L1
                        L2                                      Power
                                                                mains
                         L3
                                                  Main disconnect switch


                                                 Step-down
                                                 isolation transformer
                   L1      Fuse          120                             L2
                                         VAC                                               PLC Control Panel
                                                    Machine      Master
                                                   start/stop
                     Emergency stop switches                     control
                                                    buttons       relay
                                                                  MCR
                      Emergency Overtravel       Stop    Start
                        stop      limit
                                 switch
                                                         MCR
                                   L1  L2  GND  PLC power
                                             supply


                      MCR
                                 PLC input module
                           L1  1  2  3  4  5  6  7  8  L2







                                PLC output module
                           L1  1  2  3  4  5  6  7  8  L2










                 Figure 9-22  Safety wiring requirements for a PLC installation.
                   Source: Courtesy Minarik Automation & Control.



                 •  A hardwired master control relay is included to pro-  indicators on the processor module can still be
                    vide a convenient means for emergency controller      observed.
                    shutdown. Because the master control relay allows   •  Note that the master control relay is not a substitute
                    the placement of several emergency-stop switches      for a disconnect switch. When you are replacing
                    in different locations, its installation is important   any module, replacing output fuses, or working on
                    from a safety standpoint.                             equipment, the main disconnect switch should be
                 •  Overtravel limit switches or mushroom head emer-      pulled and locked out.
                    gency stop pushbuttons are wired in series so that   The master control relay must be able to inhibit all
                    when one of them opens, the master control is    machine motion by removing power to the machine I/O
                    de-energized.                                    devices when the relay is de-energized. This hardwired
                 •  This removes power to input and output device    electromechanical component must not be dependent
                    circuits. Power continues to be supplied to the   on  electronic  components  (hardware  or software). Any
                    controller power supply so that any diagnostic   part can fail, including the switches in a master control



               198        Chapter 9  Program Control Instructions