Page 15 - Fire Alarm-Submittal
P. 15

VM-PMI Paging Microphone Interface with EAEC          D12LS-VM Control-Indicating Module provides additional
           Emergency Audio Evacuation Controller Card provides   operator interface capability. The module consists of 12 groups of two
           controls for emergency voice/alarm communication and two-way   LED-switches arranged as a top LED that is software programmable to
           firefighters’ telephone communication. The VM-PMI consists of an audio   amber, red, blue, or green, and a bottom amber LED.
           mounting bracket, EAEC Emergency Audio Evacuation Controller card,   Voltage  24 VDC
           enclosure, and paging microphone.
                                                                  Current             11 mA.
                                                                  Standby
           The EAEC Emergency Audio Evacuation Controller         Alarm               11 mA plus 2.5 mA for each active LED, 58
                                                                                      mA max.
           Card provides the audio source interface for emergency voice/alarm   Operating environment
           communication and two-way firefighters’ telephone communication. In   Temperature   32 to 120°F (0 to 49°C)
           addition, the card includes an RJ-11 connection for downloading an audio   Relative humidity  0 to 93% noncondensing
           database.
            Voltage               24 VDC
            Current                                              ACHS Audio Channel Selector Card converts digital audio
                  Standby         23 mA                          from an EAEC card into an analog preamp signal. A VM-1 control panel
                  Alarm           29 mA                          supports up to three ACHS cards.
            Remote microphone input  Isolated and supervised      Voltage           24 VDC
            AUX input                                             Current
                  Impedance       1 kΩ                                  Standby     47 mA
                  Level           0.2 VRMS to 1.0 VRMS                  Alarm       64 mA
                  Frequency response  100 Hz to 4 kHz
            Ground fault impedance  10 kΩ                         Circuit             Class B (Style Y) or Class A (Style Z)
                                                                        Designation
            Wire size             18 to 12 AWG (0.75 mm² to 2.50 mm²)        Output   1 VRMS analog signal
            Audio channels        4 simultaneous                        Resistance   100 Ω max.
            Audio inputs                                                Capacitance   0.2 µF
                  Local microphone   Isolated and supervised            EOL resistor  15 kΩ
                  Remote microphone   Isolated and supervised     Wire size         18 - 12 AWG (0.75-2.50 mm²), twisted pair [1]
                  Firefighter telephone   Isolated and supervised   Amplifier capacity  Fifteen AA30/50 amplifiers per ACHS
                  Remote audio    Isolated and supervised         Compatible controllers  EAEC, AMK-RN, VM-MFK
            Messages                                              Operating environment
                  Storage         2 min                                 Temperature  32 to 120°F (0 to 49°C)
                  Length          39 s max.                             Relative humidity  0 to 93% noncondensing
            Controls and indicators
            Common
                  Paging Volume   Indicates relative signal strength during
                                  active page                    Voice Evacuation in Sleeping Areas
                  Ready To Page   Flashes during preannouncement tone,   VM system audio components are system is part of an end-to-end low
                                  steady when ready to page      frequency solution listed to UL 464 and UL 864. The system is approved
            Paging Microphone                                    for code-compliant 520 Hz signaling in sleeping areas when used in con-
                  All Call        Activates/deactivates page to all areas   junction with:
                  All Call Minus   Activates/deactivates page to areas not
                                  receiving EVAC or Alert message   •   integrated voice audio capability
                  Page To Evac    Activates/deactivates page to areas   •   a factory-supplied 520 Hz audio file
                                  currently receiving EVAC message
                  Page To Alert   Activates/deactivates page to areas   •   one or more Genesis High Fidelity speakers (G4HF or GCHF series)
                                  currently receiving Alert message
            Firefighter Phone                                    Consult the VM Control Panel Compatibility List for details.
                  Page By Phone   Activates/deactivates remote firefighter
                                  telephone to paging channel
                  Buzzer Silence  Silences call-in request buzzer
            Operating environment
                  Temperature     32 to 120°F (0 to 49°C)
                  Relative humidity  0 to 93% noncondensing





















           Page 7 of 10                                                                 DA T A SHEET  K85005-0138
                                                                                 Not to be used for installation purposes.  Issue 1
   10   11   12   13   14   15   16   17   18   19   20