operating voltage range 21 ... 30 Vdc
Maximum current consumption in standby 1.0 A @ 24 Vdc 0.5 A @ 24 Vdc 0.5 A @ 24 Vdc
condition
Maximum current consumption in alarm 4.0 A @ 24 Vdc 2.2 A @ 24 Vdc 1 A @ 24 Vdc
condition
EN54-2
Applied standard EN54-2
EN54-4

Note! FXS 3NET requires a power feed from an FX 3NET, FXL 3NET or FXM 3NET panel. Available
power from that panel may restrict the current consumption of the FXS panel.