Page 15 - Fire Alarm-Submittal
P. 15
VM-PMI Paging Microphone Interface with EAEC D12LS-VM Control-Indicating Module provides additional
Emergency Audio Evacuation Controller Card provides operator interface capability. The module consists of 12 groups of two
controls for emergency voice/alarm communication and two-way LED-switches arranged as a top LED that is software programmable to
firefighters’ telephone communication. The VM-PMI consists of an audio amber, red, blue, or green, and a bottom amber LED.
mounting bracket, EAEC Emergency Audio Evacuation Controller card, Voltage 24 VDC
enclosure, and paging microphone.
Current 11 mA.
Standby
The EAEC Emergency Audio Evacuation Controller Alarm 11 mA plus 2.5 mA for each active LED, 58
mA max.
Card provides the audio source interface for emergency voice/alarm Operating environment
communication and two-way firefighters’ telephone communication. In Temperature 32 to 120°F (0 to 49°C)
addition, the card includes an RJ-11 connection for downloading an audio Relative humidity 0 to 93% noncondensing
database.
Voltage 24 VDC
Current ACHS Audio Channel Selector Card converts digital audio
Standby 23 mA from an EAEC card into an analog preamp signal. A VM-1 control panel
Alarm 29 mA supports up to three ACHS cards.
Remote microphone input Isolated and supervised Voltage 24 VDC
AUX input Current
Impedance 1 kΩ Standby 47 mA
Level 0.2 VRMS to 1.0 VRMS Alarm 64 mA
Frequency response 100 Hz to 4 kHz
Ground fault impedance 10 kΩ Circuit Class B (Style Y) or Class A (Style Z)
Designation
Wire size 18 to 12 AWG (0.75 mm² to 2.50 mm²) Output 1 VRMS analog signal
Audio channels 4 simultaneous Resistance 100 Ω max.
Audio inputs Capacitance 0.2 µF
Local microphone Isolated and supervised EOL resistor 15 kΩ
Remote microphone Isolated and supervised Wire size 18 - 12 AWG (0.75-2.50 mm²), twisted pair [1]
Firefighter telephone Isolated and supervised Amplifier capacity Fifteen AA30/50 amplifiers per ACHS
Remote audio Isolated and supervised Compatible controllers EAEC, AMK-RN, VM-MFK
Messages Operating environment
Storage 2 min Temperature 32 to 120°F (0 to 49°C)
Length 39 s max. Relative humidity 0 to 93% noncondensing
Controls and indicators
Common
Paging Volume Indicates relative signal strength during
active page Voice Evacuation in Sleeping Areas
Ready To Page Flashes during preannouncement tone, VM system audio components are system is part of an end-to-end low
steady when ready to page frequency solution listed to UL 464 and UL 864. The system is approved
Paging Microphone for code-compliant 520 Hz signaling in sleeping areas when used in con-
All Call Activates/deactivates page to all areas junction with:
All Call Minus Activates/deactivates page to areas not
receiving EVAC or Alert message • integrated voice audio capability
Page To Evac Activates/deactivates page to areas • a factory-supplied 520 Hz audio file
currently receiving EVAC message
Page To Alert Activates/deactivates page to areas • one or more Genesis High Fidelity speakers (G4HF or GCHF series)
currently receiving Alert message
Firefighter Phone Consult the VM Control Panel Compatibility List for details.
Page By Phone Activates/deactivates remote firefighter
telephone to paging channel
Buzzer Silence Silences call-in request buzzer
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93% noncondensing
Page 7 of 10 DA T A SHEET K85005-0138
Not to be used for installation purposes. Issue 1