Page 120 - Programmable Logic Controllers, Fifth Edition - Mobile version
P. 120

Line side

                                                                  Load side          Line side
                                     Stationary                                                    Load side
                                      contacts

                                      Movable
                                      contacts



                                                                        Coil


                                         Movable iron
                                          armature or
                                             plunger

                                                                Line side


                                                                         Contacts
                                                        Coil
                                                                Load side
                                                              Wiring symbol
                                     Figure 6-5  Three-pole magnetic contactor.
                                     Source: Image Courtesy of Rockwell Automation, Inc.

                                                  Pump
                                                                         6.3  Motor Starters
                            Contactor power                              A motor starter is designed to provide power to motors.
                              contacts                                   The motor starter is made up of a contactor with an
                                                                         overload relay attached physically and electrically to it
                                                                         as illustrated in Figure 6-7. The function of the overload
                                                            L2
                                                                         relay can be summarized as follows:
                                                     High-current
                                                     wiring                •  Overload relays are designed to meet the special
                                                           L1                protective needs of motor control circuits.
                                                                           •  They allow harmless temporary overloads that occur
                                                                             when a motor starts.
                                         Coil
                                         terminals                         •  The overload relay will trip and disconnect power to
                                                                             the motor if an overload condition persists.
                                                                           •  Overload relays can be reset after the overload con-
                                                                             dition has been corrected.
                      Low-current                                          Figure 6-8 shows the diagram for a typical three-phase,
                          wiring
                                                                         magnetic motor starter. The operation of the circuit can be
                              L2     L1                                  summarized as follows:

                                                                           •  When the START button is pressed coil M is ener-
                                                                             gized closing all normally open M contacts.
                                       PLC output
                                        module                             •  The M contacts in series with the motor close to
                   Figure 6-6  Contactor used in conjunction with a PLC output.  complete the current path to the motor. These con-
                   Source: This material and associated copyrights are proprietary to, and used   tacts are part of the power circuit and must be de-
                   with the permission of Schneider Electric.                signed to handle the full load current of the motor.



                                            Developing Fundamental PLC Wiring Diagrams and Ladder Logic Programs  Chapter 6  101







          pet73842_ch06_098-130.indd   101                                                                              05/11/15   4:20 PM