Coverage of communications and control networks utilizes
                                                                                                 Scanner
               clear graphics to demonstrate how things work                  I/O Module         DeviceNet
                                                                                                 Module







                    Input        Ladder logic program  Outputs
               L1                I:1/3     O:2/5             L2
                         I:1/3                     O:2/5
                  OFF          Force> ON                                                    4-wire cable
                                                         ON
                                                                          Conventional system  and connector  DeviceNet system
                                O:2/5      O:2/6   O:2/6  M
                                                         ON
                                                                     BULLETED LISTS  break down processes to helpfully sum-
                   • The processor ignores the actual state of input limit  marize execution of tasks
                      switch I:1/3.
                   • Although limit switch I:1/3 is o  (0 or false) the
                     processor considers it as being in the on (1 or true)
                     state.
                   • The program scan records this, and the program is
                     executed with this forced status.
                   • In other words, the program is executed as if the
                      limit switch were actually closed.
                                                                                             Ladder logic
                                                                                    Timer_Sw
                                                                                   <Local:1:I.Data.6>
                                                                                             TON
                                                                                             Timer On Delay  EN
                                                                                             Timer  Status_Timer
                                                                                             Preset  10000  DN
                                                                                             Accum    0          Outputs L2
                                                                                                      EN_PL   EN_PL
                                                                                    Status_Timer.EN  <Local:2:O.Data.1>
                                                                      L1
                                                                            Input                             TT_PL
                                                                                                      TT_PL
                                                                                    Status_Timer.TT  <Local:2:O.Data.2>
                                                                            Timer_Sw
                                                                                                              DN_PL
               Diagrams, such as this one illustrating an overview of the func-                       DN_PL
               tion block programming language, help students put the pieces        Status_Timer.DN  <Local:2:O.Data.3>
               together
                                                                                           FBD equivalent
                                                                                            TONR_01
                                                                                             TONR  ...
                                                                                         Timer On Delay with Reset
                                                                                   0                 0
                                                                             Timer_Sw   TimerEnable  ACC  ACC_Value
                             Operation of the program can be viewed in real time     10000           0
                                                                                 10000  PRE        EN       EN_PL
                   Motor_Stop  Motor_Start   Track_Motor                                             0       TT_PL
                  <Local:1:I.Data.0>  <Local:1:I.Data.1>  <Local:2:O.Data.0>                       TT
                                                                                        Reset        0
                                                                                                   DN            DN_PL
                             Track_Motor     Enter_LS
                            <Local:2:O.Data.0>  <Local:1:I.Data.2>  Wash_In_Use  Figure 15-110  Comparison between ladder logic and the FBD equivalent for a
                                                        L             10 second TON and TONR timer.
                                                    Do_Not_Enter_Sign
                  Wash_In_Use                       <Local:2:O.Data.1>  •  When the Motor_Stop button is opened the output   •  Opening the Timer_Sw resets all outputs as well as
                                                              of the BAND block turns false to de-energize the   the accumulated value to zero.
                    Exit_LS                                   contactor coil and stop the motor.
                  <Local:1:I.Data.3>                  Wash_In_Use                                •  The timer can also be reset by way of the Reset
                                                         U                                         input.
                                                             Figure  15-110  shows  a  comparison  between  ladder
                                                           logic and the FBD equivalent for the 10 second TON (on-  Figure 15-111 shows a comparison between ladder logic
                                                           delay timer) and TONR (on-delay with reset). The opera-  and the FBD equivalent for the Up/Down counter used to
                      Discrete I/O
                                                           tion of the FBD can be summarized as follows:  limit the number of parts stored in a buffer zone to 50. The
                   Slot 1  Slot 2                                    More than  175 SLC-500 and ControlLogix
                                                                                                operation of the FBD can be summarized as follows:
                                                            •  When the Timer_Sw is closed, the TONR func-
                    00   00
                                                                   program simulation  videos tie
                                                              tion block timer turns true and starts accumulating d  directly to
                                                                                                 •  The CTUD up/down counter function block accu-
                    01   01
                                                              time.  the programs studied in the text  mulated value is initially reset by momentary actua-
                    02   02                                                                        tion of the Restart_Button.
                                                            •  The accumulated time is monitored by the output
                    03   03                                   reference tag named ACC.           •  The accumulated count is monitored by the output
                                                            •  The EN (enable bit) output changes to 1 to turn on   reference tag named ACC.
                                                              the EN_PL.                         •  Each time a part enters the buffer zone, the Enter_
                                                            •  The TT (timer timing bit) output changes to 1 to   Limit_Sw is actuated and the CUEnable input turns
                                                              turn on the TT_PL.                   true to increment the count by 1.
               xiv                                          •  The timer times out after 10 seconds to set the DN   •  Each time a part exits the buffer zone, the Exit_
                                                              (done bit) to 1 and turn on the DN_PL and reset the   Limit_Sw is actuated and the CDEnable input turns
                                                              TT bit to zero and turn off the TT_PL.  true to decrement the count by 1.
                                                            •  The EN bit and EN_PL remain on as long as the   •  Whenever the number of parts in the buffer zone
                                                              Timer_Sw stays toggled closed.       reaches 50 the DN bit is set to 1 and the output of
          pet73842_fm_i-xviii.indd   14                                                                                 05/11/15   4:15 PM
                                                                                                       Function Block Programming  Part 6   391